| Plan Review Stops For Permit 99020063 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-07-05 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-03-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-03-30 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1]COUNTY IMPACT FEES ARE REQUIRED | | | 2]SUBMIT MANUFACTURE SPECS.FOR CHAIRLIFT | | | 3]ALL DOORS MUST COMPLY WITH FL.ACCESS. | | | REQUIREMENT FOR MANUVERING CLEARENCES | | | SEE SECT.4.13.6 | | | 4]SUBMIT DETAIL AT FLOOR/CEILING CUT FOR | | | CHAIRLIFT | | | 5]MINIMUM CLEAR STAIR WIDTH IS 36" | | | 6]PROVIDE WIDOWS WALK DETAILS | | | 7]RECEPTION DESK MUST BE ACCESSIBLE S.A4 | | | 8]SUBMIT COMPLETE ROOF INFORMATION | | | 9]SHEET A.3,NORTH ELEVATION,PROVIDE | | | DETAIL FOR NEW CANOPY AND OPENINGS TO | | | BE FILLED IN | | | 10]PROVIDE HARDWARE SCHEDULE FOR DOORS | | | 11]SECTION 4.8.3,REQUIRES THE RAMP TO BE | | | MIN.44"CLEAR WIDTH | | | 12]SUBMIT PRODUCT TESTING FOR EXTERIOR | | | DOORS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
1999-02-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
1999-02-22 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2000-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-07 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-07 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** NOTE ****************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT NON ELECTRICAL | | | WAS SUBMITTED FOR REVIEW. PLEASE SEE | | | ATTACHED NOTES FOR PREVIOUS REVIEW AND | | | THOSE NOTES NOT BEING SUBMITTED YET. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-07-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-05 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-05 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** PROVISIO ************* | | | | | | 1)NOTE: PLEASE SEE THE REQ`MENTS OF | | | ART 240-21-B-1 FOR TAPPED CONDUCTORS | | | 10` RULE. | | | | | | PLEASE SUBMIT A REVISED RISER DIAGAM | | | BEFORE THE ROUGH ELECTRICAL INSPECTION. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-03-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-04-07 |
Time |
13:30 |
Rev Time |
|
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
1999-09-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-04-07 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-03-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-09-03 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2000-10-28 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-28 |
Time |
11:48 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-28 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2000-09-15 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-10 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
ndenmark |
Date |
2000-07-10 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: ******************************* | | | 1. PROVIDE CFM VALUE FOR EACH SUPPLY | | | DROP. | | | NEED ROOM CALCS SHOWING LOAD ON SYSTEM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2000-07-06 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-06 |
Time |
08:19 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-06 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | REVIEW NOTES DONE ON 03.20.00 HAS NOT | | | CHANGED OR ADDRESSED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2000-03-20 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-03-20 |
Time |
12:49 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-03-20 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | ***************DENIED******************* | | | | | | 1. NO INFO ON OUTSIDE AIR PER ASHRAE | | | 62-89 | | | 2. ACU-1 TOTAL CFM=1850 | | | ACU-2 TOTAL CFM=2300 | | | SPEC'S FOR THESE UNITS SHOW 1585 CFM | | | PER UINT SMC 104.2 | | | 3. EF #1 DETAIL DIFFERS FROM EF #1 ON | | | NOTE #5 FOR CFM FOR THIS FAN. | | | 4. EXHAUST AIR FROM 1ST FLOOR BATHROOM | | | TO MIN. 10 FT. FROM OUTSIDE AIR | | | INTAKE FOR ACU'S SMC 506.1 | | | 5. DUCTS UNDER HOUSE TO BE A MIN. OF 4" | | | ABOVE GROWN PER 1997 SMC 605.4. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
1999-08-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-08-30 |
Time |
13:05 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
1999-08-30 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO CORRECTIONS TO PREVIOUS CHECKLIST |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
1999-02-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-02-22 |
Time |
14:17 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-02-22 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO INFORMATION PROVIDED FOR OUTSIDE AIR | | | PER ASHRAE 62-89 | | | ACU-1 TOTAL CFM =1850ACU-2 TOTAL CFM= | | | 2300SPEC'S FOR THESE UNITS SHOW 1585 | | | CFM PER UNIT SMC 104.2 | | | EF#1 DETAIL DIFFERS FROM EF#1 NOTE #5 | | | FOR CFM FOR THIS FAN | | | EXHAUST AIR FROM 1ST FL BATHROOM TO MIN. | | | 10' FROM O/A INTAKE FOR ACU'S SMC 506.1 | | | DUCTS UNDER HOUSE TO BE MIN.4" ABOVE | | | GROUND PER 1994 SMC 605.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-03-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-03-04 |
Time |
12:40 |
Rev Time |
|
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-02-02 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-02-02 |
Time |
14:24 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|