| 2023-07-17 09:24:33 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE CONCRETE SLAB DETAIL ON SHEET CA-1 APPEARS TO BE |
| | FROM THE PUTNAM BUILDING DEPARTMENT. IT IS NOT CLEARLY |
| | LEGIBLE AND IS NOT SIGNED AND SEALED BY THE ENGINEER. |
| | FBC 107.2.1 |
| | |
| | 2) SPECIFY WHICH TYPE OF FOUNDATION WILL BE USED. FBC |
| | 107.2.1 |
| | |
| | 3) SINCE THIS CONCRETE PAD IS THE FOUNDATION FOR A |
| | GARAGE, SHOW THAT IT WILL COMPLY WITH FBC-R318.7 |
| | INSPECTION FOR TERMITES |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | EXCEPTIONS: |
| | L. PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN |
| | 5/8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| | MASONRY FOUNDATION SIDEWALL. |
| | 2. ACCESS OR VEHICLE RAMPS WHICH RISE TO THE INTERIOR |
| | FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH RAMPS |
| | ONLY. |
| | 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND |
| | GARAGE SLABS AND ENTRY AREAS. |
| | 4. IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, THE |
| | FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR FINISH |
| | FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | 5. MASONRY VENEERS CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION R318.4. |
| | |
| | 4) PROVIDE A DRAINAGE PLAN TO SHOW THAT THE WATER RUN |
| | OFF FROM THE PROPOSED CONSTRUCTION WILL NOT BE DRAINED |
| | ONTO THE ADJOINING PROPERTIES. FBC-R401.3 DRAINAGE |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |