Plan Review Details - Permit 23061530
Plan Review Stops For Permit 23061530
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-17 Cont ID  
Sent By rmcdouga Date 2023-07-17 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2023-07-17 Time 08:24 Sent To  
Notes
2023-07-17 09:24:33PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE CONCRETE SLAB DETAIL ON SHEET CA-1 APPEARS TO BE
 FROM THE PUTNAM BUILDING DEPARTMENT. IT IS NOT CLEARLY
 LEGIBLE AND IS NOT SIGNED AND SEALED BY THE ENGINEER.
 FBC 107.2.1
  
 2) SPECIFY WHICH TYPE OF FOUNDATION WILL BE USED. FBC
 107.2.1
  
 3) SINCE THIS CONCRETE PAD IS THE FOUNDATION FOR A
 GARAGE, SHOW THAT IT WILL COMPLY WITH FBC-R318.7
 INSPECTION FOR TERMITES
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 L. PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN
 5/8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2. ACCESS OR VEHICLE RAMPS WHICH RISE TO THE INTERIOR
 FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH RAMPS
 ONLY.
 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND
 GARAGE SLABS AND ENTRY AREAS.
 4. IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, THE
 FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR FINISH
 FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5. MASONRY VENEERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION R318.4.
  
 4) PROVIDE A DRAINAGE PLAN TO SHOW THAT THE WATER RUN
 OFF FROM THE PROPOSED CONSTRUCTION WILL NOT BE DRAINED
 ONTO THE ADJOINING PROPERTIES. FBC-R401.3 DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cdecoeur Date 2023-06-30 Time 12:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-17 Cont ID  
Sent By rmcdouga Date 2023-07-17 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2023-07-17 Time 08:14 Sent To  
Notes
2023-07-17 08:23:40SHEET CA-1 IS NOT DIGITALLY SIGNED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By lgelman Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***