Plan Review Details - Permit 99011147
| Plan Review Stops For Permit 99011147 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-06-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-04-06 |
Time |
16:04 |
Rev Time |
|
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
1999-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-05 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-10-05 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-03-31 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-04-06 |
Time |
16:04 |
Rev Time |
|
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
1999-04-06 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-04-06 |
Time |
16:04 |
Rev Time |
|
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-03-11 |
|
|
Cont ID |
|
| Sent By |
bprusiec |
Date |
1999-03-11 |
Time |
10:39 |
Rev Time |
|
| Received By |
bprusiec |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | F/A SHALL BE 15 DECIBELS ABOVE AMBIENT | | | NOISE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
1999-05-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-05-21 |
Time |
12:13 |
Rev Time |
1.00 |
| Received By |
fcounter |
Date |
1999-05-21 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-05-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-03-18 |
Time |
13:19 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
1999-03-18 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************UNSAT******************* | | | 1) PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2) PROVIDE AIR BALANCE SCHEDULE PER 1994 | | | SMC 501.2 | | | 3) FIRE DAMPERS REQUIRED AT ALL PENETRA- | | | TIONS OF RATED WALLS | | | 4) OVERFLOW PROTECTION REQUIRED ON ALL | | | UNITS PER 1994 SMC 304.8.6 | | | 5) SERVICE ACCESS TO EQUIPMENT TO BE PER | | | 1994 SMC AND 1996 NEC | | | (6)SHT M-2 A/C CONDENSATE TO RWL NOT | | | APPROVED, RUN SEPERATE SYSTEM TO STORM | | | DRAIN,DRY WELL OR PLANTER OUT SIDE OF | | | BIULDING.NOTE BY PES 05-22-99 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-03-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-03-13 |
Time |
13:30 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FACILITIES EXISTING. PES |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-03-01 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-03-01 |
Time |
13:29 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |