Plan Review Details - Permit 98110234
Plan Review Stops For Permit 98110234
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1998-12-09 Cont ID  
Sent By hpiskura Date 1998-12-09 Time 10:00 Rev Time 6.00
Received By hpiskura Date 1998-12-07 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1998-12-07 Cont ID  
Sent By jleahy Date 1998-12-07 Time 12:29 Rev Time 1.30
Received By jleahy Date 1998-12-07 Time 12:13 Sent To  
Notes
2001-01-08 00:00:001- NEED PANEL SCHEDULES FOR ALL SHOWN
 2- NEED BRANCH CKT. #S ON PLAN TO SHOW
 HOW MANY OUTLETS AND LIGHTS ARE TO BE
 ON EACH CIRCUIT.
 3- NO A/C'S SHOWN ON ELECTRICAL DRAWINGS
 SHOW SIZE OF WIRE AND PROTECTION.
 4- RISER DIAGRAM SHOWS NOT ENOUGH WIRES
 IN SOME OF THE RACWAYS FOR 301,302,
 401,402,403,404,405,408,303,304,305,
 308.
 5- NEED LOAD CALC. AND SHOW SIZE OF WIRE
 AND MAIN FOR GUTTER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 1999-03-05 Cont ID  
Sent By hpiskura Date 1998-12-09 Time 10:01 Rev Time 0.00
Received By bprusiec Date 1998-11-19 Time 10:01 Sent To  
Notes
2001-01-08 00:00:00COMMON PATH OF TRAVEL EXCEEDS THE
 ALLOWABLE 75 FEET MAXIMUM TRAVEL DISTANC
 E FROM THE MOST REMOTE POINT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1998-12-07 Cont ID  
Sent By ndenmark Date 1998-12-07 Time 14:48 Rev Time 0.25
Received By ndenmark Date 1998-12-07 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1998-11-15 Cont ID  
Sent By pschmitz Date 1998-11-15 Time 12:27 Rev Time 0.50
Received By pschmitz Date 1998-11-15 Time 12:25 Sent To  
Notes
2001-01-08 00:00:00PROVISO: SEE SHT P1

Review Stop Z ZONING
Rev No 1 Status P Date 1998-11-10 Cont ID  
Sent By gjoyce Date 1998-11-10 Time 11:18 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***