Plan Review Details - Permit 99031607
Plan Review Stops For Permit 99031607
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-04-13 Cont ID  
Sent By ndenmark Date 1999-04-13 Time 15:50 Rev Time 0.33
Received By ndenmark Date 1999-04-13 Time 15:50 Sent To  
Notes
2001-01-08 00:00:00EXISTING DUCT TO BE INSPECTED FOR CLEAN-
 LINESS AND IF DEEMED NECESSARY CLEANED
 AND SANITIZED BY LICENSED MECHANICAL
 CONTRACTOR
 2)FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 PER 1994 SMC 406.1
 3)NOTIFICATION REQUIRED PER NFPA 90A 4-4
 .4.3 BY HORN AND STROBE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-13 Cont ID  
Sent By ndenmark Date 1999-03-31 Time 13:28 Rev Time 0.25
Received By ndenmark Date 1999-03-31 Time 13:28 Sent To  
Notes
2001-01-08 00:00:00INFORMATION NOT INCLUDED FOR COMPLETE
 REVIEW