Plan Review Details - Permit 23061371
Plan Review Stops For Permit 23061371
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-07-19 Cont ID  
Sent By pvalenti Date 2023-07-19 Time 13:13 Rev Time 0.00
Received By pvalenti Date 2023-07-19 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-07-03 Cont ID  
Sent By pvalenti Date 2023-07-03 Time 10:29 Rev Time 0.00
Received By pvalenti Date 2023-07-03 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-19 Cont ID  
Sent By ppetty Date 2023-07-19 Time 11:11 Rev Time 0.00
Received By ppetty Date 2023-07-19 Time 11:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By ppetty Date 2023-06-30 Time 13:34 Rev Time 0.00
Received By ppetty Date 2023-06-30 Time 11:55 Sent To  
Notes
2023-06-30 13:39:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2.PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB
 FBC 107.1; FS 471/481
 3.PROVIDE ELECTRICAL PLAN FOR REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-13 Cont ID  
Sent By pleduc Date 2023-07-13 Time   Rev Time 0.00
Received By pleduc Date 2023-07-13 Time 15:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 09:20 Sent To  
Notes
2023-07-06 09:39:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO CLEAR INDICATION OF WHERE THE TWO (2)
 CLEAR EXIT PATHS ARE THAT LEAD TO A PUBLIC WAY ONCE A
 PERSON LEAVES THE OFFICE DOOR.
  
 IT IS UNDERSTOOD THAT THIS IS A CONSTRUCTION SITE,
 HOWEVER, ONCE OCCUPIED AND PER NFPA 101 AND 241, TWO (
 2) CLEAR AND PROTECTED EXIT PATHS ARE REQUIRED THAT
 LEAD TO A PUBLIC WAY.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THETHE TWO (2)
 EXIT PATHS AND DIMENSIONS TO A PUBLIC WAY.
  
  
 2) THERE ARE SEVERAL INDICATIONS OF STORAGE WITHIN THE
 PROVIDED FLOOR PLAN SHEETS.
  
 PLEASE IDENTIFY WHAT THIS STORAGE MATERIAL IS, HOW IT
 WILL BE STORED(PALLETS/PLASTIC WRAP. ETC) AND HOW HIGH.
  
 THESE AREAS MAY RESTRICT/IMPEDE THE PATH OF EXIT/EGRESS
 PER # 1 ABOVE IF INVLOVED IN FIRE.
  
 ADDITIONAL PROVIDE A STATEMENT IS THESE AREAS WILL BE
 INCLUDED WITH THE FIRE SPRINKLER PROTECTION?
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-19 Cont ID  
Sent By pvalenti Date 2023-07-19 Time 13:21 Rev Time 0.00
Received By pvalenti Date 2023-07-12 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-07 Cont ID  
Sent By aoliver Date 2023-07-07 Time 08:02 Rev Time 0.00
Received By aoliver Date 2023-06-28 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By jbaker Date 2023-07-17 Time 12:34 Rev Time 0.00
Received By jbaker Date 2023-07-17 Time 12:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-03 Cont ID  
Sent By hmoser Date 2023-07-03 Time 10:25 Rev Time 0.00
Received By hmoser Date 2023-07-03 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By rwbrown Date 2023-07-17 Time 08:41 Rev Time 0.00
Received By rwbrown Date 2023-07-17 Time 08:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-06-30 Cont ID  
Sent By rwbrown Date 2023-06-30 Time 11:45 Rev Time 0.00
Received By rwbrown Date 2023-06-30 Time 11:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-07-19 Cont ID  
Sent By pvalenti Date 2023-07-19 Time 13:16 Rev Time 0.00
Received By pvalenti Date 2023-07-19 Time 13:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By jgomez Date 2023-06-28 Time 14:58 Rev Time 0.00
Received By jgomez Date 2023-06-28 Time 14:58 Sent To  
Notes
2023-06-28 15:04:13SIGNATURE REVIEW:
  
 1- ALL DRAWINGS NEED TO BE SIGNED AND SEALED WITH
 LICENSED DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 481 F.S. AND CHAPTER 471 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 (COPIES OF SIGNATURES ARE NOT ALLOWED. NEED ORIGINALS)
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 ENGINEERS
 61G15-23.004. F.A.C. PROCEDURES FOR DIGITALLY SIGNING
 AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.