Plan Review Details - Permit 99020854
Plan Review Stops For Permit 99020854
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 1999-07-12 Cont ID  
Sent By hpiskura Date 1999-07-12 Time 12:52 Rev Time 4.00
Received By hpiskura Date 1999-07-12 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-04-12 Cont ID  
Sent By hpiskura Date 1999-04-12 Time 13:33 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 1999-07-13 Cont ID  
Sent By dpalmer Date 1999-07-13 Time 12:39 Rev Time 0.00
Received By dpalmer Date 1999-07-13 Time 12:39 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
  
 NOTE:2ND REVIEW.STILL NO LIGHTING SHOWN
 FOR STORAGE AREAS AS REQ`D PER TABLE
 220-3B WAREHOUSES.
 NOTE:NO ELECTRICAL RISER DIAGRAM SHOWN!!
 NEED TO SHOW SERVICE TO INCLUDE RISER,
 METER,PANELS,ALL CONDUITS,WIRE SIZES,
 GROUNDING SYSTEM.FAULT CURRENT CALCULAT-
 IONS FOR AIC RATING OF EQUIPMENT.
 ALL THE ABOVE IS TO BE DONE AS PER ART:
 215-5
 NOTE:NEED TO SHOW LOAD CALCULATIONS AND
 PANEL SCHEDULES.
 NOTE:PAGENOTE MISSING RECEPTS.AS PER
 210-52A
 NOTE: RECEPTS. SERVING KITCHEN COUNTER
 ARE TO BE GFI/GFI PROTECTED AS PER ART:
 210-8-A-6
 NOTE:RECEPT.REQ`D FOR A/C COND. UNIT
 AS PER 210-63
 NOTE:GROUNDING ELECTRODE CONDUCTOR TO
 BLDG.STEEL ALSO.
 NOTE: SMOKE DETECTORS REQ`D INSIDE AND
 BEDROOMS AS PER NFPA-72

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-04-06 Cont ID  
Sent By hpiskura Date 1999-07-12 Time 12:54 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 1999-02-24 Cont ID  
Sent By hpiskura Date 1999-07-12 Time 12:53 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-03-16 Cont ID  
Sent By bprusiec Date 1999-03-16 Time 17:17 Rev Time 0.00
Received By bprusiec Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE 20' FIRE DEPT ACCESS LANE INTO
 PROJECT. PROVIDE S/D BETWEEN B/R'S OF
 APT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-01 Cont ID  
Sent By ndenmark Date 1999-04-01 Time 07:33 Rev Time 0.50
Received By ndenmark Date 1999-04-01 Time 07:33 Sent To  
Notes
2001-01-08 00:00:00EXHAUST DUCT TO BE RUN PER 1994 SMC 503.
 3.1
 DRYER VENT DUCT TO BE RUN PER 509.1

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-25 Cont ID  
Sent By pschmitz Date 1999-03-25 Time 14:27 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***