Plan Review Details - Permit 99010917
Plan Review Stops For Permit 99010917
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-05-04 Cont ID  
Sent By hpiskura Date 1999-05-04 Time 08:02 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00MEZZ REQ 125# LL FOR STORAGE USE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-02-23 Cont ID  
Sent By ndenmark Date 1999-02-23 Time 12:57 Rev Time 0.50
Received By ndenmark Date 1999-02-23 Time 12:57 Sent To  
Notes
2001-01-08 00:00:001.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2.PROVIDE AIR BALANCESCHEDULE PER 1994
 SMC 501.2
 3.DUCT DETECTORS TO BE TIED IN TO BLDG
 FIRE ALARM SYSTEM PER NFPA 90A 4-4.4.2
 OR IF NO BLDG SYSTEM, HORN AND STROBE
 TO BE INSTALLED FOR NOTIFICATION PER
 NFPA90A 4-4.4.3

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-02-20 Cont ID  
Sent By pschmitz Date 1999-02-20 Time 12:59 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***