| Plan Review Stops For Permit 99040339 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-06-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-05-27 |
Time |
08:27 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | | | | NEED TO HAVE ELECTRICAL DISC.MEANS AT | | | DETACHED BUILDING.225-8-A,B/250-24C | | | NEED TO SHOW EXISTING SERVICE, COMPLETE | | | RISER DIAGRAM SHOWING SIZE OF SERVICE, | | | WIRE SIZE, LOAD CALCULATION AND LOAD | | | BEING ADDED TO EXISTING PANEL.215-5 | | | NEED TO SHOW ALL ELECTRIC AT DETACHED | | | BUILDING INCLUDING DISC. MEANS.!!!!!! |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-06-04 |
|
|
Cont ID |
|
| Sent By |
fcounter |
Date |
1999-06-04 |
Time |
09:25 |
Rev Time |
1.00 |
| Received By |
fcounter |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-04-13 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-04-13 |
Time |
10:03 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|