Plan Review Details - Permit 99030754
Plan Review Stops For Permit 99030754
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-08-31 Cont ID  
Sent By dpalmer Date 1999-08-31 Time 13:02 Rev Time 0.00
Received By dpalmer Date 1999-08-31 Time 13:02 Sent To P
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:RISER DIAGRAM SHOWS 2#4`S PLEASE
 CORRECT AS #4 IS NOT RATED FOR 150AMPS
 ART:310-16
 2)NOTE:RISER DIAGRAM SHOWS 4/0 FOR GRND-
 ING ELECTRODE CONDUCTOR IN 1/2" CONDUIT.
 ALSO NEEDS TO SHOW GOING TO CWP AND
 BLDG.STEEL.250-81
 3)NOTE:MASTER BATH RECEPTS. TO BE GFI
 AND 20 AMP BRANCH CIRCUT ART210-52D
 4)NOTE:WP GFI REQ`D FOR A/C COND.UNIT
 AS PER ART: 210-63
 5)NOTE:MASTER BEDROOM MISSING RECEPT.
 AT DOOR REQ`D BY ART: 210-52
 6)NOTE: ART:210-8-A-6 REQ`SALL RECEPTS.
 SERVING KITCHEN COUNTER TO BE GFI AS PER
 NEC.
 7)NOTE:PANEL SCHEDULE SHOWS SMALL APPLI-
 -ANCE CIRCUT WITH #14 AWG.SMALL APPLI-
 -ANCE ARE REQ`D TO BE 20AMP THEREFORE
 WIRE NEEDS TO BE #12.ART:310-16
 NOTE OTHER CIRCUTS THAT ARE BEING
 PROTECTED BY 20AMP BRKS.ON #14 AWG.
 NEED TO CHANGE WIRE OR OVERCURRENT
 POTECTION.
  
 PLEASE NOTE THAT ALL THE ABOVE CHANGES
 NEED TO BE SUBMITTED AND APPROVED BEFORE
 FIRST ELECTRICAL ROUGH INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-05-14 Cont ID  
Sent By jgomez Date 1999-05-14 Time 10:41 Rev Time  
Received By jgomez Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By jleech Date 1999-09-02 Time 08:35 Rev Time 0.50
Received By jleech Date 1999-09-02 Time 08:35 Sent To  
Notes
2001-01-08 00:00:00NEED MODEL NUMBERS OF EQUIPMENT,SEER
 AND HEAT STRIP SIZE.
  
 SHOW RETURN AIR.
  
 MISSING A/C DROP IN EXERCISE ROOM.
  
 SHOW DRYER VENT.
  
 BATHROOM WINDOW MUST HAVE A CLEAR
 OPENING OF THREE SQ. FT. OR MORE OR A
 EXHAUST FAN MUST BE INSTALLED WITH A
 VENT TO THE OUTSIDE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-30 Cont ID  
Sent By jgomez Date 1999-05-14 Time 10:45 Rev Time 0.50
Received By cthirben Date 1999-11-30 Time 16:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-31 Cont ID  
Sent By tlarge Date 1999-08-31 Time 16:29 Rev Time 0.33
Received By tlarge Date 1999-08-31 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-05-14 Cont ID  
Sent By dpalmer Date 1999-08-31 Time 13:02 Rev Time  
Received By jgomez Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-11-30 Cont ID  
Sent By jgomez Date 1999-11-30 Time 14:31 Rev Time 1.50
Received By jgomez Date 1999-11-30 Time 14:31 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE 2 COPIES OF PRODUCT APPROVALS
 (BEFORE INSTALLATION) FOR: EXTERIOR
 DOORS, EXTERIOR WINDOWS, ROOF SHINGLES
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
 3-PROVIDE A COMPLETE STRUCTURAL SECTION/
 DETAIL FOR CONSTRUCTION OF ROOF
 CRICKET.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-09-08 Cont ID  
Sent By jgomez Date 1999-09-08 Time 15:43 Rev Time 2.00
Received By jgomez Date   Time   Sent To D
Notes
2001-01-08 00:00:00SECOND CHECKLIST:
 1-PROVIDE 2 COPIES OF ENERGY CALCULATION
 AND MANUAL "J" CALCULATIONS.
 2-PROVIDE ADEQUATE LIGHT AND VENTILATION
 AT MASTER BEDROOM AND LIVING AREA.
 SEC. 1203.1 AND 1203.1.4 SBC 1994.
 3-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1994.
 4-SPECIFY/CLARIFY HURRICANE TRUSS ANCHOR
 AT EXISTING WALL. CONNECTOR SPECIFIED,
 SIMPSON LTS 18, IS A WOOD TO WOOD
 CONNECTOR BUT THE CONNECTOR REQUIRED IS
 A WOOD TO CONCRETE BEAM.
 5-PROVIDE TWO COPIES OF CURRENT PRODUCT
 APPROVAL FOR: ALL EXTERIOR DOORS AND
 WINDOWS, STORM SHUTTERS, ROOF SHINGLES.
 6-PROVIDE ROOF SHEATHING FASTENING
 SPECIFICATIONS. TABLE 2306.1 CITY
 AMENDMENTS TO SBC 1994.
 7-PROVIDE COMPLETE COLUMN/SECTION DETAIL
 CLEARLY SPECIFY THE TOP PLATE SIZE AND
 BOLTS. INCLUDING CORNER COLUMN.
 *SPECIFY COLUMN TO BE USED.INCLUDING
 THICKNESS.
 *CLARIFY INSTALLATION OF COLUMN AT BASE
 AND PROVIDE UPLIFT CALCULATIONS.
 8-IDENTIFY LOCATION AND DIMENSIONS OF
 EACH SHEAR WALL SEGMENT AND SPECIFY
 ANCHORING AT EACH END.
 *SPECIFY SPECIAL ANCHORING AT CORNERS.
 SEC. 2310 SBC 1994.
 9-PROVIDE NAME AND ADDRESS OF ENGINEER
 OF RECORD OR ENGINEER'S BUSINESS LOGO.
 SEC. 104.2.2 CITY AMENDMENTS.
 10-*PAY IMPACT FEES TO THE COUNTY.
 *PAY ADDITIONAL FEES TO THE CITY
 $479.49 FOR RADON FEES & VALUATION
 11-PROVIDE SIZE AND REINFORCEMENT FOR
 CONCRETE EDGE AT REAR PORCH SLAB.
 12-PROVIDE COMPLETE SPECIFICATIONS FOR
 CONSTRUCTION OF CEILING AT REAR PORCH
 AS PER SEC. 2504.2 SBC 1994 (ASTM C926
 AND ASTM C1063).
 NOTE:SEE COMMENTS ON PLANS & MECHANICAL
 PLAN EXAMINER CHECKLIST.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-05-12 Cont ID  
Sent By jgomez Date 1999-05-12 Time 18:13 Rev Time  
Received By jgomez Date   Time   Sent To D
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-03-22 Cont ID  
Sent By gjoyce Date 1999-03-22 Time 16:04 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***