| Plan Review Stops For Permit 98101449 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1998-11-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1998-11-09 |
Time |
13:09 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
1998-11-09 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1- NORTH ELECTRICAL ROOM SHOWS MAINS #2, | | | 3 BEING 1200 AMPERES AND WIRE TO THEM | | | IS ONLY 1005 AMPERES | | | 2- SOUTH ELECTRICAL ROOM SAME AS ABOVE | | | ON MAIN #4 | | | 3- PANEL GPD HAS TWO SUBFEEDERS NEED TO | | | SHOW THE SIZE OF THE CONDUCTORS. | | | 4- NEED FAULT CURRENT ON ALL PANELS AND | | | SWITCH GEAR. 110-10,110-11 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|