Plan Review Details - Permit 99010496
Plan Review Stops For Permit 99010496
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By hpiskura Date 1999-03-19 Time 16:30 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 11:20 Sent To  
Notes
2001-01-08 00:00:00SHEET E-8

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-06-02 Cont ID  
Sent By dpalmer Date 2000-06-02 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2000-06-02 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 20:20 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE!!!!! FIRST NOTE THE LAST PAGE OF
 NOTE SENT OUT BY THE CHIEF ELECTRICAL
 INSPECTOR.HIS NOTES ARE ATTACHED.
 WE DO HAVE RECORD OF YOU PULLING YOUR
 LOW VOLTAGE FOR FIRE ALARM AND FOR FOUR
 DATA OUTLETS. THERE IS STILL NO PERMIT
 PULLED FOR TELEPHONE SYSTEM. THIS MUST
 BE DONE!! THE PLANS ARE SHOWING TELE.
  
  
 2)NOTE: PLEASE CHECK YOUR ELECTRICAL
 RISER DIAGRAM E-16. YOU WILL NOTE THAT
 YOU SHOW 7-SETS OF 500MCM FROM FPL TO
 MAIN GUTTER. HOWEVER LINE FROM GUTTER
 SHOW CONDUCTORS HOW 8-500`S ? WHICH ONE?
 PLEASE CORRELATE.215-5
  
 3)NOTE; ALSO YOU ARE SHOWING THE AIC
 RATINGS FOR MOST EQUIPMENT. WHAT ABOUT
 THESIX MAINS FROM FPL? 1OF6,2OF6,3OF6
 ,,,,,ETC. IF THESE ARE FUSED DISC.S
 PLEASE LIST AIC RATING OF FUSES THAT ARE
 BEING INSTALLED. ABOVE FROM 215-5
  
  
 PLEASE TAKE CARE OF THE PERMIT SITUATION
 AND ADDRESS THE ABOVE COMMENTS.
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372 OR THE
 CHIEF ELEC. INSPEC. AT EXT.8451

Review Stop E ELECTRICAL
Rev No 3 Status P Date 1999-12-07 Cont ID  
Sent By jleahy Date 1999-12-07 Time 09:20 Rev Time 0.00
Received By jleahy Date 1999-12-07 Time 09:23 Sent To  
Notes
2001-01-08 00:00:001-CHECKING OUR RECORDS THE CITY SHOWS
 THAT THERE ARE NO LOW VOLTAGE
 PERMITS FOR ANY LOW VOLTAGE SYSTEMS
  
 2-FIRE ALARM, TELEPHONES, COMPUTERS,
 SOUND SYSTEMS ECT. ECT. ARE SOME OF
 THE TYPES THAT REQUIRE A SEPERATE
 PERMIT !!!!!!!!!!!!!!!!!!!!!!!!!!!
  
 3-PLEASE CHECK YOUR RECORDS TO SEE IF
 YOUR SUBS HAVE THE PROPER PERMITS!!
  
 4-AGAIN THESE LOW VOLTAGE PERMITS ARE
 REQUIRED AND ARE NOT INCLUDED WITH
 THE MASTER PERMIT CHECK YOUR PERMIT
 IT STATES WHAT IS INCLUDED!!!!!!!

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-10-04 Cont ID  
Sent By jleahy Date 1999-10-04 Time 14:49 Rev Time 0.45
Received By jleahy Date 1999-10-04 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-02-23 Cont ID  
Sent By hpiskura Date 1999-03-19 Time 16:30 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2000-05-04 Cont ID  
Sent By mgonzale Date 2000-05-04 Time 15:07 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00SHEET C-3 SHOWS SIGN ON TOP OF SANITARY
 SEWER EASEMENT.SING MUST BE OUTSIDE OF
 UTILITY EASEMENTS.
 PLEASE REVISE PLAN AND RESUBMIT THIS
 SHEET FOR APPROVAL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-05-05 Cont ID  
Sent By hpiskura Date 1999-03-19 Time 16:31 Rev Time 0.50
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00STORM CKLST

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 13:57 Rev Time 0.00
Received By mcarsill Date 2000-09-29 Time 13:56 Sent To  
Notes
2001-01-08 00:00:001) EXIT DOORS SHOULD SWING IN THE
 DIRECTION OF EXIT TRAVEL. IF OCCUPANT
 LOADS ARE EXPECTED TO BE FIFTY OR MORE
 PERSONS FROM A PARTICULAR AREA, THEN
 THE EXIT DOORS MUST SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 08:36 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) SMOKE BOMB PLAN ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2000-06-19 Cont ID  
Sent By rturnque Date 2000-06-19 Time 10:35 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-04-28 Cont ID  
Sent By rturnque Date 2000-04-28 Time 14:56 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-03-28 Cont ID  
Sent By rturnque Date 2000-03-28 Time 10:41 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 1999-11-21 Cont ID  
Sent By rturnque Date 1999-11-21 Time 12:55 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-01-28 Cont ID  
Sent By hpiskura Date 1999-03-19 Time 16:31 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00HORN/STROBE CIRCUIT SHALL BE CLASS "A"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 08:07 Rev Time 0.25
Received By ndenmark Date 2000-10-21 Time 08:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-05-05 Cont ID  
Sent By ndenmark Date 2000-05-05 Time 11:33 Rev Time 0.00
Received By cthirben Date 2000-05-25 Time 12:12 Sent To  
Notes
2001-01-08 00:00:00REVISION ^15 OKAY

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-03-22 Cont ID  
Sent By ndenmark Date 2000-03-22 Time 07:00 Rev Time 1.00
Received By ndenmark Date 2000-03-22 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-12-14 Cont ID  
Sent By ndenmark Date 1999-12-14 Time 06:54 Rev Time 0.33
Received By ndenmark Date 1999-12-14 Time 06:54 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 ALL LOUVERED DOORS THRU RATED WALLS TO
 BE PROTECTED BY FIRE DAMPERS IN LOUVERED
 DOORS
 ALL FLOOR/CEILING PENETRATIONS OF DUCTS
 TO BE PROTECTED BY METHODS COMPLYING W/
 THE DESIGN OF THE ASSEMBLY OR BY CEILING
 FLOOR DAMPERS SPECIFICALLY DESIGNED AND
 LISTED FOR THIS TYPE SERVICE PER 1997
 SMC 610.2 AND 610.4 SHAFT ENCLOSURES

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-04-28 Cont ID  
Sent By ndenmark Date 1999-02-18 Time 13:24 Rev Time 0.50
Received By ndenmark Date 1999-02-18 Time 13:24 Sent To  
Notes
2001-01-08 00:00:001ST FL "B" ZONE HAS NO AIR PATH FOR S/A
 TO GET TO E/A FAN IN OFFICE AREA
 NEED MORE COMPLETE SEQUENCE OF OPERATION
 ON SMOKE EVAC. INCL. CFM PER FLOOR
 AIR BALANCE SCHEDULE NEEDED FOR O/A TO
 EXHAUST AIR PER 1994 SMC 501.2

Review Stop P PLUMBING
Rev No 9 Status P Date 2000-10-14 Cont ID  
Sent By tlarge Date 2000-10-14 Time 06:08 Rev Time 0.65
Received By tlarge Date 2000-10-14 Time 06:08 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 SHT.A-14-HANDICAP DETAILS-WATER CLOSET
 SHALL BE 17"-19" AFF.NOT 19"MAX.PER
 FACBC SEC.4.16.3.,4.17.2.
  
 TOILET PAPER DISPENSERS SHALL BE 19"TO
 CENTERLINE,NOT TO BOTTOM OF DISPENSER.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 8 Status P Date 2000-05-08 Cont ID  
Sent By tlarge Date 2000-05-08 Time 08:15 Rev Time 0.33
Received By tlarge Date 2000-05-08 Time 08:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2000-04-30 Cont ID  
Sent By tlarge Date 2000-04-30 Time 11:53 Rev Time 0.75
Received By tlarge Date 2000-04-30 Time 11:53 Sent To  
Notes
2001-01-08 00:00:00SHT.P-6-2"ROOF DRAIN CANNOT DRAIN TO
 SANITARY SYSTEM PER SPC SEC.301.3 & CITY
 ORDINANCE.
  
 SUBMIT DOCUMENTATION FROM AIR ADMITTANCE
 VALVE MANUF.ALLOWING USE OF AAV'S ON
 CONDENSATE SYSTEM.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.9, 104.2.1, 303.5,
 905.7.
  
 INDIRECT WASTE PIPES SHALL DISCHARGE
 ABOVE RECEIVING RECEPTACLE AND PROVIDE
 MIN.REQD.AIR GAP PER SPC 806, 807.1.3.
  
 SHOW/NOTE TERMINATION PT. OF CONDENSATE
 DRAINS.

Review Stop P PLUMBING
Rev No 6 Status F Date 2000-03-05 Cont ID  
Sent By tlarge Date 2000-03-05 Time 11:35 Rev Time 1.50
Received By tlarge Date 2000-03-05 Time 11:35 Sent To  
Notes
2001-01-08 00:00:00SUBMIT CLEAR DETAIL OF ROOF SCUPPERS AND
 SHOW LOCATION OF SCUPPERS ON ROOF PLAN.
 SIZE OF SCUPPERS SHALL COMPLY W/ SPC
 APPENDIX "A",TABLE "A101.2".(PLANS DON'T
 SHOW WIDTH OF SCUPPER,ONLY 4"HT.)
  
 CLARIFY SQ.FOOTAGE DRAINED BY RAIN WATER
 LINES.ROOF PLAN AND PLBG.SHEETS DON'T
 MATCH.
  
 SHT.A14-CLEAR FLOOR SPACE UNDER H.C. LAV
 SHALL BE 29",NOT 27" AS SHOWN.SEE FACBC
 SEC.4.19.2.
  
 SHT.P-6-RAINWATER (2"R.D)CANNOT DRAIN
 INTO SANITARY SYSTEM.301.3.AND CITY ORD.
  
 SUBMIT DOCUMENTATION FROM AIR ADMITTANCE
 VALVE CO.THAT THE AAV'S CAN BE USED ON
 AN A/C CONDENSATE SYSTEM.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.9,104.2.1.,
 303.5,905.7.

Review Stop P PLUMBING
Rev No 5 Status N Date 1999-11-24 Cont ID  
Sent By tlarge Date 1999-11-24 Time 16:04 Rev Time 0.65
Received By tlarge Date 1999-11-24 Time 15:40 Sent To  
Notes
2001-01-08 00:00:00PLUMBING NOT AFFECTED THIS REVISION.

Review Stop P PLUMBING
Rev No 4 Status N Date 1999-11-24 Cont ID  
Sent By tlarge Date 1999-11-24 Time 11:43 Rev Time 0.50
Received By tlarge Date 1999-11-24 Time 11:43 Sent To  
Notes
2001-01-08 00:00:00NO CHANGES TO PLBG.SYSTEM THIS REVISION.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-24 Cont ID  
Sent By tlarge Date 1999-11-24 Time 10:54 Rev Time 0.75
Received By tlarge Date 1999-11-24 Time 10:54 Sent To  
Notes
2001-01-08 00:00:00CONDENSATE DRAINS IN WINE
 STORAGE ROOMS

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-20 Cont ID  
Sent By tlarge Date 1999-11-20 Time 06:20 Rev Time 0.75
Received By tlarge Date 1999-11-20 Time 06:20 Sent To  
Notes
2001-01-08 00:00:00AIR ADMITTANCE SHALL BE INSTALLED PER
 MANUF.RECOMMENDATIONS AND SPC 905.7.
 SUPPORT DATA FROM MANUF.REQD.FOR USE ON
 CONDENSATE SYSTEMS.
  
 SLOPE OF PIPE SHALL BE MIN. OF 1/4" PER
 FT.PER SPC SEC.705.2.
  
 INDIRECT WASTE FOR COOLING TOWER SHALL
 DISCHARGE TO OPEN RECEPTACLE PER SPC
 SEC.804.5,807.2.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-04-09 Cont ID  
Sent By pschmitz Date 1999-02-25 Time 14:33 Rev Time 0.75
Received By tlarge Date 1999-04-09 Time 08:57 Sent To  
Notes
2001-01-08 00:00:00 
 PROVISO: SEE SHT. P-5&7

Review Stop Z ZONING
Rev No 2 Status P Date 2000-02-29 Cont ID  
Sent By gjoyce Date 2000-02-29 Time 16:53 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-05-05 Cont ID  
Sent By hpiskura Date 1999-05-05 Time 09:00 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***