Plan Review Details - Permit 98091279
Plan Review Stops For Permit 98091279
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1998-10-29 Cont ID  
Sent By jleahy Date 1998-10-29 Time 14:05 Rev Time 1.00
Received By jleahy Date   Time   Sent To  
Notes
2001-01-08 00:00:001- SHOW BRANCH CIRCUIT NUMBERS
 2- RISER SHOWS NO U.P.S. SYSTEM
 3- IDENTIFY OUTLETS ON PLANS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1998-10-01 Cont ID  
Sent By jleahy Date 1998-10-01 Time 14:11 Rev Time 0.00
Received By ndenmark Date 1998-10-27 Time 07:45 Sent To  
Notes
2001-01-08 00:00:00NEED DRAWING SHOWING ALL LOADS
 RISER DIAGRAM NOT COMPLETE SHOW ALL WIRE
 SIZES, WIRE TO PANELS A&B IS TO SMALL.