Plan Review Details - Permit 23061390
Plan Review Stops For Permit 23061390
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-26 Cont ID  
Sent By jbrooks Date 2023-07-26 Time 10:27 Rev Time 0.00
Received By jbrooks Date 2023-07-26 Time 07:57 Sent To  
Notes
2023-07-26 10:27:16JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 REVISE SCOPE OF WORK ON PERMIT
 APPLICATION TO INCLUDE INCREASE VALUE FOR ROOF-TO-WALL
 MITIGATION. WORK TO BE PERFORMED BY A LICENSED
 RESIDENTIAL CONTRACTOR, LICENSED BUILDING CONTRACTOR OR
 LICENSED GENERAL CONTRACTOR. PROVIDE CONTRACTORS NAME &
 LICENSE NUMBER ON PERMIT APPLICATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By jbrooks Date 2023-07-06 Time 10:44 Rev Time 0.00
Received By jbrooks Date 2023-07-06 Time 08:04 Sent To  
Notes
2023-07-06 10:45:18JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3. SUBMITTED PRODUCT APPROVAL
 FL5680-R36 HAS BEEN REVISED TO FL5680-R37. PROVIDE THE
 FOLLOWING: COVER PAGE, EVALUATION REPORTS PAGES 1-6 TO
 INCLUDE LIMITATIONS PAGE(S) AND INSTALLATION
 INSTRUCTIONS FOR SYSTEMS TO BE USED.
 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER TO UPDATE PRODUCT
 APPROVAL TO THE CURRENT APPROVED VERSION
 FL5680-R37; INCLUDE UPDATED SYSTEMS/PAGE NUMBERS TO BE
 USED.
 3. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED. WOOD DECKS ONLY.
 4. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF
 DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE
 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020
 FBC-PLUMBING. ROOF #2 & #4E ONLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-26 Cont ID  
Sent By jbrooks Date 2023-07-26 Time 10:27 Rev Time 0.00
Received By jbrooks Date 2023-07-20 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-06 Cont ID  
Sent By jbrooks Date 2023-07-06 Time 10:45 Rev Time 0.00
Received By jbrooks Date 2023-07-05 Time 12:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-26 Cont ID  
Sent By jbrooks Date 2023-07-26 Time 10:27 Rev Time 0.00
Received By jbrooks Date 2023-07-26 Time 07:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By jbrooks Date 2023-07-06 Time 10:43 Rev Time 0.00
Received By jbrooks Date 2023-07-06 Time 10:37 Sent To  
Notes
2023-07-06 10:43:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS ARE COPIES OF WET SIGNATURES. PLEASE
 UPLOAD VALID ELECTRONICALLY SIGNED PLANS/DOCUMENTS TO
 PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  