Plan Review Details - Permit 99040142
Plan Review Stops For Permit 99040142
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-05-18 Cont ID  
Sent By lmartine Date 1999-05-18 Time 10:02 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-05-18 Cont ID  
Sent By lmartine Date 1999-05-18 Time 11:07 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-04-13 Cont ID  
Sent By bprusiec Date 1999-04-13 Time 10:48 Rev Time  
Received By bprusiec Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE ALARM SYSTEM SHALL BE 15 DECIBELS
 ABOVE AMBIENT NOISE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-05-24 Cont ID  
Sent By ndenmark Date 1999-05-24 Time 10:49 Rev Time 0.25
Received By ndenmark Date 1999-05-24 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-05-24 Cont ID  
Sent By ndenmark Date 1999-05-04 Time 12:29 Rev Time 0.33
Received By ndenmark Date 1999-05-04 Time 12:29 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-06-07 Cont ID  
Sent By pschmitz Date 1999-05-22 Time 11:30 Rev Time 0.00
Received By jwitmer Date 1999-06-07 Time 08:32 Sent To  
Notes
2001-01-08 00:00:00PROVISO: SHT M-2, FD TRAP PRIMER.
 WTR. HTR TO BE READLY ACCESIBLE SPC94
 SEC 501.7PES.