Plan Review Details - Permit 99040252
Plan Review Stops For Permit 99040252
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2000-04-06 Cont ID  
Sent By jgomez Date 2000-04-06 Time 13:25 Rev Time 0.25
Received By jgomez Date 2000-04-06 Time 13:25 Sent To  
Notes
2001-01-08 00:00:00REVIEW OF PRODUCT APPROVAL FOR EXTERIOR
 WINDOWS AND WINDOW MULLIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2000-04-04 Cont ID  
Sent By jgomez Date 2000-04-03 Time 17:22 Rev Time 0.50
Received By jgomez Date 2000-04-03 Time 17:22 Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVALS SUBMITTAL:
 1-PRODUCT APPROVAL FOR WINDOW MULLIONS
 ARE NOT ACCEPTABLE. THESE MULLIONS ARE
 TO BE INSTALLED WITH HURRICANE MISSILE
 IMPACT WINDOWS. THEREFORE, THE MULLION
 NEEDS TO BE TESTED FOR MISSILE IMPACT
 AS WELL. RESUBMIT PRODUCT APPROVAL.
  
 2-PRODUCT APPROVAL FOR DOOR NUMBERED #1
 NEED TO BE SIGNED, SEALED AND DATED
 BY THE PROFESSIONAL ENGINEER OF
 RECORD. AND, LEGIBLY PROVIDE THE NAME
 ADDRESS AND LICENSE NUMBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 1999-11-02 Cont ID  
Sent By jgomez Date 1999-11-02 Time 15:51 Rev Time 0.25
Received By jgomez Date 1999-11-02 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00FIRE RATED CEILING ASSEMBLY UL-P522.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 1999-10-21 Cont ID  
Sent By jgomez Date 1999-10-21 Time 18:51 Rev Time 0.25
Received By jgomez Date 1999-10-21 Time 18:51 Sent To  
Notes
2001-01-08 00:00:00REVIEW OF REVISION AT UNIT B-2 BY THE
 MASTER BEDROOM CLOSET AREA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 1999-10-02 Cont ID  
Sent By jgomez Date 1999-10-02 Time 13:32 Rev Time 1.00
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVIEW OF REVISIONS. JG. 10-2-99

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-08-14 Cont ID  
Sent By jgomez Date 1999-08-14 Time 14:59 Rev Time 2.00
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE 3 COPIES OF EACH UL FIRE RATED
 ASSEMBLY SPECIFIED.
 2-ATTIC ACCESS TO BE 22"X36" MIN. AS PER
 SEC. 2309.6 SBC 1994.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By jgomez Date 1999-04-26 Time 16:47 Rev Time 0.25
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00SPRINKLER SYSTEM TO BE 13, NOT 13R

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-28 Cont ID  
Sent By dpalmer Date 2000-03-28 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2000-03-28 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By jgomez Date 1999-04-28 Time 12:36 Rev Time  
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY JAKE. SEE APPLICATION

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By jgomez Date 1999-04-28 Time 12:36 Rev Time  
Received By jgomez Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-04-22 Cont ID  
Sent By bprusiec Date 1999-04-22 Time 09:11 Rev Time  
Received By bprusiec Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-05 Cont ID  
Sent By cthirben Date 2000-04-05 Time 09:15 Rev Time 1.00
Received By cthirben Date 2000-04-05 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By jgomez Date 1999-04-28 Time 12:37 Rev Time  
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY NANCY WITH PROVISO

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-08-16 Cont ID  
Sent By tlarge Date 1999-08-16 Time 16:04 Rev Time 0.75
Received By tlarge Date 1999-08-16 Time 16:04 Sent To  
Notes
2001-01-08 00:00:00SEPARATE PERMIT REQ'D.FOR FOUNTAINS.SPC
 104.1.1.
  
 PLANS REFER TO CIVIL DRWGS.FOR CONTIN-
 UATION OF FOUNTAIN DISCHARGE PIPING.
 SUBMIT CIVIL DRWGS.THAT CLEARLY SHOW
 PIPING.SPC 104.2.1.
  
 SUBMIT FOUNTAIN PLANS FOR REVIEW.SPC
 104.2.1.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-04-23 Cont ID  
Sent By pschmitz Date 1999-04-23 Time 13:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By jgomez Date 1999-04-28 Time 12:38 Rev Time  
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY GRACE