Plan Review Details - Permit 99030450
Plan Review Stops For Permit 99030450
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By lmartine Date 1999-06-01 Time 14:13 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-05-21 Cont ID  
Sent By lmartine Date 1999-05-18 Time 14:54 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-07-19 Cont ID  
Sent By lmartine Date 1999-06-01 Time 14:15 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-04-22 Cont ID  
Sent By bprusiec Date 1999-04-22 Time 09:08 Rev Time  
Received By bprusiec Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-05-05 Cont ID  
Sent By ndenmark Date 1999-05-05 Time 10:53 Rev Time 1.00
Received By ndenmark Date 1999-05-05 Time 10:53 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 1)ALL DUCTS PENETRATING RATED WALLS TO
 HAVE FIRE DAMPERS UNLESS PROVISIONS OF
 1994 SMC 610.1.3 ARE COMPLIED WITH
 2) SERVICE ACCESS FOR ELECTRIC ON MECH-
 ANICAL EQUIPMENT TO COMPLY WITH THE NAT-
 IONAL ELECTRIC CODE (36")
 3) ALL AHU'S IN AREAS WITH 2000 CFM OR
 GREATOR TO HAVE FAN SHUT DOWN BY DUCT
 SMOKE DETECTORS WITH NOTIFICATION BY
 BLDG FIRE ALARM OR HORN AND STROBE PER
 1996 NFPA 90A 4-4.4.2 OR .3

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-06-07 Cont ID  
Sent By tlarge Date 2000-06-07 Time 12:13 Rev Time 0.33
Received By tlarge Date 2000-06-07 Time 12:13 Sent To  
Notes
2001-01-08 00:00:00REVISED IRRIG.PLANS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-05-02 Cont ID  
Sent By tlarge Date 2000-05-02 Time 08:09 Rev Time 0.33
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO:SHOWER STALL SHALL COMPLY W/
 FACBC SECS.4.21.1-4.21.6.SUBMIT MANUF.
 SHEETS FOR STALL PRIOR TO INSP.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-03-29 Cont ID  
Sent By tlarge Date 2000-03-29 Time 15:06 Rev Time 0.00
Received By tlarge Date 2000-03-29 Time 15:06 Sent To  
Notes
2001-01-08 00:00:00SUBMIT MANUF.SHEETS FOR SHOWER STALL.
 STALL SHALL COMPLY W/FACBC SECS.4.21.1-
 4.21.8.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-04-30 Cont ID  
Sent By pschmitz Date 1999-04-30 Time 15:23 Rev Time 1.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: SEE SHT M-1&2.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-21 Cont ID  
Sent By lmartine Date 1999-04-05 Time 14:55 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved