Plan Review Details - Permit 98120860
Plan Review Stops For Permit 98120860
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-09-10 Cont ID  
Sent By hpiskura Date 1999-09-10 Time 15:21 Rev Time 2.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By hpiskura Date 1999-01-12 Time 16:37 Rev Time 3.00
Received By lsmith Date 1999-01-12 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-16 Cont ID  
Sent By dpalmer Date 2000-05-16 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2000-05-16 Time 12:46 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 NOTES ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By hpiskura Date 1999-01-12 Time 16:37 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-05-22 Cont ID  
Sent By mamini Date 2001-05-22 Time 08:29 Rev Time 3.00
Received By mamini Date 2001-05-22 Time 08:22 Sent To  
Notes
2001-05-22 00:00:00PASSED:
 1. RESPONSES TO PREVIOUS REVIEW COMMENTS
 DATED 4-24-01 SATISFACTORY.PLANS HAVE
 BEEN REVISED PER REVIEW COMMENTS AND
 CALCULATIONS PROVIDED.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-04-20 Cont ID  
Sent By mamini Date 2001-04-20 Time 11:26 Rev Time 4.00
Received By mamini Date 2001-04-20 Time 10:43 Sent To  
Notes
2001-04-20 00:00:00FAILED:
 1. PLEASE PROVIDE ITEMS AS INDICATED ON
 ATTACHED SHEET FOR STORM WATER
 CONSTRUCTIONS TO, JOSE DEL RIO, STORM
 WATER ENGINEER, 1000 45TH STREET WEST
 PALM BEACH, FL 33407 561-659-8040.
 2. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY THE CITY OR IF IT IS
 PRIVATE PICKUP.CITY PICKUP THEN THE
 FOLLOWING REQUIREMENTS MUST BE MET.SEE
 ATTACHED
 3. THE "APPLICATION FOR CONSTRUCTION
 WITHIN PUBLIC R.O.W" MUST BE SUBMITTED
 TO CITY ENGINEER, RICHARD PITTMAN
 100045TH STREET WEST PALM BEACH, FL
 33407 561-569-8040. SEE ATTACHED
 4. A SEPARATE PERMIT FOR UNDERGROUND
 UTILITIES CONSTRUCTION MAY BE REQUIRED.
 PLEASE CONTACT, DEAN RUNNELS LIC./PER.
 SUPERVISOR, 200 2ND STREET WEST PALM
 BEACH, FL 33407561- 659-8040 EXT. 8496
 5. PLEASE CONTACT RODNEY COMPO UTILITIES
 TECHNICIAN ( INDUSTRIAL PRETRETMENT )
 FOR INSTALLATION, INSPECTIONS ON GREASE/
 WATER SEPARATOR561-837- 4051 EXT. 4074
 6. PLEASE PROVIDE DETAIL/ SIZE FOR
 JUNCTION BOX AS SHOWN ON SHEET C-2
 7. PLEASE SHOW POINT OF CONFLICTS, WHERE
 WATER CROSSING SANITARY AND STORM WATER
 LINES AND INDICATE INVERTS/CROWNS ELEV.
 8. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SERVICES FOR
 CONNECTING TO INLET.PROVIDE TWO SETS
 OF PLANS FOR THIER APPROVAL AND ACTUAL
 SERVICE CONNECTIONS.
 9. PLEASE SHOW HORIZANTAL CLEARANCES
 BETWEEN THE SERVICE LINES.
  
 IF ANY QUESTIONS PLEASE CONTACT 561-569-
 8096 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1998-12-28 Cont ID  
Sent By hpiskura Date 1999-01-12 Time 16:38 Rev Time  
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 1999-12-16 Cont ID  
Sent By ndenmark Date 1999-10-21 Time 11:14 Rev Time 0.00
Received By jleech Date 1999-12-14 Time 15:13 Sent To  
Notes
2001-01-08 00:00:00ORIGINAL MECH DRAWINGS ENGINEER SEALED
 REVISED SET NOT SEALED CANNOT ACCEPT
 CONTRACTOR CALLED TO SUBMIT ENGINEER
 APPROVED AND SEAL DRAWING FOR REVISION
 SHOWING AREAS CHANGED INDICATED BY CLOUD
 OR TRIANGLE
 CONTRACTOR WILL USE APPROVED DRAWINGS
 THIS REVISION IS VOID.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 1999-10-04 Cont ID  
Sent By ndenmark Date 1999-10-04 Time 15:28 Rev Time 0.33
Received By ndenmark Date 1999-10-04 Time 15:28 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FAN SHUT DOWN TO BE TIED TO HORN AND
 STROBE FOR NOTIFICATION PER NFPA 4-4.4.3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-10-04 Cont ID  
Sent By ndenmark Date 1999-09-01 Time 12:27 Rev Time 0.33
Received By ndenmark Date 1999-09-01 Time 12:27 Sent To  
Notes
2001-01-08 00:00:00PRIOR PLAN REVIEW COMMENTS NOT CORRECTED
 FROM 12/22/98

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By ndenmark Date 1999-01-04 Time 11:27 Rev Time 0.50
Received By ndenmark Date 1999-01-04 Time 11:27 Sent To  
Notes
2001-01-08 00:00:001) NEED OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) NEED AIR BALANCE SCHEDULE PER 1994
 SMC 501.2
 3) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1994 SMC 406.1
 3A) NOTIFICATION TO BE PER 1996 NFPA 90A
 4-4.4.2 OR 4-4.4.3 STOBE AND HORN
 4) SECOND FLOOR DUCT TO BE INSULATED W/
 R-6 PER FLORIDA ENERGY EFFICIENCY CODE
 1997, UNLESS ROOF IS INSULATED TO R-16
 5) ROOF PLAN DOES NOT SHOW EXHAUST FAN
 TERMINATION LOCATION

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-06-27 Cont ID  
Sent By pschmitz Date 2001-06-27 Time 09:00 Rev Time 5.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-06-27 00:00:00PLUMBING REVISION, DELETE (1) GREASE
 TRAP.OK PES

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-04-18 Cont ID  
Sent By jleech Date 2001-04-18 Time 18:06 Rev Time 2.50
Received By jleech Date 2001-04-18 Time 18:06 Sent To  
Notes
2001-04-18 00:00:00SITE PLANS DENIED;
  
 NOT ENOUGH INFORMATION;
  
 1.WHAT SIZE ARE GREASE TRAPS?
  
 2.WHY IS THERE 3 GREASE TRAPS?
  
 3.GREASE TRAPS SHALL BE REVIEW AND
 APPROVED BY THE UTILITY DEPARTMENT.
 CALL RODNEY COMPO AT 837-4074.
  
 4.TWO WAY CLEANOUTS ARE REQUIRED BETWEEN
 EACH TANK AND AT THE FRONT OF THE
 FIRSTTANK AND AFTER THE LAST TANK.
  
 5.WHY IS SEWER AND WATER TIDED INTO TWO
 BUILDINGS? EACH BUILDING SHOULD HAVE
 ITS OWN HOOKUP.
  
 6.NEED CAULKULATIONS FOR STORM DRAINAGE
 PIPING.PLEASE SHOW SQUIRE FOOTAGE TO
 BE DRAINED.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377 OR 8369

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-08-19 Cont ID  
Sent By pschmitz Date 1999-08-19 Time 10:25 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: SHT.P-2 SECONDARY DRAINAGE
 SYSTEM REQUIRED, ( SCUPPERS)
 SEE NOTES ON ISOMETRIC

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-08-19 Cont ID  
Sent By pschmitz Date 1999-01-06 Time 15:23 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 PLUMBING PLAN REVIEW 94 STD.PLBG. CODE
 UNSAT CONTACT PAUL SCHMITZ 561-659-8096
 X 8233
 (1) SHT. P-1 NO HORIZONTAL DRY VENTS.
 (2) SHT. P-1 CONTACT REGIONAL SEWER
 TREATMENT PLANT, 561-688-6324
 (3) SHT P-3 EQUIPMENT SCHEDULE INCOMPLET
 SHOOW ALL EQUIPMENT WITH DRAINS
 INCLUDING ICEBINS.
 (4) SHT P-4 SAFE WASTE PROHIBITED.
 (5) SHT P-4ALL INDIRECT WASTE TO FLOOR
 SINKS, NO HUB DRAINS.
 (6) SHT P-4 TOTAL DEVELOPED LGTH GAS.
 (7) SHT P-4 EMERGENCY GAS VALVE BELOW
 CEILING.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-10 Cont ID  
Sent By hpiskura Date 1999-09-10 Time 15:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***