Plan Review Details - Permit 98121020
Plan Review Stops For Permit 98121020
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-02-02 Cont ID  
Sent By hpiskura Date 1999-02-02 Time 11:28 Rev Time 7.00
Received By hpiskura Date 1999-01-29 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-01-21 Cont ID  
Sent By hpiskura Date 1999-02-02 Time 11:28 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-01-07 Cont ID  
Sent By hpiskura Date 1999-02-02 Time 11:29 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 1999-03-05 Cont ID  
Sent By pschmitz Date 1999-01-15 Time 15:12 Rev Time 1.50
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PLUMBING NOTES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-01-22 Cont ID  
Sent By ndenmark Date 1999-01-22 Time 10:53 Rev Time 1.50
Received By ndenmark Date 1999-01-22 Time 10:53 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SEPARATE PERMITS REQUIRED FOR
 HOOD AND SUPPRESSION SYSTEM FOR HOOD
 2) EXISTING DUCTS TO BE REUSED TO BE INS
 PECTED FOR CLEANLINESS AND CLEANED AND
 SANITIZED BY LICENSED MECH. CONTRACTOR
 3) CEILING DIFFUSERS IN RATED CEILING TO
 BE RADIANT TYPE-RATED DIFFUSERS,SEE A-8
 DETAIL 4
 4) MACHINERY ROOMS ON ROOF TO BE VENTI-
 LATED AND PROTECTED PER 1994 SMC CH.11,
 INCLUDING LEVEL 1 MACHINE ROOM 1105

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-03-04 Cont ID  
Sent By pschmitz Date 1999-01-15 Time 14:36 Rev Time 1.50
Received By pschmitz Date 1999-01-15 Time 15:31 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW 94 STD PLBG CODE
 CONTACT PAUL SCHMITZ 561-659-8096 X8233
  
 (1) SHT.PM-6 GENERAL 1.1.1.8, 3.4.1.1
 HUB DRAINS PROHIBITED,USE FLOOR SINKS.
 (2) SHT P-3 GREASE TRAPS: CONTACT W.
 PALM BCH REG. SEWER TREATMENT PLANT FOR
 GREASE TRAP SIZE 561-686-6324
 (3) SHT. P-4 GAS PIPING: SHOW BTU'S OF
 EACH APPLIANCE, TOT. BTU'S,TOT. DEVE-
 LOPED LENTH, ISOMETRIC DRWG.
 (4) SHT P-5 SAFE WASTEPROHIBITED,USE
 HORIZONTAL WASTE & VENT,SPC SEC 921.
 (5) A/C CONDENSATE: TO STORM DRAIN, DRY
 WELL, OR PLANTER,NOT TO SANITARY SEWER.
 (6) DISH WASHER TO SANITARY SEWER.
 (7) SHT P-7 DETAIL 4 SANITIZER SYSTEM:
 WATTS #7 BFP NOT APPROVED, USE WATTS
 36N ANTI SYPHON DEVICE.
 (8) DETAIL 12 FOOD PREPARATION SINK: EA.
 COMPARTMENT WASTE TO HAVE A SEPERATE
 WASTE TO FLOOR SINK.
 (9) DISH WASHERS TO BY PASS GREASE TRAP.
 END OF COMMENTS
 PERMIT ISSUED WIHH PROVISO SEE LIST
 03-04-99PES

Review Stop Z ZONING
Rev No 1 Status P Date 1998-12-29 Cont ID  
Sent By gjoyce Date 1998-12-29 Time 13:37 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***