Plan Review Details - Permit 99011147
Plan Review Stops For Permit 99011147
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-06-17 Cont ID  
Sent By hpiskura Date 1999-04-06 Time 16:04 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-10-05 Cont ID  
Sent By dpalmer Date 1999-10-05 Time 11:01 Rev Time 0.00
Received By dpalmer Date 1999-10-05 Time 11:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-03-31 Cont ID  
Sent By hpiskura Date 1999-04-06 Time 16:04 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 1999-04-06 Cont ID  
Sent By hpiskura Date 1999-04-06 Time 16:04 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-03-11 Cont ID  
Sent By bprusiec Date 1999-03-11 Time 10:39 Rev Time  
Received By bprusiec Date   Time   Sent To  
Notes
2001-01-08 00:00:00F/A SHALL BE 15 DECIBELS ABOVE AMBIENT
 NOISE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 1999-05-22 Cont ID  
Sent By ndenmark Date 1999-05-21 Time 12:13 Rev Time 1.00
Received By fcounter Date 1999-05-21 Time 12:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-05-21 Cont ID  
Sent By ndenmark Date 1999-03-18 Time 13:19 Rev Time 0.50
Received By pschmitz Date 1999-03-18 Time 13:19 Sent To  
Notes
2001-01-08 00:00:00***************UNSAT*******************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1994
 SMC 501.2
 3) FIRE DAMPERS REQUIRED AT ALL PENETRA-
 TIONS OF RATED WALLS
 4) OVERFLOW PROTECTION REQUIRED ON ALL
 UNITS PER 1994 SMC 304.8.6
 5) SERVICE ACCESS TO EQUIPMENT TO BE PER
 1994 SMC AND 1996 NEC
 (6)SHT M-2 A/C CONDENSATE TO RWL NOT
 APPROVED, RUN SEPERATE SYSTEM TO STORM
 DRAIN,DRY WELL OR PLANTER OUT SIDE OF
 BIULDING.NOTE BY PES 05-22-99

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-23 Cont ID  
Sent By pschmitz Date 1999-03-13 Time 13:30 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00FACILITIES EXISTING. PES

Review Stop Z ZONING
Rev No 1 Status P Date 1999-03-01 Cont ID  
Sent By gjoyce Date 1999-03-01 Time 13:29 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***