Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-08-02 Cont ID  
Sent By dpalmer Date 1999-06-10 Time 11:01 Rev Time 0.25
Received By jgomez Date 1999-06-10 Time 11:01 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
 APPROVED BY D. PALMER. SEE APPLICATION
 NEED FAULT CURRENT CALCULATIONS FOR
 AIC RATING.215-5
 NEED COMPLETE RISER DIAGRAM.!!!
 SHOW CONDUIT SIZES,WIRE SIZES,GROUNDING
 ELECTRODE SYSTEM TO INCLUDE GROUND ROD,
 C.W.P,AND BLDG.STEEL.
 NEED LOAD CACULATION FOR EACH PANEL!
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:WP GFI RECEPTS.REQ`D FOR A/C EQUIP.
 ART.210-63
 NOTE:RECEPTS. LOCATED IN GARAGE ARE TO
 BE GFI OR GFI PROTECTED UNLESS
 DEICATED OUTLET.210-8-A-2
 NOTE:RECEPTS.REQ`D TO SERVE KITCHEN.
 ART`S 210-8-A-6,210-52C-1-2-3-4-5
 NOTE:210-52A 2`6`12`RULE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By jleech Date 1999-06-12 Time 11:21 Rev Time 0.50
Received By jleech Date 1999-07-31 Time 13:11 Sent To  
Notes
2001-01-08 00:00:00AC PLAN DOESNOT SHOW THIRD A/H.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-12-21 Cont ID  
Sent By tlarge Date 1999-12-21 Time 18:15 Rev Time 0.25
Received By tlarge Date 1999-12-21 Time 18:15 Sent To  
Notes
2001-01-08 00:00:00REVISED PLBG.RISER

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-07-31 Cont ID  
Sent By jleech Date 1999-06-12 Time 11:28 Rev Time 0.50
Received By jleech Date 1999-07-31 Time 13:12 Sent To  
Notes
2001-01-08 00:00:00PLUMING RISER NOT TO CODE.

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 1999-12-30 Cont ID  
Sent By jgomez Date 1999-12-30 Time 11:36 Rev Time 0.50
Received By jgomez Date 1999-12-30 Time 11:35 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 1999-12-01 Cont ID  
Sent By jgomez Date 1999-12-01 Time 14:27 Rev Time 0.50
Received By jgomez Date 1999-12-01 Time 14:27 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST FOR ROUND WINDOWS (MISSILE
 IMPACT GLAZING) AND STORE FRONT PRODUCT
 APPROVAL:
  
 1-ROUND WINDOW WITH IMPACT GLAZING:
 -PROVIDE COMPLETE SET OF DRAWINGS,
 SIGNED, DATED AND SEALED.
 -PROVIDE COMPLETE REPORTS FOR MISSILE
 IMPACT TESTS PERFORMED SIGNED, DATED
 AND SEALED.
 -PROVIDE COMPLETE ENGINEERING CALCS AND
 STIPULATE DESIGN CRITERIA AND BUILDING
 CODE USED (SBC OR SFBC-DADE COUNTY).
 -ARCHITECT OF RECORD TO APPROVEALL
 ENGINEERING TO VERIFY COMPLIANCE WITH
 HIS DESIGN.
 -PROVIDE COPIES OF SPECIFICATIONS FOR
 METRO DADE PROTOCOL PA 202 AND ANSI/
 AAMA 101-93 AS SPECIFIED IN TEST
 REPORT BY FENESTRATION TESTING LAB.
  
 2-STOREFRONT SYSTEM PRODUCT APPROVAL
 DOESN'T MATCH SYSTEM SPECIFIED ON
 ARCHITECT'S DRAWINGS. SEE LIMITATIONS
 ON PRODUCT APPROVAL (MAX. SIZE OF
 GLASS PANELS).
  
 NOTE:
 REVISE INSTALLATION SCHEDULE AND KEY
 PLAN ON STORM PANELS PERMIT NUMBER
 99-08-1274. IT DOESN'T MATCH THE
 ARCHITECT'S DRAWINGS.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 1999-10-19 Cont ID  
Sent By jgomez Date 1999-10-19 Time 17:16 Rev Time 1.00
Received By jgomez Date 1999-10-19 Time 17:16 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PRODUCT APPROVAL FOR GARAGE DOOR IS
 OK FOR 8'0" WIDE DOOR, BUT NEED PRODUCT
 APPROVAL REPORT FOR 16'0" WIDE DOOR.
 2-CLARIFY AREAS WHERE THIS STOREFRONT
 SYSTEM IS GOING TO BE INSTALLED.
 NOTE: THIS SYSTEM IS NOT GOOD FOR
 LIVING ROOM. CHECK SIZES SPECIFIED ON
 ARCHITECT'S DRAWINGS AND MAX SIZE
 ALLOWED BY THIS PRODUCT APPROVAL.
 3-PRODUCT APPROVAL FOR DOUBLE OUTSWING
 RESIDENTIAL DOORS IS EXPIRED.
 4-FROM PROVISO DATED 7/31/99:
 PROVIDE PRODUCT APPROVAL FOR ALL ROUND
 WINDOWS, FRENCH DOORS WITH SIDELITES
 ASSEMBLY, SLIDING GLASS DOORS WITH
 TRANSOM ASSEMBLY, BUTT GLAZING SYSTEM.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-10-14 Cont ID  
Sent By jgomez Date 1999-10-14 Time 18:45 Rev Time 0.50
Received By jgomez Date 1999-10-14 Time 18:45 Sent To  
Notes
2001-01-08 00:00:00REVIEW OF PRODUCT APPROVALS

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-07-31 Cont ID  
Sent By jgomez Date 1999-07-31 Time 14:49 Rev Time 3.00
Received By jgomez Date   Time   Sent To O
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO.
 1)PROVIDE PRODUCT APPROVAL FOR ROUND
 WINDOWS, MULLIONS, FRENCH DOORS WITH
 SIDELITES, EXTERIOR SIDE DOOR AT GARAGE,
 BUTT GLAZING SYSTEM.
 2)RESUBMIT PRODUCT APPROVAL FOR GARAGE
 DOORS.
 3)PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS, UNDER A SEPARATE PERMIT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-07-07 Cont ID  
Sent By jgomez Date 1999-07-07 Time 17:13 Rev Time 3.00
Received By jgomez Date   Time   Sent To D
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-04 Cont ID  
Sent By gjoyce Date 1999-05-04 Time 11:07 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved