| Plan Review Stops For Permit 23070473 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2023-07-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-07-18 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-07-18 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2023-07-18 10:45:26 | SUITE 315 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE | | | PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR. | | | PLEASE EMAIL TO [email protected] FOR FURTHER | | | QUESTIONS YOU CAN ALSO CALL 561-805-6659 |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-07-26 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-07-26 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2023-07-26 14:13:18 | COMMERCIAL ASBESTOS | | | TO THE BUILDING CONTRACTOR: | | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING | | | THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS | | | PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM | | | BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION | | | WILL BE GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | | -RENOVATION.HTML | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-07-26 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2023-07-26 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2023-07-26 14:11:55 | PASSED CORRIDOR WIDTH 60 INCHES, DOOR WIDTH 36 INCHES, | | | REQUIRED COORIDOR WIDTH 44 INCHES 1/2 OF REQUIRED | | | CORIDOR WIDTH IS 22 INCHES MINIMUM. 60-36= 24 INCHES, 2 | | | INCHES OVER THE MINIMUM REQUIRED CORRIDOR WIDTH. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-28 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-28 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-28 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-28 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2023-07-28 12:18:21 | VOICE AND DATA AS PER PLAN JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-07-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-07-17 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2023-07-17 14:26:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF WHAT APPEARS TO BE A | | | DOUBLE SWING ENTRY DOOR, # 1, HOWEVER, IF IT WERE TO | | | SWING OUT IT APPEAR TO RESTRICT THE CORRIDOR EGRESS | | | WIDTH. | | | | | | PER NFPA 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS | | | | | | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO | | | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE | | | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. | | | | | | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL | | | LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF | | | AN AISLE, A CORRIDOR, | | | A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF | | | THE FOLLOWING | | | CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL | | | NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED | | | WIDTH OF AN AISLE, | | | A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR | | | LEAF IS EQUIPPED | | | WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT | | | REQUIRED BY THE PROVISIONS | | | OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS | | | TRAVEL. | | | | | | | | | PLEASE REVIEW AND CORRECT AND/OR PROVIDE THE REMINAING | | | CORRIDOR WIDTH DIMENSION IN COMPLIANCE WITH THE | | | REQUIREMENT. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-14 |
Time |
12:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-07-21 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-07-21 |
Time |
08:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-28 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-07-28 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2023-07-26 14:14:56 | ARCHITECTURAL SHEETS DIGITAL REVIEW PASSED. 7-26-23. J | | | WITMER | | 2023-07-21 08:11:31 | PLUMBING SIGNATURES PASSED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|