Plan Review Details - Permit 98100755
| Plan Review Stops For Permit 98100755 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-07-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-07-12 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-07-12 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************************************** | | | | | | NOTE:ASBUILTS ARE REQ`D BEFORE FINAL | | | INSPECTION IS CALLED IN. | | | NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | | AND OUTSIDE BEDROOMS AS PER NFPA-72. | | | NOTE:MISSING OUTLETS AS PER 210-52E | | | REQ`D FRONT AND BACK OF RESIDENCE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-09-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-09-09 |
Time |
15:58 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
1999-09-09 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-09-09 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-07-07 |
Time |
09:07 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-07-07 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | | | | THESE COMMENTS APPLY TO ALL MODEL TYPES | | | | | | 1) OVERFLOW PROTECTION REQUIRED ON ALL | | | AIR HANDLERS | | | 2) DRYER VENTS EXCEEDING 25' LENGTH ALL- | | | OWED PER CODE INCL. 5' DEDUCTION FOR EA. | | | 90 AND 2.5' DEDUCTION FOR EA. 45 DEGREE | | | BEND TO PROVIDE MANUFACTURES SPECS WITH | | | ALLOWED LENGTHS AND EQUIPMENT TO BE INS- | | | TALLED AT FINAL INSPECTION | | | 3) CONDENSER ACCESS TO COMPLY WITH SMC | | | AND NEC MIN. 36 INCHES FOR ELEC ACCESS | | | AND 24 INCHES FOR MECH | | | 4) ANY DIFFUSERS PENETRATING RATED CEIL- | | | INGS TO HAVE RATED FIRE DAMPERS INSTALL- | | | ED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
1999-10-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-27 |
Time |
11:58 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
1999-10-27 |
Time |
11:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
1999-10-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-23 |
Time |
11:30 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
1999-10-23 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THESE COMMENTS APPLY TO ALL MODEL TYPES | | | | | | CLEANOUTS SHALL BE INSTALLED IN THE | | | HORIZONTAL DRAINAGE PIPING PER SPC SEC. | | | 710.2.4.(1)(2). | | | | | | RISER NUMBERS ON SHT P-7 DON'T CORRELATE | | | W/SHT.P-14.(SEE FLOOR PLAN D1.1.)SPC | | | SEC.104.2.1. | | | | | | LOCATION OF FIXTURES ON RISERS S-1A,6,6A | | | DOESN'T CORRELATE W/FLOOR PLAN ON SHT.P7 | | | | | | SHT.P-20-RISERS S10 AND S9 ARE MIS- | | | LABELED.(SEE SHT.P-7.WATER CLOSETS | | | SHOULD BE LABELED AS S9,TUBS AND LAVS.AS | | | S10.) | | | | | | REVISE FIXTURE UNIT LOAD FOR W/M RISERS. | | | COMPLY W/TABLE 713.1. | | | | | | SIZE OF VENT STACKS FOR RISERS # 1,2,6,7 | | | 9,11,13,14.SHALL COMPLY W/SPC SEC.911.3. | | | | | | PLANS SHALL BE SIGNED AND SEALED PER | | | SBC SEC.104.2.2. AND SPC SEC.104.2.3 | | | | | | MIN.SIZE OF DRAIN PAN RISER SHALL BE | | | 1 1/4" PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.507.8.3.(MIN.SIZE PAN DRAIN SHALL BE | | | 1" PER SPC SEC.507.8.2.) | | | | | | SUBMIT DETAILS FOR WOOD BLOCKING FOR | | | FUTURE HANDICAP GRAB BAR INSTALLATION | | | PER FEDERAL FAIR HOUSING ACT. | | | AND 24 CFR 100.205. | | | | | | SHOW WIDTH OF SHOWERS IN ALL UNITS. | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.409.8.2.1. | | | | | | NOTE:CALL TIMOTHY LARGE | | | AT (561)659-8096,EXT.8377 TO ARRANGE AN | | | APPOINTMENT TO REVIEW THESE COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
1999-07-14 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-07-14 |
Time |
09:32 |
Rev Time |
7.00 |
| Received By |
tlarge |
Date |
1999-07-15 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THESE COMMENTS APPLY TO ALL MODEL TYPES. | | | | | | SUBMIT SANITARY AND WATER ISOMETRICS FOR | | | CAR WASH AND TRASH COMPACTOR AREAS PER | | | SPC SEC.104.2.1.(AN APPROVED INTERCEPTOR | | | SHALL BE INSTALLED PER SPC SEC.1004.5, | | | 1004.6. | | | | | | CLEANOUTS SHALL BE INSTALLED IN THE | | | HORIZONTAL PIPING PER SPC.SEC-710.2.4. | | | (1)(2). | | | | | | THE LABELING OF THE SANITARY RISERS ON | | | SHEETS P-1,P-13,P-14,P-15 DON'T | | | CORRELATE W/EACH OTHER. SPC SEC.104.2.1. | | | | | | INDICATE SLOPE OF PIPE ON PLANS.COMPLY | | | W/SPC TABLE 714.1,714.2. | | | | | | LOCATION OF FIXTURES ON SANITARY RISERS | | | SHALL MATCH THE ARCH.FLOOR PLANS.SPC | | | SEC.104.2.1. | | | | | | SHT.P-20-SIZE OF PAN DRAIN RISER SHALL | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.507.8.3. | | | | | | RELIEF VALVE DRAIN AND PAN DRAIN SHALL | | | NOT USE COMMON RISERS PER SPC SEC. | | | 507.8.4. | | | | | | FIXTURE UNIT LOAD FOR SANITARY RISERS | | | SHALL COMPLY W/SPC TABLE 713.1.(CHECK | | | W/M STACKS.) | | | | | | SIZE OF VENT STACKS FOR RISERS #1,2,6,7, | | | 9,11,13,14 SHALL COMPLY W/SPC SEC.911.1, | | | 911.3, AND TABLE 911.3. | | | | | | INDICATE TYPE OF OCCUPANCY OF BUILDING | | | ON PLANS.SEE STD.BLDG.CODE AND PLBG.CODE | | | SECS.104.2.3,AND 322.2 FOR REQ'S.FOR | | | SIGNED AND SEALED DRAWINGS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1998-10-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1998-10-28 |
Time |
10:58 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
1998-10-28 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-10-28 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1998-10-17 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BLDG REV:L MAR |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1998-10-17 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1998-10-17 |
Time |
09:18 |
Rev Time |
|
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
R |
|
| Notes |
|
|
|