| 2023-07-18 09:08:50 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT |
| | LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. |
| | SUBMITTED MIAMI-DADE COUNTY NOA 22-0706.09 COVERS |
| | MULTIPLE ROOFING SYSTEMS TYPES A (1) THROUGH E (8). |
| | SELECT SYSTEM TYPE TO BE USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. GENERAL LIMITATION #7 IS |
| | SPECIFICALLY REFERRED TO IN THIS NOA. SUBMIT FASTENER |
| | DENSITY CALCULATIONS PREPARED, SIGNED AND SEALED BY A |
| | FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| | 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT |
| | LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. GENERAL |
| | LIMITATION #7 IS SPECIFICALLY REFERRED TO IN THIS NOA. |
| | SUBMIT FASTENER DENSITY CALCULATIONS PREPARED, SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER, REGISTERED ARCHITECT, OR REGISTERED ROOF |
| | CONSULTANT. NOTE: THIS PROJECT IS LOCATED IN AN |
| | EXPOSURE CATEGORY C AREA; TWO-STORY BUILDING MEAN ROOF |
| | HEIGHT 20 FT. |
| | 3. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| | SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| | NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| | PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| | INDICATE ON ROOF DRAWING/SKETCH). |
| | 4. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |