Plan Review Details - Permit 99040478
Plan Review Stops For Permit 99040478
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-05-27 Cont ID  
Sent By jleahy Date 1999-05-27 Time 11:40 Rev Time  
Received By jleahy Date   Time   Sent To  
Notes
2001-01-08 00:00:00KITCHEN LTS/RECEPTS.NEED TO BE SEPARATED
 BATH LTS/RECEPTS.NEED TO BE SEPARATED
 ALSO!
 RECEPTS.IN KIT.EXT.IF THERES WORK DONE
 IN THAT AREA THEN THEY NEED TO BE ON
 20A CIRCUT.
 NEED COMPLETE RISER DIAGRAM TO SHOW
 PANEL/CONDUITS/WIRE SIZE/AND NEED NEW
 LOAD CALCULATION.215-5
 BATHS REFER TO 210-52D
  
 ALL INFORMATION IS REQ`D BEFORE ROUGH
 INSPECTION IS CALLED!!!!!!!!!! D.V.P.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-28 Cont ID  
Sent By ndenmark Date 1999-06-07 Time 15:12 Rev Time 0.25
Received By ndenmark Date 1999-06-07 Time 15:12 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 NO A/C PLANS SUBMIT PLANS FOR REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-23 Cont ID  
Sent By tlarge Date 1999-06-23 Time 11:35 Rev Time 0.50
Received By tlarge Date 1999-06-23 Time 11:35 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-28 Cont ID  
Sent By fcounter Date 1999-06-28 Time 14:08 Rev Time 1.00
Received By fcounter Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-18 Cont ID  
Sent By gjoyce Date 1999-04-15 Time 10:43 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO SURVEYCALLED 4-15-99