Plan Review Details - Permit 23070102
Plan Review Stops For Permit 23070102
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-20 Cont ID  
Sent By pvalenti Date 2023-07-20 Time 14:25 Rev Time 0.00
Received By pvalenti Date 2023-07-20 Time 10:54 Sent To  
Notes
2023-07-20 14:39:44PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED, PLEASE PROVIDE A RESPONSE SHEET
 WITH RESUBMITTALS FOR THE FOLLOWING ITEMS:
  
 1.) FBC A 902.1, THE BAR HEIGHT HAS BEEN INCLUDED IN
 THE
 ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN.
 34" MAX.).
 THE ISSUE IS THAT THE ACCESSIBLE LOCATION AT THE BAR
 NEEDS TO BE PERMANENT SO THE INDIVIDUAL REQUIRING THE
 ACCESSIBLE LOCATION WILL NOT HAVE TO ADJUST/PULL UP THE
 BAR FOR USAGE.
  
  
  
 4.) NOTICE: PLAN SHEETS A-3, E-1, E-2, & E-3 NEED TO
 HAVE A THIRD PARTY VERIFIABLE DIGITAL SIGNATURE BY THE
 DESIGN PROFESSIONAL. PLEASE SEE THE SIGNATURE REVIEW
 COMMENTS.
 A.)DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
 B.)SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-10 Cont ID  
Sent By pvalenti Date 2023-07-10 Time 13:26 Rev Time 0.00
Received By pvalenti Date 2023-07-10 Time 11:16 Sent To  
Notes
2023-07-10 13:36:27PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED, PLEASE PROVIDE A RESPONSE SHEET
 WITH RESUBMITTALS FOR THE FOLLOWING ITEMS:
  
 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE
 ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN.
 34" MAX.).
  
 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION
 PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT
 LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA
 BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS
 MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING
 FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2
 ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55
 OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED
 STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER
 PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS).
 THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO
 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1.
 APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD.
 PLEASE REVISE PLAN SHEET A-1 OCCUPANT LOADS (INCLUDING
 STANDING AREA BEHIND BAR), PLAN SHEET A-2 SHOWING A
 SEATING PLAN INDICATING UNCONCENTRATED TABLES AND
 CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS
 APPLICABLE.
  
 3.) FBC B 107.2.1, ON PLAN SHEET A-2 DOOR
 SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS
 A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN
 THE PRODUCT APPROVAL.
  
 4.) NOTICE: ALL PLAN PAGES OR PLAN PAGES NEED TO HAVE A
 THIRD PARTY VERIFIABLE DIGITAL SIGNATURE BY THE DESIGN
 PROFESSIONAL. PLEASE SEE THE SIGNATURE REVIEW COMMENTS.
 A.)DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
 B.)SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-13 Cont ID  
Sent By fgiaquin Date 2023-07-13 Time 16:32 Rev Time 0.00
Received By jleahy Date 2023-07-13 Time 16:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-20 Cont ID  
Sent By pleduc Date 2023-07-20 Time   Rev Time 0.00
Received By pleduc Date 2023-07-20 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-12 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-20 Cont ID  
Sent By pvalenti Date 2023-07-20 Time 14:43 Rev Time 0.00
Received By pvalenti Date 2023-07-19 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-13 Cont ID  
Sent By jleahy Date 2023-07-13 Time 16:33 Rev Time 0.00
Received By jleahy Date 2023-07-07 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-07-20 Cont ID  
Sent By rwbrown Date 2023-07-20 Time 10:01 Rev Time 0.00
Received By rwbrown Date 2023-07-20 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-07-20 Cont ID  
Sent By pvalenti Date 2023-07-20 Time 14:40 Rev Time 0.00
Received By pvalenti Date 2023-07-20 Time 10:54 Sent To  
Notes
2023-07-20 14:43:18SIGNATURE REVIEW DENIED:
  
 PLAN SHEETS: A-3, E-1, E-2, & E-3 NEED TO HAVE 3RD
 PARTY VERIFIABLE SIGNATIRES/SEALS.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-10 Cont ID  
Sent By pvalenti Date 2023-07-10 Time 11:10 Rev Time 0.00
Received By pvalenti Date 2023-07-10 Time 11:07 Sent To  
Notes
2023-07-10 11:14:15SIGNATURE REVIEW DENIED:
  
 THE SUBMITTE PAPER PLAN SHEETS (A-1, A-2, A-3, E-1,
 E-2, E-3, & L.S.-1) APPEAR TO BE SCANNED PLAN SHEETS
 FROM THE DIGITALLY SIGNED SEALED PLAN SHEETS.
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  