Plan Review Details - Permit 23061490
Plan Review Stops For Permit 23061490
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By dbattles Date 2023-07-12 Time 13:42 Rev Time 0.00
Received By dbattles Date 2023-07-12 Time 10:25 Sent To  
Notes
2023-07-12 13:42:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23061490
 REVIEWED: JULY 12, 2023
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 R505.1 FBC[E] ADD FLORIDA BUILDING CODE ??? ENERGY,
 2020 EDITION TO YOUR BUILDING CODE TABLE ON SHEET A1.
 PLEASE STATE WHAT THE EXISTING OCCUPANCY IS (GROUP U)
 AND THE NEW OCCUPANCY SHOULD BE R-3.
 THIS IS A CHANGE OF USE.
  
 R505.1 FBC[E] PROVIDE ENERGY CALCULATIONS FOR THE NEW
 SPACE.
  
 R806 FBC[R] IS THIS ATTIC VENTED OR UNVENTED.
 PLEASE PROVIDE VENTING CALCULATIONS, OR STATE IT IS
 ENCLOSED AND SHOW HOW IT COMPLIES.
  
 R807 FBC[R] PLEASE SHOW THE LOCATION OF ATTIC ACCESS.
  
 R301.2.1.4.3 FBC[R] YOU ARE WITHIN 1500 FEET OF THE
 INTRACOASTAL.
 PLEASE UPDATE YOUR EXPOSURE CATEGORY TO EXPOSURE C.
  
 107.3.4 FBC[AMENDED]I SEE THE PRODUCT SCHEDULE ON SHEET
 A1. PLEASE PROVIDE PDF OF EACH PRODUCT APPROVAL WITH
 DESIGNER OF RECORD APPROVAL AND SELECTION S MADE.
  
 R703.4 FBC[R] PLEASE ADD NOTE ON SHEET A1 THAT OPENINGS
 WILL COMPLY WITH FBC R703.4 FOR FLASHING.
 YOU DONT NEED TO SPECIFY WHAT PRODUCT, JUST THAT YOU
 WILL COMPLY AND IT WILL BE HANDLED WITH THE INSPECTOR.
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By mpeterso Date 2023-07-12 Time 08:27 Rev Time 0.00
Received By mpeterso Date 2023-07-11 Time 16:35 Sent To  
Notes
2023-07-12 08:31:21ELECTRIC REVIEW FAILED
  
 1) PLEASE CORRECT CONFLICTS WITH ELECTRICAL PLANS.
 RISER DETAILS TWO ELECTRIC PANELS AS 125 AMP, ONE
 EXISTING AND ONE NEW WITH MAIN CIRCUIT BREAKERS FED BY
 A METER MAIN WITH A 125 AMP AND 200 AMP MAIN BREAKERS.
 PANEL SCHEDULE INCLUDED IN SUBMITTAL DETAILS PANEL, A,
 NEW LOAD CENTER,150 AMP, MAIN LUG ONLY LOCATED IN A
 UTILITY ROOM WITH VARIOUS LOADS. ELECTRICAL SERVICE
 CALCULATION IS DETAILED AS PANEL B, LOCATED IN UTILITY
 ROOM WITH VARIOUS ELECTRIC LOADS. THERE ARE TOO MANY
 CONFLICTS FOR THIS REVIEWER TO DO ANY KIND OF REVIEW
 FOR THE ELECTRICAL SERVICE. PLEASE CORRECT AS
 APPLICABLE AND ENSURE TO INCLUDE ALL DETAILS CORRECTLY
 AND IN COMPLIANCE WITH ALL 2017 NEC CODE REQUIREMENTS.
 FBC 107.2
  
 2) PLEASE PROVIDE MORE DETAIL AS TO KITCHEN AREA.
 APPLIANCES IF ANY, SINKS, COUNTER AREAS ETC. FBC 107.2
  
 3) PROVIDE DETAILS THIS KITCHEN WILL BE PROVIDED WITH 2
 SMALL APPLIANCE 20 AMP CIRCUITS IN ACCORDANCE WITH NEC
 210.11 (C)(1)
  
 4) PLEASE DETAIL RECEPTACLE CIRCUIT AS 20 AMP IN
 ACCORDANCE WITH NEC 210.11)3)(C)
  
 5) PLEASE DETAIL THE CORRECTLY SPACED RECEPTACLES IN
 MAIN AREA IN ACCORDANCE WITH NEC 210.52
  
 6) PLEASE DETAIL AN OUTDOOR RECEPTACLES IN ACCORDANCE
 WITH NEC 210.52(E)(1)
  
 7) PLEASE DETAIL THE REQUIRED DIGITAL SIGNATURE FROM
 THE ENGINEER OF RECORD
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-12 Cont ID  
Sent By dbattles Date 2023-07-12 Time 13:49 Rev Time 0.00
Received By dbattles Date 2023-07-06 Time 11:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By hmoser Date 2023-07-12 Time 08:41 Rev Time 0.00
Received By hmoser Date 2023-07-12 Time 08:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-10 Cont ID  
Sent By rwbrown Date 2023-07-10 Time 15:27 Rev Time 0.00
Received By rwbrown Date 2023-07-10 Time 15:27 Sent To  
Notes
2023-07-10 15:32:271ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - THE CHANGES TO THE
 PLUMBING REQUIRE THE PLUMBING PERMIT TO BE REOPENED.
 HOWEVER, THE PLUMBING CONTRACTOR'S INSURANCE IS EXPIRED
 AND NEEDS RENEWED. EITHER RENEW THE COI WITH THE
 PERMITTING DESK OR CHANGE CONTRACTORS SO I AN REOPEN
 THE PLUMBING PERMIT AND ADD THE APPROPRIATE INSPECTIONS
 TO INSEPECT THE LAUNDRY DRAIN AND SINK DRAIN. THESE
 WERE NOT LOOKED AT DURING THE PLUMBING INSPECTION.
  
 2. 2017 WPB AMENDS 107.2.1 - THE DRAWING DOES NOT
 ACCURATE DEPICT WHAT IS GOING INTO THE PROJECT. THE 3"
 FROM THE LAUNDRY EXITS IN THE OPPOSITE DIRECTION FROM
 THE LAUNDRY. ACCURATELY SHOW THE CONNECTIONS WITH WHAT
 IS ACTUALLY ON THE JOB. INCLUDE A FLOOR PLAN WITH THE
 PLUMBING PAGES TO SHOW THE ROUTING OF THE DRAINS IN
 REFERENCE TO THE LAYOUT AND FOOTPRINT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By dbattles Date 2023-07-12 Time 13:46 Rev Time 0.00
Received By dbattles Date 2023-07-12 Time 13:46 Sent To  
Notes
2023-07-12 13:49:39THE DRAWINGS SHOW STAMP THAT THEY WERE DIGITALLY
 SIGNED, BUT WHEN I OPEN THEM THERE IS NO DIGITAL
 SIGNATURE.
 PLEASE SUBMIT NEW SHEETS WITH DIGITAL SIGNATURES
 INTACT.

Review Stop Z ZONING
Rev No 1 Status P Date 2023-07-12 Cont ID  
Sent By lgelman Date 2023-07-12 Time 08:48 Rev Time 0.00
Received By vbroglia Date 2023-07-12 Time 08:48 Sent To  
Notes
***NONE***