Plan Review Details - Permit 23061336
Plan Review Stops For Permit 23061336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By jbrooks Date 2023-06-29 Time 11:25 Rev Time 0.00
Received By jbrooks Date 2023-06-29 Time 07:52 Sent To  
Notes
2023-06-29 11:25:54JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 THE CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. PLEASE
 NOTE THIS PROJECT IS LOCATED IN AN EXPOSURE C CATEGORY
 AREA.
 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 ROOFING TILE SYSTEM TO BE USED. INCLUDE COVER PAGE,
 EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH OF EACH BUILDING WITH THE AREAS TO
 RECEIVE NEW ROOFING TILES CLEARLY IDENTIFIED ON
 DRAWING. PROVIDE TOTAL SQUARE FOOTAGE OF THE ROOF TILE
 AREA. PROVIDE TOTAL SQUARE FOOTAGE OF AREAS TO RECEIVE
 NEW ROOF TILES AND CLEARLY IDENTIFY ON ROOF SKETCH. NOT
 MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF
 SECTION OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12-MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION IS
 REPLACED TO CONFORM TO THIS CODE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-07-18 Cont ID  
Sent By amhamilt Date 2023-07-18 Time 16:14 Rev Time 0.00
Received By amhamilt Date 2023-07-18 Time 16:14 Sent To  
Notes
2023-07-18 16:15:12THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 WHAT TYPE OF TILE WILL BE USED? MUST BE BARREL TILE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-19 Cont ID  
Sent By aoliver Date 2023-07-19 Time 09:07 Rev Time 0.00
Received By aoliver Date 2023-06-28 Time 13:23 Sent To  
Notes
***NONE***