Plan Review Details - Permit 98120695
Plan Review Stops For Permit 98120695
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-01-05 Cont ID  
Sent By lmartine Date 1999-01-05 Time 15:42 Rev Time 0.00
Received By lmartine Date 1999-01-05 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-06 Cont ID  
Sent By dpalmer Date 2000-06-06 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2000-06-06 Time 12:06 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEEDS TO BE SHOWN IN LOAD CALCS.
 AT 125 %.(LIGHTING) OR LOADS FOR EXPECT.
 FOR 3 OR MORE HOURS.
  
 2)NOTE: ALSO PLEASE NOTE THAT YOU SHOW
 PHASE "C" ON ALL PANELS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE THE FINAL ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096 X8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-25 Cont ID  
Sent By dpalmer Date 1999-10-25 Time 14:20 Rev Time 0.00
Received By dpalmer Date 1999-10-25 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-07-07 Cont ID  
Sent By lmartine Date 1999-07-07 Time 14:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-03-10 Cont ID  
Sent By jleech Date 2000-03-10 Time 15:26 Rev Time 0.50
Received By jleech Date 2000-03-10 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-01-14 Cont ID  
Sent By ndenmark Date 1999-01-14 Time 14:38 Rev Time 0.33
Received By ndenmark Date 1999-01-14 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-26 Cont ID  
Sent By ndenmark Date 1998-12-17 Time 11:01 Rev Time 0.33
Received By lmartine Date 1998-12-17 Time 11:01 Sent To  
Notes
2001-01-08 00:00:00EROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89 ANDSHOW AIR BALANCE
 SCHEDULE PER 1994 SMC 501.2

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-05-26 Cont ID  
Sent By tlarge Date 2000-05-26 Time 15:37 Rev Time 0.33
Received By tlarge Date 2000-05-26 Time 15:37 Sent To  
Notes
2001-01-08 00:00:00SHOW THE SQ.FT.AREA DRAINED BY EACH
 DRAIN AND THE SLOPE OF THE PIPE.COMPLY
 W/SPC SEC.1108.2.
  
 CLEANOUTS ARE REQD.IN THE HORIZONTAL
 DRAINAGE PIPE PER SPC SEC.710.2.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-03 Cont ID  
Sent By tlarge Date 2000-01-03 Time 06:06 Rev Time 0.25
Received By tlarge Date 2000-01-03 Time 06:06 Sent To  
Notes
2001-01-08 00:00:00LETTER DELETING SINK IN CONFERENCE ROOM.

Review Stop P PLUMBING
Rev No 1 Status P Date 1998-12-30 Cont ID  
Sent By pschmitz Date 1998-12-30 Time 15:31 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-26 Cont ID  
Sent By lmartine Date 1999-10-26 Time 13:56 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***