| Plan Review Stops For Permit 23070426 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-07-14 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-07-14 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2023-07-14 15:07:41 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-25 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-25 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-21 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-21 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2023-07-21 09:07:04 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23070426 | | | | | | REVIEWED: 7.21.2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | ASBESTOS PLAN REVIEW: FAILED | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: | | | | | | THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | | ES/ENVIRONMENTAL-HEALTH/AIR- | | | QUALITY/ASBESTOS-DEMOLITION-RENOVATION.HTML | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-25 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-25 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-21 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-21 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2023-07-21 09:09:01 | PROVISO | | | | | | COMPLY TO SIGNATURE COMMENT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-07-28 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-28 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-07-13 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-17 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2023-07-17 10:51:06 | ELECTRIC APPLICATION UPLOADED TO SUPPORTING DOCS | | | FOLDER. 7/17/23 MP | | 2023-07-13 07:52:32 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | | APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL | | | PERMIT APPLICATION TO [email protected], [email protected], AND | | | [email protected] SO WE RECEIVE IT ALSO. WHEN THIS | | | EMAIL IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE | | | PLAN REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-07-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-07-25 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2023-07-25 10:09:27 | FIRE PROVISO: | | | | | | ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES | | | AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS FOR CODE COMPLIANT COVERAGE | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-07-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-07-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-07-13 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2023-07-13 16:03:24 | FIRE PROVISO: | | | | | | ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES | | | AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS FOR CODE COMPLIANT COVERAGE | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-07-28 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-24 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-21 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-12 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
N |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-21 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-21 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-25 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-25 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-07-21 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-07-21 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2023-07-21 09:08:15 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 23021359 | | | | | | REVIEWED: 6.22.2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | PLAN BY FL. LICENSES ENGINEERS/ARCHITECT THAT ARE | | | SUBMITTED ELECTRONICALLY SHALL BEAR VERIFIABLE, | | | ORIGINAL DIGITAL SIGNATURE AND SEALS- FL STATUTE | | | 471.025 AND SEC 61G15-23.005 FLORIDA ADMINISTRATIVE | | | CODE. | | | USING BLUEBEAM REVU, ADOBE OR SIMILAR SOFTWARE THAT | | | ALLOW TO VALIDATE DIGITAL SIGNATURE CERTIFICATE, PLEASE | | | RESUBMIT ORIGINALS. THE CERTIFICATE WILL SHOW IN GREEN, | | | YELLOW OR BLUE TO BE VALID. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|