Plan Review Details - Permit 98090618
Plan Review Stops For Permit 98090618
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1998-12-09 Cont ID  
Sent By hpiskura Date 1998-10-20 Time 13:48 Rev Time 4.00
Received By hpiskura Date 1998-10-20 Time 13:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1998-12-08 Cont ID  
Sent By jleahy Date 1998-10-06 Time 13:35 Rev Time 1.45
Received By jleahy Date 1998-12-08 Time 13:33 Sent To  
Notes
2001-01-08 00:00:001-NEED LOAD CALCULATIONS ON THE FOLLOWIN
 4/0S, PP,LP,KP
 2-NEED FAULT CURRENT CALCULATION.
 3-OUTLET SPACING NOT TO LOCAL CODE.
 4-PANEL SCHEDULUE NOT COMPLETE.
 5-SEE PAGE E-1 FOR ELECTRICAL NOTES 12/8

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1998-10-16 Cont ID  
Sent By hpiskura Date 1998-10-20 Time 13:50 Rev Time 0.00
Received By hpiskura Date 1998-10-08 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1998-12-02 Cont ID  
Sent By ndenmark Date 1998-12-02 Time 13:07 Rev Time 0.25
Received By ndenmark Date 1998-12-02 Time 13:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1998-12-02 Cont ID  
Sent By ndenmark Date 1998-10-22 Time 12:34 Rev Time 0.33
Received By ndenmark Date 1998-10-22 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1998-12-07 Cont ID  
Sent By pschmitz Date 1998-10-19 Time 14:50 Rev Time 1.50
Received By pschmitz Date 1998-12-07 Time 10:50 Sent To  
Notes
2001-01-08 00:00:001 CONTACT HOTEL BUSINESS REGULATION FOR
 THEIR PLAN REVIEW, APPROVAL 954-958-5520
 2 CONTACT W. PALN BCH REGIONAL SEWER
 PLANT FOR GREASE TRAP SIZE 561-688-6324.
 3 MINIMUM FACILITIES,TAB 407 WOMEMS REST
 ROOM REQUIRES 3 WATER CLOSETS.
 4SHT P2.0 WITH SEC 921 SPC COMBINATION
 WASTE ,VENT SYSTEM,2 PIPE SIZES LARGER,
 VENTS ON EACH END OF SYSTEM.
 5 SHT P2.0 ALL INRIRECT WASTE TO FLOOR
 SINKS, NO HUB DRAINS OR FUNNEL DRAINS.
 6 SHT P2.0 HOUSE TRAP NOT REQUIRED.
 7 SHT P2.0 FIRE LINE TO BE SEPERATE FROM
 DOMESTIC WATER.
 8 BACK FLOW PREVENTERS REQUIREDON
 DOMESTIC,FIRE LINE
 9 DISH WASHER TO BY PASS GREASE TRAP
 LOCAL ORDINANCE.
 10 SHT M2.0 A/C CONDENSATE TO STORM
 DRAIN, PLANTER OR DRY WELL.
 11 PROVISO 12-07 98 SEE SHT 2-P REVISION

Review Stop Z ZONING
Rev No 1 Status P Date 1998-10-03 Cont ID  
Sent By gjoyce Date 1998-10-03 Time 10:31 Rev Time  
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***