Plan Review Details - Permit 99020063
Plan Review Stops For Permit 99020063
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-07-05 Cont ID  
Sent By lmartine Date 2000-07-05 Time 10:28 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-03-30 Cont ID  
Sent By lmartine Date 2000-03-30 Time 15:14 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001]COUNTY IMPACT FEES ARE REQUIRED
 2]SUBMIT MANUFACTURE SPECS.FOR CHAIRLIFT
 3]ALL DOORS MUST COMPLY WITH FL.ACCESS.
 REQUIREMENT FOR MANUVERING CLEARENCES
 SEE SECT.4.13.6
 4]SUBMIT DETAIL AT FLOOR/CEILING CUT FOR
 CHAIRLIFT
 5]MINIMUM CLEAR STAIR WIDTH IS 36"
 6]PROVIDE WIDOWS WALK DETAILS
 7]RECEPTION DESK MUST BE ACCESSIBLE S.A4
 8]SUBMIT COMPLETE ROOF INFORMATION
 9]SHEET A.3,NORTH ELEVATION,PROVIDE
 DETAIL FOR NEW CANOPY AND OPENINGS TO
 BE FILLED IN
 10]PROVIDE HARDWARE SCHEDULE FOR DOORS
 11]SECTION 4.8.3,REQUIRES THE RAMP TO BE
 MIN.44"CLEAR WIDTH
 12]SUBMIT PRODUCT TESTING FOR EXTERIOR
 DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-02-22 Cont ID  
Sent By jwitmer Date 1999-02-22 Time 11:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2000-12-07 Cont ID  
Sent By dpalmer Date 2000-12-07 Time 14:24 Rev Time 0.00
Received By dpalmer Date 2000-12-07 Time 14:24 Sent To  
Notes
2001-01-08 00:00:00*************** NOTE ******************
  
  
 1)NOTE: PLEASE NOTE THAT NON ELECTRICAL
 WAS SUBMITTED FOR REVIEW. PLEASE SEE
 ATTACHED NOTES FOR PREVIOUS REVIEW AND
 THOSE NOTES NOT BEING SUBMITTED YET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 11:36 Sent To  
Notes
2001-01-08 00:00:00***************** PROVISIO *************
  
 1)NOTE: PLEASE SEE THE REQ`MENTS OF
 ART 240-21-B-1 FOR TAPPED CONDUCTORS
 10` RULE.
  
 PLEASE SUBMIT A REVISED RISER DIAGAM
 BEFORE THE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-03-03 Cont ID  
Sent By hpiskura Date 1999-04-07 Time 13:30 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By hpiskura Date 1999-04-07 Time 13:31 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-03-04 Cont ID  
Sent By lmartine Date 1999-09-03 Time 11:18 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2000-10-28 Cont ID  
Sent By ndenmark Date 2000-10-28 Time 11:48 Rev Time 0.50
Received By ndenmark Date 2000-10-28 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2000-09-15 Cont ID  
Sent By cthirben Date 2000-07-10 Time 15:04 Rev Time 0.00
Received By ndenmark Date 2000-07-10 Time 15:09 Sent To  
Notes
2001-01-08 00:00:00PROVISO: *******************************
 1. PROVIDE CFM VALUE FOR EACH SUPPLY
 DROP.
 NEED ROOM CALCS SHOWING LOAD ON SYSTEM

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2000-07-06 Cont ID  
Sent By cthirben Date 2000-07-06 Time 08:19 Rev Time 1.00
Received By cthirben Date 2000-07-06 Time 08:15 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 REVIEW NOTES DONE ON 03.20.00 HAS NOT
 CHANGED OR ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2000-03-20 Cont ID  
Sent By cthirben Date 2000-03-20 Time 12:49 Rev Time 1.00
Received By cthirben Date 2000-03-20 Time 12:39 Sent To  
Notes
2001-01-08 00:00:00 
 ***************DENIED*******************
  
 1. NO INFO ON OUTSIDE AIR PER ASHRAE
 62-89
 2. ACU-1 TOTAL CFM=1850
 ACU-2 TOTAL CFM=2300
 SPEC'S FOR THESE UNITS SHOW 1585 CFM
 PER UINT SMC 104.2
 3. EF #1 DETAIL DIFFERS FROM EF #1 ON
 NOTE #5 FOR CFM FOR THIS FAN.
 4. EXHAUST AIR FROM 1ST FLOOR BATHROOM
 TO MIN. 10 FT. FROM OUTSIDE AIR
 INTAKE FOR ACU'S SMC 506.1
 5. DUCTS UNDER HOUSE TO BE A MIN. OF 4"
 ABOVE GROWN PER 1997 SMC 605.4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 1999-08-30 Cont ID  
Sent By ndenmark Date 1999-08-30 Time 13:05 Rev Time 0.33
Received By ndenmark Date 1999-08-30 Time 13:05 Sent To  
Notes
2001-01-08 00:00:00NO CORRECTIONS TO PREVIOUS CHECKLIST

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-02-22 Cont ID  
Sent By ndenmark Date 1999-02-22 Time 14:17 Rev Time 0.50
Received By ndenmark Date 1999-02-22 Time 14:17 Sent To  
Notes
2001-01-08 00:00:00NO INFORMATION PROVIDED FOR OUTSIDE AIR
 PER ASHRAE 62-89
 ACU-1 TOTAL CFM =1850ACU-2 TOTAL CFM=
 2300SPEC'S FOR THESE UNITS SHOW 1585
 CFM PER UNIT SMC 104.2
 EF#1 DETAIL DIFFERS FROM EF#1 NOTE #5
 FOR CFM FOR THIS FAN
 EXHAUST AIR FROM 1ST FL BATHROOM TO MIN.
 10' FROM O/A INTAKE FOR ACU'S SMC 506.1
 DUCTS UNDER HOUSE TO BE MIN.4" ABOVE
 GROUND PER 1994 SMC 605.4

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-04 Cont ID  
Sent By lmartine Date 1999-03-04 Time 12:40 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-02-02 Cont ID  
Sent By gjoyce Date 1999-02-02 Time 14:24 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***