Plan Review Details - Permit 98101449
Plan Review Stops For Permit 98101449
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1998-11-09 Cont ID  
Sent By jleahy Date 1998-11-09 Time 13:09 Rev Time 2.00
Received By jleahy Date 1998-11-09 Time 13:01 Sent To  
Notes
2001-01-08 00:00:001- NORTH ELECTRICAL ROOM SHOWS MAINS #2,
 3 BEING 1200 AMPERES AND WIRE TO THEM
 IS ONLY 1005 AMPERES
 2- SOUTH ELECTRICAL ROOM SAME AS ABOVE
 ON MAIN #4
 3- PANEL GPD HAS TWO SUBFEEDERS NEED TO
 SHOW THE SIZE OF THE CONDUCTORS.
 4- NEED FAULT CURRENT ON ALL PANELS AND
 SWITCH GEAR. 110-10,110-11