| | BUILDING REVIEW DENIED, PLEASE PROVIDE A RESPONSE SHEET |
| | WITH RESUBMITTALS FOR THE FOLLOWING ITEMS: |
| | |
| | 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE |
| | ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN. |
| | 34" MAX.). |
| | |
| | 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION |
| | PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT |
| | LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA |
| | BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS |
| | MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING |
| | FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2 |
| | ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55 |
| | OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED |
| | STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER |
| | PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS). |
| | THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO |
| | 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1. |
| | APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD. |
| | PLEASE REVISE PLAN SHEET A-1 OCCUPANT LOADS (INCLUDING |
| | STANDING AREA BEHIND BAR), PLAN SHEET A-2 SHOWING A |
| | SEATING PLAN INDICATING UNCONCENTRATED TABLES AND |
| | CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS |
| | APPLICABLE. |
| | |
| | 3.) FBC B 107.2.1, ON PLAN SHEET A-2 DOOR |
| | SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS |
| | A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN |
| | THE PRODUCT APPROVAL. |
| | |
| | 4.) NOTICE: ALL PLAN PAGES OR PLAN PAGES NEED TO HAVE A |
| | THIRD PARTY VERIFIABLE DIGITAL SIGNATURE BY THE DESIGN |
| | PROFESSIONAL. PLEASE SEE THE SIGNATURE REVIEW COMMENTS. |
| | A.)DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND |
| | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A |
| | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND |
| | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A |
| | VALID DIGITAL SIGNATURE. |
| | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR |
| | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH |
| | 61G1-16 AND 61G15, F.A.C. |
| | B.)SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |
| | |