Plan Review Details - Permit 99020720
Plan Review Stops For Permit 99020720
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-06-25 Cont ID  
Sent By hpiskura Date 1999-04-05 Time 10:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-06-08 Cont ID  
Sent By hpiskura Date 1999-04-05 Time 10:44 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-06-07 Cont ID  
Sent By bprusiec Date 1999-06-07 Time 16:20 Rev Time 0.00
Received By bprusiec Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE 1 HR. FIRE PROTECTION TO ALL
 OPENINGS 10 FEET HORIZONTALLY AND 10 FEE
 T ABOVE DINGLE MEANS OF EGRESS FROM 2ND
 FLOOR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-06-02 Cont ID  
Sent By ndenmark Date 1999-06-02 Time 14:38 Rev Time 0.50
Received By ndenmark Date 1999-06-02 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-06-02 Cont ID  
Sent By ndenmark Date 1999-03-08 Time 11:23 Rev Time 1.00
Received By ndenmark Date 1999-03-08 Time 11:23 Sent To  
Notes
2001-01-08 00:00:00**********DENIED********************
 1) NO INFORMATION INCLUDED FOR THE AIR
 HANDLING OR CONDENSING UNITS.
 2) ALL DUCTS PENETRATING RATED WALLS OR
 CEILINGS TO BE PROTECTED PER 1994 SMC
 610
 3)NEED OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 4) NEED AIR BALANCE INFORMATION PER 1994
 SMC 501.2
 5) PROVIDE INFORMATION ON EXHAUST FANS
 6)VENTILATION REQUIRED PER ASHRAE 62-89
 FOR ALL ROOMS INCLUDING STORAGE.
 7) EXHAUST DUCTS IN RATED WALLS TO BE
 PROTECTED PER 1994 610.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-11 Cont ID  
Sent By pschmitz Date 1999-03-11 Time 09:17 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-06-25 Cont ID  
Sent By hpiskura Date 1999-06-25 Time 12:54 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00AJ ON APP HHP


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved