| Plan Review Stops For Permit 99040392 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-09-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-05-26 |
Time |
14:19 |
Rev Time |
0.50 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK BY L SMITH 9/1/99 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-12 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-12 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2001-07-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-19 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-19 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2001-07-19 00:00:00 | ***************** UNSAT *************** | | | | | | PLEASE NOTE THAT THESE NOTES ARE IN | | | RESPONSE TO LETTER FROM MR. GEORGE PEREZ | | | | | | | | | 1)NOTE: RESPONSE TO NOTE#2 PLEASE NOTE | | | THAT NO PANEL SCHEDULES WERE SUBMITTED?? | | | PLEASE ALSO NOTE THAT THERE IS NOTHING | | | IN THE NEC OR LOCAL AMENDMENTS THAT DOES | | | NOT ALLOW #14AWG IN COMMERCIAL BLDG`S. | | | | | | 2)NOTE: IN RESPONSE TO NOTE #5 PLEASE | | | NOTE THAT HABITABLE ROOMS NEED TO SHOW | | | LIGHT FIXTURES. SOME ROOMS IN APTS STILL | | | SHOW "JB'S" WHER LTS SHOULD BE SHOWN. | | | 210-70 | | | | | | 3)NOTE: IN RESPONSE TO NOTE# 6. NO PANEL | | | SCHEDULES?? | | | | | | 4)NOTE: IN REPSONSE TO NOTE #8; FIRST | | | SET OF NOTES REFER TO LOCAL AMENDMENT | | | 210-50 REQ`S OUTLETS EVERY 20`. | | | | | | 5)NOTE: IN RESPONSE TO NOTE# 6; PLEASE | | | NOTE THAT NO BRANCH CIRCUIT #`S ARE | | | SHOWN ON PLANS AND NO PANEL SCHEDULE TO | | | CORRELATE? PLEASE SUBMIT. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-13 |
Time |
06:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-13 |
Time |
06:30 |
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | ****************UNSAT ***************** | | | | | | PLEASE NOTE: ELECTRCIAL PLANS ARE JUST | | | NOW BEING SUBMIITED FOR REVIEW. PLEASE | | | SEE THE FOLLOWING NOTES. | | | | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. FOR ALL APTS. | | | | | | 3) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 4) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. PLEASE SHOW | | | CLARIFICATION. | | | | | | 5) PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | YOU SHOW JB IN LOCATIONS OF WHICH MEANS | | | OF EGRESS LIGHTING IS REQ`D. | | | | | | 6)NOTE: PLANS NEED TO SHOW ALL BRANCH | | | CIRCUIT #`S ON PLANS. THESE NEED TO | | | CORRELATE WITH PANEL SCHEDULES. NEED TO | | | SUBMIT PANEL SCHEDULES FOR ALL PANELS. | | | PLANS ARE COMING IN AS "AS-BUILTS" ?? | | | | | | 7)NOTE: PLEASE NOTE PER 210-8 RECEPTS | | | SHOWN IN BATHROOMS DOWNSTAIRS NEED TO | | | BE SHOWN AS GFI/GFI PROTECTED. | | | | | | 8)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET LOCAL AMENDMENTS OF ART 210-50. | | | UPSTAIRS HALLWAYS. | | | | | | 9)NOTE: PLEASE SHOW LOCATIONS OF AHU`S. | | | | | | 11)NOTE:PLEASE LABEL APARTMENTS ON E- | | | SHEETS. | | | | | | 12)NOTE: PLEASE SEE TWO SWITCHES IN | | | REARAPT IN BEDROOM? GOING TO ??? | | | | | | 13)NOTE: PLEASE SEE 553-79-6A F.A.C. | | | REQUIRES SERVICES ON COMMERCIAL | | | PRODJECTS OF 800A OR MORE TO BE SIGNED | | | AND SEALED BY AN ENGINEER PER 471.025 | | | | | | PLEASE ADDRESS ALL OF THE ABOVE COMMENTS | | | AND SUBMIT FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS PERTAINING TO ANY OF THE ABOVE | | | PLEASE CALL FOR CLARIFICATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-11 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-11 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2001-01-11 00:00:00 | ************* UNSAT ********** | | | | | | 1)NOTE: PLEASE ADDRESS ORIG NOTES FROM | | | 6/25/99. PLEASE HAVE ORIG ENGINEER OF | | | RECORD EITHER ADDRESS PLANS OR RELEASE, | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-06-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-06-25 |
Time |
11:34 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
1999-05-18 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO ELECTRIC SHOWN, NEEDS ELECTRICAL | | | DRAWINGS | | | | | | 6/25/99******PROVISO*********** | | | NEED TO DRAW IN ALL SWITCH LEGS FOR | | | LIGHTING SWITCHES. | | | NOTE:RECEPTS.REQ`D 210-52 | | | NOTE:EGRESS LIGHTING.210-70 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-05-20 |
|
|
Cont ID |
|
| Sent By |
bprusiec |
Date |
1999-05-20 |
Time |
09:11 |
Rev Time |
|
| Received By |
bprusiec |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-09-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-08-27 |
Time |
12:57 |
Rev Time |
0.33 |
| Received By |
sgraham |
Date |
1999-08-27 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CONTRQCTOR TO BRING A/C PLANSNCD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-09-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-06-28 |
Time |
08:43 |
Rev Time |
0.33 |
| Received By |
sgraham |
Date |
1999-06-28 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1) NO OUTSIDE AIR CALCULATIONS SHOWN PER | | | ASHRAE 62-89 | | | 2) 2ND FL APTS A/CSUPPLY SHALL NOT | | | SERVE THE COMMON CORRIDOR PER 1994 SMC | | | 609.1.1 | | | 3) PROVIDE INFORMATION ON BATHROOM EX- | | | HAUST FANS AND VENT DUCT FOR THE SECOND | | | FLOOR | | | 4) DRYER VENT TO COMPLY WITH 1994 SMC | | | 509.1, 509.2 AND 509.4 COMMERCIAL EX- | | | HAUST AND SHALL NOT BE IN RATED WALL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2001-03-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-13 |
Time |
17:11 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-03-13 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2001-03-13 00:00:00 | DENIED; | | | | | | 1.KITCHEN SINK REQUIRED IN APARTMENTS. | | | 94 SPC 401.2.1 | | | | | | 2.A-2 UTILITY ROOM WATER HEATER SHOWS | | | GAS. SHEET E-1 SHOWS ELECTRIC.IS IT | | | GAS OR ELECTRIC? | | | | | | 3.SHOW A WATER RISER DIAGRAM. | | | | | | 4.SHOW A SANITARY RISER DIAGRAM FOR NEW | | | FIXTURES ADDED ON 2ND FLOOR. | | | | | | 5.WHAT TYPE OF PIPE WILL BE USED? WATER | | | AND DWV. | | | | | | 6.SPECIFY HANDICAP FIXTURES TO BE USED | | | IN HANDICAP BATHROOMS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
1999-08-31 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-08-31 |
Time |
09:48 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
1999-08-31 |
Time |
09:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-08-31 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-08-17 |
Time |
12:24 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
1999-08-17 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT COMPLETE GAS RISER DIAGRAM THAT | | | CLEARLY REFLECTS ENTIRE SCOPE OF WORK | | | BEING DONE.STD.GAS CODE SEC.302. | | | (SHOW TYPE OF PIPE,BTU LOAD,SUPPLY | | | PRESSURE,LOCATION OF METER,ETC.) | | | | | | SUBMIT COMPLETE WATER AND SANITARY | | | RISERS THAT CLEARLY SHOW SCOPE OF NEW | | | PLBG.WORK BEING DONE.SPC 104.2.1. | | | | | | PROVIDE CALCS.FOR COMBUSTION AIR FOR | | | GAS WTR.HTR.COMPLY W/STD.GAS CODE SEC. | | | 402. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-08-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-05-22 |
Time |
14:04 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | UNSAT: PROVIDE ISOMETRIC FOR DWV AND | | | WATER LINES ALSO LOCAION OF WATER | | | HEATER'S.PES | | | READ-- NOTES:UNSAT.06-26-99 2ND TIME | | | APPLIES TO ALL NEW PLUMBING WORK.PES |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-04-15 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-04-15 |
Time |
08:18 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|