Plan Review Details - Permit 99030153
Plan Review Stops For Permit 99030153
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-03-23 Cont ID  
Sent By bprusiec Date 1999-03-23 Time 13:07 Rev Time 0.00
Received By fcounter Date 1999-04-28 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT & SHOP DRAWINGS FOR FIRE
 ALARM & FIRE SPRINKLER SYSTEMS REMODEL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-29 Cont ID  
Sent By ndenmark Date 1999-03-09 Time 10:55 Rev Time 0.00
Received By hpiskura Date 1999-04-28 Time 12:50 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*****************
 1)PROVIDE OUTSIDE AIR CALCULATIONS FOR
 AREA PER ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1994
 SMC 501.2
 3) PROVISO: ALL DUCTS PENETRATING RATED
 WALLS TO BE PROTECTED PER 1994 SMC 610.1
 4) PROVISO: EXISTING DUCT TO BE INSPECT-
 ED FOR CLEANLINESS AND IF DEEMED NECESS-
 ARY, CLEANED AND SANITIZED BY LICENSED
 MECHANICAL CONTRACTOR

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-24 Cont ID  
Sent By pschmitz Date 1999-03-24 Time 10:52 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***