Plan Review Details - Permit 99040966
Plan Review Stops For Permit 99040966
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.25
Received By lsmith Date 1999-08-06 Time 09:51 Sent To  
Notes
2001-01-08 00:00:00FOUNDATION REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.25
Received By lsmith Date 1999-08-06 Time 09:52 Sent To  
Notes
2001-01-08 00:00:00STRUCTUAL & BLDG. REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-07-27 Cont ID  
Sent By hpiskura Date 1999-07-12 Time 15:02 Rev Time 3.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By hpiskura Date 1999-06-04 Time 08:32 Rev Time 1.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By hpiskura Date 1999-06-02 Time 11:37 Rev Time 1.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-07-27 Cont ID  
Sent By hpiskura Date 1999-06-02 Time 11:37 Rev Time 1.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-04-29 Cont ID  
Sent By bprusiec Date 1999-04-29 Time 11:17 Rev Time  
Received By bprusiec Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-06-23 Cont ID  
Sent By ndenmark Date 1999-06-23 Time 07:23 Rev Time 0.33
Received By ndenmark Date 1999-06-23 Time 07:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-05-12 Cont ID  
Sent By ndenmark Date 1999-05-12 Time 14:52 Rev Time 0.33
Received By ndenmark Date 1999-05-12 Time 14:52 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1) VENTILATION REQUIRED FOR OFFICE (TOOL
 ROOM) BEHIND OFFICE #6 ASHRAE 62-89
 2) AREAS WITH 300 CFM OR GREATER REQUIRE
 R/A FROM AREA
 3) NO COMBUSTIBLES PERMITTED IN RETURN
 AIR PLENUM INCLUDING PVC VENT MATERIAL
 4) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 PER 1994 SMC 406.1 WITH NOTIFICATION BY
 HORN AND STROBE OR TIED TO BLDG FIRE
 ALARM PER NFPA 90A 4-4.4.2 OR .3

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-09-20 Cont ID  
Sent By tlarge Date 1999-09-20 Time 09:44 Rev Time 0.33
Received By tlarge Date 1999-09-20 Time 09:44 Sent To  
Notes
2001-01-08 00:00:00REVISE SEWER SIZE.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-08-10 Cont ID  
Sent By pschmitz Date 1999-08-10 Time 14:10 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-06-26 Cont ID  
Sent By pschmitz Date 1999-06-26 Time 14:49 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00RESUBMIT:EQUIPMENT AREA DRAIN TO
 INTERCEPTOR ON SHT SP. PES

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-26 Cont ID  
Sent By pschmitz Date 1999-05-27 Time 10:17 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00SHOW WHERE EQUIPMENT AREA DRAIN CONNECTS
 TO SANITARY SEWER.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-04-26 Cont ID  
Sent By gjoyce Date 1999-04-26 Time 13:24 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***