Plan Review Details - Permit 99040411
Plan Review Stops For Permit 99040411
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-09-21 Cont ID  
Sent By lsmith Date 1999-09-21 Time 12:31 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00FORMS/SLAB SURVEY DATED 8/31/99

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-05-03 Cont ID  
Sent By hpiskura Date 1999-05-03 Time 13:18 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS S-13, S-20, S-21 OK 6-29-99

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 08:45 Sent To  
Notes
2001-03-01 00:00:00REVISION FOR MAIN SERVICE RISER.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-11-20 Cont ID  
Sent By dpalmer Date 2000-11-20 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2000-11-20 Time 12:12 Sent To  
Notes
2001-01-08 00:00:00REVIEW FOR E2.2

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-17 Cont ID  
Sent By jleahy Date 2000-05-17 Time 14:30 Rev Time 1.00
Received By jleahy Date 2000-05-17 Time 14:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-10-05 Cont ID  
Sent By jleahy Date 1999-10-05 Time 13:56 Rev Time 0.30
Received By jleahy Date 1999-10-05 Time 13:49 Sent To  
Notes
2001-01-08 00:00:00CLUB HOUSE ELECTRICAL
 1) EMERGENCY BRANCH CIRCUITS NEDD A
 MEANS OF DISCONNECT AT CLUB HOUSE
  
 2) THIS/THESE DISCONNECTS ARE TO BE
 GROUPED WITH THE MAINS FOR CLUBHSE.
  
 3) PER225-8A

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-04-27 Cont ID  
Sent By hpiskura Date 1999-05-03 Time 13:18 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-05-03 Cont ID  
Sent By hpiskura Date 1999-05-03 Time 13:19 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-15 Cont ID  
Sent By mcarsill Date 2000-11-15 Time 08:38 Rev Time 0.00
Received By mcarsill Date 2000-11-15 Time 08:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-05-16 Cont ID  
Sent By rturnque Date 2000-05-16 Time 09:57 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-03-04 Cont ID  
Sent By hpiskura Date 1999-05-03 Time 13:19 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2000-03-06 Cont ID  
Sent By lsmith Date 2000-03-09 Time 08:25 Rev Time 1.00
Received By lsmith Date 2000-02-21 Time 08:24 Sent To  
Notes
2001-01-08 00:00:00SEE LETTER WITH DEFECIENCIES PER JIM
 MCELHENY, LANDSCAPE ARCHITECT P&Z

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2001-06-18 Cont ID  
Sent By pkrauss Date 2001-06-18 Time 12:40 Rev Time 0.35
Received By pkrauss Date 2001-06-18 Time 12:39 Sent To  
Notes
2001-06-18 00:00:00REVIEW NOTES FOR THIS REVISION UNDER
 MECHANICAL PERMIT99040402.

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2001-03-28 Cont ID  
Sent By pkrauss Date 2001-03-28 Time 13:08 Rev Time 0.30
Received By pkrauss Date 2001-03-28 Time 12:24 Sent To  
Notes
2001-03-28 00:00:00REVISION - 1ST FLOOR, CHANGE DUCT LAYOUT

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2001-03-15 Cont ID  
Sent By ndenmark Date 2001-03-15 Time 13:34 Rev Time 0.33
Received By ndenmark Date 2001-03-15 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2001-03-09 Cont ID  
Sent By pkrauss Date 2001-03-09 Time 08:28 Rev Time 0.45
Received By pkrauss Date 2001-03-09 Time 08:22 Sent To  
Notes
2001-03-09 00:00:00APPROVED - REVISIONS, CHANGED GRILLE
 SIZES AND CFM'S - AS BUILTS.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2001-01-19 Cont ID  
Sent By ndenmark Date 2001-01-19 Time 15:02 Rev Time 0.50
Received By ndenmark Date 2001-01-19 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2000-11-15 Cont ID  
Sent By ndenmark Date 2000-11-15 Time 17:42 Rev Time 0.33
Received By ndenmark Date 2000-11-15 Time 17:42 Sent To  
Notes
2001-01-08 00:00:00REVISION ON ELEVATOR LOBBY

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2000-05-15 Cont ID  
Sent By cthirben Date 2000-05-15 Time 08:59 Rev Time 1.00
Received By cthirben Date 2000-05-15 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2000-05-08 Cont ID  
Sent By cthirben Date 2000-05-08 Time 09:08 Rev Time 1.00
Received By cthirben Date 2000-05-08 Time 09:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-04-05 Cont ID  
Sent By cthirben Date 2000-04-05 Time 09:08 Rev Time 1.00
Received By cthirben Date 2000-04-05 Time 09:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 1999-11-15 Cont ID  
Sent By ndenmark Date 1999-11-15 Time 15:45 Rev Time 0.25
Received By ndenmark Date 1999-11-15 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 1999-09-30 Cont ID  
Sent By ndenmark Date 1999-09-30 Time 10:39 Rev Time 0.25
Received By ndenmark Date 1999-09-30 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-06-17 Cont ID  
Sent By ndenmark Date 1999-06-17 Time 07:36 Rev Time 0.33
Received By ndenmark Date 1999-06-17 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By ndenmark Date 1999-04-28 Time 13:42 Rev Time 0.33
Received By ndenmark Date 1999-04-28 Time 13:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 16 Status P Date 2000-11-16 Cont ID  
Sent By pschmitz Date 2000-11-16 Time 16:57 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 15 Status P Date 2000-11-04 Cont ID  
Sent By pschmitz Date 2000-11-04 Time 06:25 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION FOR RISERCLAMP ON SOVENT
 SYSTEM.

Review Stop P PLUMBING
Rev No 14 Status F Date 2000-10-21 Cont ID  
Sent By pschmitz Date 2000-10-21 Time 14:17 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 2 SUBMITTALS DATED 10-19-00
 RE: CANTILEVERED HANGERS TO SUPPORT
 SOVENT AIREATOR FITTING,IS NOT A
 ACCEPTABLE METHOD, SEE ATTACHED FROM
 SPC 94 SEC 310.1.1,310.2.1
  
 PLEASE SUBMIT INFORMATION AS STATED IN
 MEETING WITH STAFF FROM JPI AND
 MR KEN LOWERY KTD ENGINEERING ON THE
 JOB SITE 10-17-00 RE: HANGERS FOR THE
 SOVENT AIREATOR FITTING, TO USE A 4"
 RISER CLAMP ON EA FITTING WITH 2 3/8"
 RODS ATTACHED TO ABOVE DECK WITH
 FLUSH ANCHORS.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 13 Status P Date 2000-10-16 Cont ID  
Sent By tlarge Date 2000-10-16 Time 20:06 Rev Time 0.33
Received By pschmitz Date 2000-10-16 Time 20:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 12 Status P Date 2000-10-06 Cont ID  
Sent By tlarge Date 2000-10-06 Time 09:01 Rev Time 1.50
Received By pschmitz Date 2000-10-06 Time 09:01 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 PROVIDE FIRESAFING DETAILS AND UL
 ASSEMBLY NUMBER FOR PVC PENETRATIONS.
 (THE STACKS ON THE JOB ARE PVC.)
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 11 Status F Date 2000-09-05 Cont ID  
Sent By tlarge Date 2000-09-05 Time 15:07 Rev Time 4.75
Received By pschmitz Date 2000-09-05 Time 15:06 Sent To  
Notes
2001-01-08 00:00:001)THE MATERIALS USED FOR THE SOVENT
 SYSTEM SHALL MEET THE STANDARDS AND
 SPECIFICATIONS LISTED IN TABLE 703 OF
 THE SPC.THE CERTIFICATE OF COMPLIANCE
 FROM S.E.SPECIALTY LISTS 3 STANDARDS
 THAT ARE NOT CONTAINED IN SPC TABLE 703.
 ONE BEING "CISMA"177-85.MY CONCERNS
 REGARDING THIS STANDARD ARE AS FOLLOWS:
  
 )WHAT DO THE LETTERS "CISMA"REPRESENT
 AND IS THIS A NATIONALLY RECOGNIZED
 ORGANIZATION WITH THE AUTHORITY TO
 ISSUE SUCH DOCUMENTATION? SPC SEC.303.1,
 303.2,303.3.PROVIDE SUPPLEMENTAL SUPPORT
 DOCUMENTATION ON THIS ISSUE.
  
 B)PAGE ONE OF"CISMA DESIGNATION 177-85"
 NOTES"FOR DESIGN AND INSTALLATION
 STANDARDS REFER TO "CAST IRON SOVENT
 DESIGN MANUAL NO.802.MANUAL 802 IS
 PROPRIETARY TO CONINE MANUFACTURING.
 HOW CAN YOU COMPLY W/THIS"DESIGNATION"
 IF YOU ARE NOT INSTALLING CONINE
 FITTINGS?
  
 C)THE SUBMIITED "DESIGNATION"REFERS TO
 TABLES AND FIGURES WHICH ARE NOT
 ENCLOSED AND THEREFORE RENDER THIS ITEM
 INCOMPLETE AND UNACCEPTABLE.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.YOU MUST
 SUBMIT DOCUMENTATION FROM A PROFESSIONAL
 ENGINEER SHOWING HOW YOU COMPLY WITH
 THIS "DESIGNATION"IF PROPERLY SUBMITTED,
 AND IF IT IS ACCEPTED BY THIS DEPARTMENT
  
 2)STANDARD ASTM-126 IS FOR VALVE
 PRESSURE RETAINING PARTS,PIPE FITTINGS
 AND FLANGES AND DOES NOT APPLY TO
 SOVENT PLUMBING SYSTEMS.
  
 3)ASME/ANSI B16.45-1987-PLEASE SUBMIT A
 COPY OF THIS STANDARD AND DOCUMENTATION
 FROM A PROFESSIONAL ENGINEER VERIFYING
 COMPLIANCE.ALTHOUGH THIS STANDARD IS NOT
 LISTED IN THE SPC THE BUILDING OFFICIAL
 HAS THE AUTHORITY TO APPROVE SUCH METHOD
 OR MATERIAL ACCORDING TO THE MODEL
 COUNTYWIDE AMENDMENTS TO THE STANDARD
 CODES,1997 EDITION ADMINISTRATIVE AND
 SECOND AMENDMENTS TO THE 1994 PLUMBING
 CODE.
  
 4)THE DESIGN MANUAL NO.101 FROM SOUTH-
 EASTERN SPECIALTY & MANUFACTURING CO.
 CONTAINS THE COVER OF DESIGN MANUAL NO.
 802 FROM CONINE MANUF.AND ALSO A DESIGN
 GUIDE FROM THE CONINE MANUAL.SUBMIT
 PROOF OF AUTHORIZATION FROM CONINE
 MANUF.ALLOWING USE OF THEIR DESIGN
 MANUAL WITH YOUR SYSTEM.
  
 5)REMOVE THE APPLICATION GUIDELINES FOR
 A SPLIT SYSTEM AIR CONDITIONING SYSTEM
 FROM THE SOUTHEASTERN DESIGN MANUAL NO.
 101.THIS IS NOT APPLICABLE.
  
 6)THE LETTER FROM JIM STAHL DATED
 8/28/00 REFERS TO A CAST IRON SOVENT
 SYSTEM WHICH THIS IS NOT.IT IS A HYBRID
 SYSTEM CONSISTING OF PVC AND CAST IRON.
 THE FIRE SAFING DETAILS DO NOT ADDRESS
 PVC PIPING,THEREFORE THIS SYSTEM IS
 UNACCEPTABLE.COUNTYWIDE AMENDMENTS TO
 SBC SEC.104.2.4.
  
 7)DOCUMENTATION AND TEST RESULTS SHALL
 BE SUBMITTED FROM A PROFESSIONAL
 ENGINEER CLEARLY SHOWING HOW THE SOVENT
 FITTINGS MANUFACTURED BY SOUTHEASTERN
 SPECIALTY COMPLY W/CISPI STANDARD 301-82
 AND APPLICABLE STANDARDS REFERENCED IN
 TABLE 703 OF THE STANDARD PLUMBING CODE.
 THE CERTIFICATE OF COMPLIANCE FROM THE
 VICE PRESIDENT OF SOUTHEASTERN
 SPECIALTY IS UNACCEPTABLE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 10 Status F Date 2000-08-19 Cont ID  
Sent By pschmitz Date 2000-08-19 Time 09:16 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLBG PLAN REVIEW OF SINGLE STACK
 PLUMBING SYSTEM
 (1) SHT P1.5 NOTE I PROVIDE CUT SHT FOR
 PVC TO CI NO HUB BAND, THAT IS LISTED
 FOR A TRANSITION OF CI TO PVC PIPE.
 (2) SHTP1.5 PROVIDE A CUT SHT OF THE
 UNDERFLOOR CLAMP MODEL #USC 886 TO
 SUPPORT AERATOR FTG.AND HOW THIS IS TO
 BE ANCHORED IN CONCRETE.
 (3) SHT P1.5 PROVIDE A CUT SHT OF THE
 INSTALLATION OF THE PRO-SET BOX P4542HEZ
 4" SOVENT BOX.
 (4) SHT P1.5 NOTE # 8 SOVENT FITTING
 MANFACTURE STANDARD, PROVIDE INFORMATION
 ON CISMA DESIGNATION 177-85, STANDARD.
 (5) SHT PI.6 RISER 1-S & 5-S,CONNECTION
 OF SOIL OR WASTE BRANCHES BETWEEN THE
 PRL & THE STACK,SHALL BE MORE THAN 10
 PIPE DIAMETERS DOWN STREAM OF THE STACK.
 END OF COMMENTS,QUESTONS,CONTACT
 PAUL SCHMITZ 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 9 Status P Date 1999-10-05 Cont ID  
Sent By tlarge Date 1999-10-05 Time 10:58 Rev Time 0.75
Received By pschmitz Date 1999-10-05 Time 10:57 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY AND WATER FOR CLUBHOUSE
 (SHT.CP 1.1)

Review Stop P PLUMBING
Rev No 8 Status P Date 1999-09-18 Cont ID  
Sent By tlarge Date 1999-09-18 Time 11:07 Rev Time 0.75
Received By pschmitz Date 1999-09-18 Time 11:07 Sent To  
Notes
2001-01-08 00:00:00REVISIONS FOR SOVENT SYSTEM(TYPICAL
 BATHROOM GROUP.)

Review Stop P PLUMBING
Rev No 7 Status P Date 1999-09-13 Cont ID  
Sent By tlarge Date 1999-09-13 Time 07:42 Rev Time 1.00
Received By pschmitz Date 1999-09-13 Time 07:42 Sent To  
Notes
2001-01-08 00:00:00REVISE STORM,SANITARY & CONDENSATE LINES

Review Stop P PLUMBING
Rev No 6 Status P Date 1999-09-07 Cont ID  
Sent By tlarge Date 1999-09-07 Time 09:48 Rev Time 0.75
Received By pschmitz Date 1999-09-07 Time 09:48 Sent To  
Notes
2001-01-08 00:00:00REVISE U/G SAN.& STORM,COND.,RELIEF AND
 PAN DRAIN LINES.

Review Stop P PLUMBING
Rev No 5 Status P Date 1999-08-14 Cont ID  
Sent By tlarge Date 1999-08-14 Time 07:16 Rev Time 1.50
Received By pschmitz Date 1999-08-14 Time 07:16 Sent To  
Notes
2001-01-08 00:00:00MET W/ENGINEER ON 8/13/99 FOR 1.5 HRS.

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-08-14 Cont ID  
Sent By tlarge Date 1999-08-11 Time 12:30 Rev Time 1.00
Received By pschmitz Date 1999-08-11 Time 12:30 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A REVISED RISER FOR THE CHANGES
 TO THE UNDERGROUND SANITARY,CONDENSATE,
 AND WATER SYSTEMS.SHOW ALL LINES
 AFFECTED BY THESE CHANGES.SPC 104.2.1.
  
 PLANS SHOW POOL,SPA AND FOUNTAIN DRAIN
 PIPING.THIS WORK IS NOT COVERED UNDER
 THIS PERMIT.SPC 104.1.1.
  
 RISER S-1-SOVENT STACK TO REMAIN FULL
 SIZE THRU ROOF PER ASSE STANDARD 1043.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-09-13 Cont ID  
Sent By tlarge Date 1999-08-05 Time 15:38 Rev Time 0.75
Received By pschmitz Date 1999-08-05 Time 15:38 Sent To  
Notes
2001-01-08 00:00:00CHANGES HAVE BEEN MADE TO THE U/G DRAIN-
 AGE,CONDENSATE AND WATER SUPPLY SYSTEMS.
 A REVISED ISOMETRIC DRAWING SHALL BE
 SUBMITTED THAT REFLECTS ALL CHANGES TO
 THESE SYSTEMS.SPC 104.2.1.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-07-15 Cont ID  
Sent By tlarge Date 1999-07-15 Time 15:55 Rev Time 0.00
Received By pschmitz Date   Time 16:19 Sent To  
Notes
2001-01-08 00:00:00REVISIONS:REVISE COND.RISER,SHOW RISER
 FOR PAN DRAINS AND TP VALVES.
 `

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-04-27 Cont ID  
Sent By pschmitz Date 1999-04-27 Time 16:00 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE REVISIONS.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-03 Cont ID  
Sent By hpiskura Date 1999-05-03 Time 13:20 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***