| Plan Review Stops For Permit 99041302 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-06-10 |
Time |
11:01 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
1999-06-10 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************DENIED********************** | | | APPROVED BY D. PALMER. SEE APPLICATION | | | NEED FAULT CURRENT CALCULATIONS FOR | | | AIC RATING.215-5 | | | NEED COMPLETE RISER DIAGRAM.!!! | | | SHOW CONDUIT SIZES,WIRE SIZES,GROUNDING | | | ELECTRODE SYSTEM TO INCLUDE GROUND ROD, | | | C.W.P,AND BLDG.STEEL. | | | NEED LOAD CACULATION FOR EACH PANEL! | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:WP GFI RECEPTS.REQ`D FOR A/C EQUIP. | | | ART.210-63 | | | NOTE:RECEPTS. LOCATED IN GARAGE ARE TO | | | BE GFI OR GFI PROTECTED UNLESS | | | DEICATED OUTLET.210-8-A-2 | | | NOTE:RECEPTS.REQ`D TO SERVE KITCHEN. | | | ART`S 210-8-A-6,210-52C-1-2-3-4-5 | | | NOTE:210-52A 2`6`12`RULE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-07-31 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-06-12 |
Time |
11:21 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
1999-07-31 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | AC PLAN DOESNOT SHOW THIRD A/H. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
1999-12-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-12-21 |
Time |
18:15 |
Rev Time |
0.25 |
| Received By |
tlarge |
Date |
1999-12-21 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISED PLBG.RISER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-07-31 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-06-12 |
Time |
11:28 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
1999-07-31 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMING RISER NOT TO CODE. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
6 |
Status |
F |
Date |
1999-12-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-12-30 |
Time |
11:36 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
1999-12-30 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
F |
Date |
1999-12-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-12-01 |
Time |
14:27 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
1999-12-01 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST FOR ROUND WINDOWS (MISSILE | | | IMPACT GLAZING) AND STORE FRONT PRODUCT | | | APPROVAL: | | | | | | 1-ROUND WINDOW WITH IMPACT GLAZING: | | | -PROVIDE COMPLETE SET OF DRAWINGS, | | | SIGNED, DATED AND SEALED. | | | -PROVIDE COMPLETE REPORTS FOR MISSILE | | | IMPACT TESTS PERFORMED SIGNED, DATED | | | AND SEALED. | | | -PROVIDE COMPLETE ENGINEERING CALCS AND | | | STIPULATE DESIGN CRITERIA AND BUILDING | | | CODE USED (SBC OR SFBC-DADE COUNTY). | | | -ARCHITECT OF RECORD TO APPROVEALL | | | ENGINEERING TO VERIFY COMPLIANCE WITH | | | HIS DESIGN. | | | -PROVIDE COPIES OF SPECIFICATIONS FOR | | | METRO DADE PROTOCOL PA 202 AND ANSI/ | | | AAMA 101-93 AS SPECIFIED IN TEST | | | REPORT BY FENESTRATION TESTING LAB. | | | | | | 2-STOREFRONT SYSTEM PRODUCT APPROVAL | | | DOESN'T MATCH SYSTEM SPECIFIED ON | | | ARCHITECT'S DRAWINGS. SEE LIMITATIONS | | | ON PRODUCT APPROVAL (MAX. SIZE OF | | | GLASS PANELS). | | | | | | NOTE: | | | REVISE INSTALLATION SCHEDULE AND KEY | | | PLAN ON STORM PANELS PERMIT NUMBER | | | 99-08-1274. IT DOESN'T MATCH THE | | | ARCHITECT'S DRAWINGS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
1999-10-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-10-19 |
Time |
17:16 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
1999-10-19 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST: | | | 1-PRODUCT APPROVAL FOR GARAGE DOOR IS | | | OK FOR 8'0" WIDE DOOR, BUT NEED PRODUCT | | | APPROVAL REPORT FOR 16'0" WIDE DOOR. | | | 2-CLARIFY AREAS WHERE THIS STOREFRONT | | | SYSTEM IS GOING TO BE INSTALLED. | | | NOTE: THIS SYSTEM IS NOT GOOD FOR | | | LIVING ROOM. CHECK SIZES SPECIFIED ON | | | ARCHITECT'S DRAWINGS AND MAX SIZE | | | ALLOWED BY THIS PRODUCT APPROVAL. | | | 3-PRODUCT APPROVAL FOR DOUBLE OUTSWING | | | RESIDENTIAL DOORS IS EXPIRED. | | | 4-FROM PROVISO DATED 7/31/99: | | | PROVIDE PRODUCT APPROVAL FOR ALL ROUND | | | WINDOWS, FRENCH DOORS WITH SIDELITES | | | ASSEMBLY, SLIDING GLASS DOORS WITH | | | TRANSOM ASSEMBLY, BUTT GLAZING SYSTEM. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
1999-10-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-10-14 |
Time |
18:45 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
1999-10-14 |
Time |
18:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVIEW OF PRODUCT APPROVALS |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
1999-07-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-07-31 |
Time |
14:49 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
O |
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO. | | | 1)PROVIDE PRODUCT APPROVAL FOR ROUND | | | WINDOWS, MULLIONS, FRENCH DOORS WITH | | | SIDELITES, EXTERIOR SIDE DOOR AT GARAGE, | | | BUTT GLAZING SYSTEM. | | | 2)RESUBMIT PRODUCT APPROVAL FOR GARAGE | | | DOORS. | | | 3)PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS, UNDER A SEPARATE PERMIT |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
1999-07-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-07-07 |
Time |
17:13 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
D |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-05-04 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-05-04 |
Time |
11:07 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|