Plan Review Details - Permit 99040339
Plan Review Stops For Permit 99040339
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-04 Cont ID  
Sent By jleahy Date 1999-05-27 Time 08:27 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
  
 NEED TO HAVE ELECTRICAL DISC.MEANS AT
 DETACHED BUILDING.225-8-A,B/250-24C
 NEED TO SHOW EXISTING SERVICE, COMPLETE
 RISER DIAGRAM SHOWING SIZE OF SERVICE,
 WIRE SIZE, LOAD CALCULATION AND LOAD
 BEING ADDED TO EXISTING PANEL.215-5
 NEED TO SHOW ALL ELECTRIC AT DETACHED
 BUILDING INCLUDING DISC. MEANS.!!!!!!

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-06-04 Cont ID  
Sent By fcounter Date 1999-06-04 Time 09:25 Rev Time 1.00
Received By fcounter Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-04-13 Cont ID  
Sent By gjoyce Date 1999-04-13 Time 10:03 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***