Plan Review Details - Permit 98120699
Plan Review Stops For Permit 98120699
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1998-12-17 Cont ID  
Sent By ndenmark Date 1998-12-17 Time 12:22 Rev Time 0.33
Received By ndenmark Date 1998-12-17 Time 12:22 Sent To  
Notes
2001-01-08 00:00:00(1) COND. UNITS TO BO MIN. 18" ABOVE
 FINISHED ROOF
 (2) APPLICABLE CODE IS SBCCI STANDARD
 MECHANICAL CODE, NOT SO. FL. BLDG. CODE
 (3) SEPARATE PERMITS WILL BE REQUIRED
 FOR HOODS AND COOLERS/FREEZERS

Review Stop P PLUMBING
Rev No 1 Status F Date 1998-12-30 Cont ID  
Sent By pschmitz Date 1998-12-30 Time 10:15 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00(1)CONTACT HOTEL BUSINESS REGULATION
 FOR THEIR PLAN REVIEW,APPROVAL.
 954-958-5520.
 (2) CONTACT W. PALM BCH REGIONAL SEWER
 PLANT FOR GREASE TRAP SIZE 561-688-5520
 (3) SHT. P-1 SAFE WASTE PROHIBITED:
 ALL INDIRECT WASTE TO FLOOR SINKS,
 NO HUB DRAINS.
 (4) SHT P-2,2 & 3 COMPARTMENT SINKS TO
 HAVE INDIVIDUAL TRAPS ON EACH COMPART-
 MENT.
 END OF COMMENTS.

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***