| 2023-07-20 11:13:46 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3. SUBMITTED MIAMI-DADE COUNTY NOA |
| | 22-1221.05 COVERS MULTIPLE PRODUCTS & APPROVED |
| | ASSEMBLIES: SYSTEMS E(1) THROUGH E(4). SELECT PRODUCT & |
| | SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. |
| | 2. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL5259-R40 HAS NOT BEEN APPROVED YET. PLEASE |
| | PROVIDE A COMPLETE SET OF APPROVED 2020 CODE VERSION |
| | PRODUCT APPROVALS/NOA???S FOR THE PROPOSED FLAT/LOW |
| | ROOF SYSTEM USED. INCLUDE COVER PAGE, EVALUATION |
| | REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED. |
| | (FL5259-R39) |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39 |
| | COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED |
| | ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2 |
| | MECHANICALLY-ATTACHED BASE SHEET TABLE 4B ALLOWABLE |
| | DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE |
| | ROOF APPLICATIONS SYSTEM NO. UDL-15 DO NOT MEET OR |
| | EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENTS FOR A |
| | HIP ROOF; (5:12) ROOF SLOPE; MEAN ROOF HEIGHT 15 FT. |
| | MINIMUM DESIGN PRESSURE REQUIREMENT OF -70 IN AN |
| | EXPOSURE CATEGORY C AREA. PROVIDE UNDERLAYMENT SYSTEM |
| | THAT MEETS OR EXCEEDS THE ABOVE CRITERIA. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |