| Plan Review Stops For Permit 99020713 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-04 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE MASTER PLANS FOR APPROVAL BY JAKE, |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-03-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-03-08 |
Time |
13:47 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-03-08 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **********PROVISO*********************** | | | RETURN AIR LOCATION IS WITHIN 10 FEET OF | | | COOKING EQUIPMENT, THIS IS ACCEPTABLE IN | | | THE 1994 SMC, IT IS EXPECTED THAT THE | | | 1997 SMC WILL BE ADOPTED IN JUNE, 1999 | | | AND THIS LOCATION WILL NO LONGER BE AC- | | | CEPTABLE PER 1997 SMC 409. ANY PERMITS | | | ISSUED AFTER THIS WILL REQUIRE COMPLIANC | | | WITH THIS SECTION OF THE CODE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-03-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-03-13 |
Time |
09:41 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
8 |
Status |
P |
Date |
2000-04-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-04-04 |
Time |
19:00 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2000-04-04 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | PERMIT TYPE ON SCREEN #1 WAS CHANGED | | | FROM BLD-RES TO MASTER TO ALLOW PERMITS | | | TO BE PRINTED. ORIGINAL PERMIT | | | APPLICATION WAS SUBMITTED FOR A BLD-RES | | | AND LATER ON THE APPLICANT WANTED TO GET | | | A MASTER PERMIT. SUCH CHANGE WAS NEVER | | | REVISED ON THIS SCREEN. THEREFORE, I HAD | | | TO CHANGE THE PERMIT TYPE TO AVOID MORE | | | CONFUSION AND BE ABLE TO REFER TO THIS | | | MASTER AS THE MASTER FOR TYPE V MODEL, | | | INCLUDING STORM PANELS. J.G. 4-4-00. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
7 |
Status |
F |
Date |
1999-10-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-10-28 |
Time |
18:42 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
1999-10-28 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | CHECKLIST FOR PROVISO GIVEN ON 10/15/99: | | | 1-PROVIDE COMPLETE SPECIFICATIONS AND | | | DETAILS FOR CONSTRUCTION OF CEILING AT | | | PORCH. SEC 104.2.2 CITY AMENDMENTS. | | | NOTE: ALCOA RIGID VINYL SIDING AND | | | SOFFIT PRODUCT APPROVAL DOESN'T | | | INCLUDE INSTALLATION AT PORCHE'S | | | CEILING. | | | 2-SPECIFY ATTIC VENTILATION FOR NEW | | | SOFFIT SYSTEM AS PER SEC 2309.7 SBC/94 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
6 |
Status |
P |
Date |
1999-10-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-10-15 |
Time |
14:54 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
1999-10-15 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | VINYL SIDING PRODUCT APPROVAL PROVISO: | | | 1-PROVIDE MANUFACTURER'S INSTALLATION | | | SPECIFICATIONS. | | | 2-PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS FOR INSTALLATION AT | | | PORCH'S CEILING. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
1999-10-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-10-08 |
Time |
13:24 |
Rev Time |
0.75 |
| Received By |
jgomez |
Date |
1999-10-08 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED TRUSSES. JG. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
1999-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-10-07 |
Time |
09:48 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
1999-10-07 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ROOF SHINGLES PRODUCT APPROVAL. JG. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
1999-09-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-09-30 |
Time |
13:43 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS: | | | TYPICAL FLOOR TO FLOOR TIE INSTALLATION | | | | | | MODEL V - PERMIT #S: | | | 99-06-0223 | | | 0224 | | | 0204 | | | 0216 | | | 0225 | | | 0191 | | | 0195 | | | 0214 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
1999-09-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-09-18 |
Time |
14:21 |
Rev Time |
1.30 |
| Received By |
jgomez |
Date |
1999-09-18 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CHECKLIST - MODEL V: | | | 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS | | | DRAWINGS PRIOR TO SUBMITTAL TO THIS | | | OFFICE. | | | 2-ENGINEERED TRUSSES: REVISE MEAN ROOF | | | HEIGHT.THIS IS A TWO STORY BUILDING. | | | REMAINDER THERE IS ONLY ONE MEAN ROOF | | | HEIGHT FOR ENTIRE BUILDING. | | | 3-PROVIDE COMPLETE DETAIL AND SPECS FOR | | | LEDGER TO RECEIVE ROOF TRUSSES AT | | | FRONT PORCH. SEC 104.2.2 CITY AMENDMEN | | | 4-PROVIDE COMPLETE SECTIONS/DETAILS FOR | | | TWO STORY WALL SECTIONS. SPECIFY ALL | | | CONNECTORS. SHEARWALLS. TRANSITION | | | FROM FIRST FLOOR TO SECOND FLOOR. NOTE | | | THAT THERE ARE TWO CONDITIONS: ONE | | | WHEN EXTERIOR WALL IS PERPENDICULAR TO | | | 2ND FLOOR FRAMING AND ONE WHEN IT'S | | | PARALLEL. | | | 5-CHECK/REVISE IF ALL HURRICANE ANCHORS | | | SPECIFIED WILL BE ABLE TO RESIST THE | | | HORIZONTAL LOADS SPECIFIED BY THE | | | ENGINEERED TRUSSES. | | | 6-CLARIFY NOTE #1 ON ENGINEERED TRUSSES. | | | FOR EXAMPLE, TRUSS JO5 AT FRONT PORCH | | | SAYS IF PORCHES EXIST, THERE ARE NOT | | | EXPOSED TO WIND. WHY? | | | WHAT DOES DOL STANDS FOR? | | | REVISE DESIGN CRITERIA DATA ON TRUSS | | | LAYOUT. IT DOESN'T MATCH DESIGN | | | CRITERIA SHOWN ON ENGINEERED TRUSSES. | | | 7-PROVIDE A COMPLETE DETAIL FOR ALUMINUM | | | CEILINGS AT PORCH. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-04-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
1999-04-08 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
O |
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO |
|
|