Plan Review Details - Permit 23061311
Plan Review Stops For Permit 23061311
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By cthroop Date 2023-06-30 Time 09:54 Rev Time 0.00
Received By cthroop Date 2023-06-29 Time 12:41 Sent To  
Notes
2023-06-30 09:59:021ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM US-21-11935
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARXD AREA (SFHA). THE FLOOD ZONE IS AE7 WITH A BASED
 FLOOD ELEVATION OF 7.0' NAVD. THE DESIGN FLOOD
 ELEVATION IS 9.0' NAVD.
  
 1. SUBMIT A CONSTRUCTION DRAWING ELEVATION CERTIFICATE.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 2. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY
 LOCATION OF WORK.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDRY LINE SURVEY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-05 Cont ID  
Sent By rperdomo Date 2023-07-05 Time 10:55 Rev Time 0.00
Received By rperdomo Date 2023-07-05 Time 10:42 Sent To  
Notes
2023-07-05 10:57:00FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE ELECTRICAL SCOPE OF WORK. FBC 107.2.1,
 107.3.5, AND FS 471.003(2), 471.025
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-14 Cont ID  
Sent By ecolon Date 2023-07-14 Time 10:16 Rev Time 0.00
Received By aoliver Date 2023-06-28 Time 13:17 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By cthroop Date 2023-06-30 Time 09:59 Rev Time 0.00
Received By cthroop Date 2023-06-30 Time 09:19 Sent To  
Notes
2023-06-30 10:32:371ST NFIP REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM US-21-11935
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CONSTRUCTION TRAILER
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE
 IS AE 7 WITH A BASE FLOOD ELEVATION (BFE) OF 7???0???
 NAVD.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9???0??? NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
  
 BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS ONE FOOT, OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER. (PLUS TWO FEET PER CITY ORDINANCE 4729-17).
  
 2. PROVIDE A CONSTRUCTION DRAWING ELEVATION
 CERTIFICATES AS REQUIRED.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By ccole Date 2023-06-29 Time 14:41 Rev Time 0.00
Received By ccole Date 2023-06-29 Time 13:51 Sent To  
Notes
2023-06-29 14:43:221ST REVIEW FBC-RES. 2020 PLUMBING
 PERMIT- 23061311
 6/29/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA RESIDENTIAL CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) POTABLE WATER SERVICE AND A SEWERAGE DISPOSAL SYSTEM
 ARE REQUIRED FOR THE JOB SITE TRAILER- SEC.108.2 WPB
 AND SEC. P2602.1 FBC RES. CURRENTLY NO MODULAR PLANS
 HAVE BEEN SUBMITTED HOWEVER IF THE TRAILER CONTAINS
 PLUMBING FIXTURES INTENDED FOR USE BY THE OCCUPANTS,
 PLEASE NOTE SEC. P2601 FBC RES BELOW-
 THE WATER-DISTRIBUTION AND DRAINAGE SYSTEM OF ANY
 BUILDING OR PREMISES WHERE PLUMBING FIXTURES ARE
 INSTALLED SHALL BE CONNECTED TO A PUBLIC WATER SUPPLY
 OR SEWER SYSTEM, RESPECTIVELY, IF AVAILABLE. WHERE
 EITHER A PUBLIC WATER-SUPPLY OR SEWER SYSTEM, OR BOTH,
 ARE NOT AVAILABLE, OR CONNECTION TO THEM IS NOT
 FEASIBLE, AN INDIVIDUAL WATER SUPPLY OR INDIVIDUAL
 (PRIVATE) SEWAGE-DISPOSAL SYSTEM, OR BOTH, SHALL BE
 PROVIDED. INDIVIDUAL WATER SUPPLIES SHALL BE
 CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE
 APPLICABLE STATE AND LOCAL LAWS. WHERE SUCH LAWS DO NOT
 ADDRESS ALL OF THE REQUIREMENTS SET FORTH IN NGWA-01,
 INDIVIDUAL WATER SUPPLIES SHALL COMPLY WITH NGWA-01 FOR
 THOSE REQUIREMENTS NOT ADDRESSED BY STATE AND LOCAL
 LAWS.
  
 2) WATER SERVICE SUBMITTAL: SHOW THE TYPE AND SIZE OF
 SERVICE LINE, SERVICE LINE RUN, POINT OF CONNECTION TO
 THE CITY MAIN, AND THE LOCATIONS OF THE WATER METER AND
 BACKFLOW PREVENTER. INDICATE THE TYPE AND SIZE OF
 BACKFLOW PREVENTER TO BE INSTALLED- SECS. P2901.1 &
 P2902.3 FBC RES AND SEC. E WPB UTILITIES CROSS
 CONNECTION MANUAL.
  
 A) CONCERNING THE BACKFLOW PREVENTER PLEASE NOTE A
 PERMIT APPLICATION SHALL BE SUBMITTED FOR THE
 INSTALLATION PRIOR TO APPROVAL OF THE PLUMBING PLAN
 REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 3) SANITARY SEWER SUBMITTAL: PROVIDE EITHER A DIRECT
 PIPE CONNECTION TO THE CITY SEWER LINE OR AN ONSITE
 SYSTEM SUCH AS A HOLDING TANK WITH PUMP-OUT CAPABILITY.
  
 A) SEWER CONNECTION- SHOW THE TYPE AND SIZE OF BUILDING
 DRAIN PIPE, THE DRAIN PIPE RUN, POINT OF CONNECTION TO
 THE SEWER LINE, AND CLEANOUT LOCATIONS- SEC. P3001.1
 FBC RES.
  
 B) PUMP TANK- SHOW THE LOCATION OF THE TANK ON THE
 PLAN, PROVIDE A PIPING DIAGRAM, AND SUBMIT
 MANUFACTURER???S SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-29 Cont ID  
Sent By cthroop Date 2023-06-29 Time 12:41 Rev Time 0.00
Received By cthroop Date 2023-06-29 Time 12:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By ecolon Date 2023-07-14 Time 10:15 Rev Time 0.00
Received By ecolon Date 2023-07-14 Time 10:09 Sent To  
Notes
2023-07-14 10:15:51PLEASE ILLUSTRATE LOCATION OF PROPOSED SITE TRAILER ON
 SURVEY/SITE PLAN. STRUCTURE MUST BE LOCATED WITHIN
 PROPERTY LINES AND CANNOT BE LOCATED INSIDE A
 VISIBILITY TRIANGLE.
  
 AS PER CITY CODE ARTICLE IX SEC. 94-273:
 TEMPORARY OFFICES AND FACILITIES FOR CONSTRUCTION,
 STORAGE AND SECURITY (PXR: SEE ITEM 160, TABLE IX-1).
 A.ADDITIONAL APPLICATION REQUIREMENTS. NONE.
 B.ADDITIONAL STANDARDS.
 1.TEMPORARY CONSTRUCTION OFFICES, STORAGE BUILDINGS,
 TRAILERS, AND WATCHMEN'S QUARTERS SHALL BE PERMITTED TO
 EXPEDITE CONSTRUCTION ON THE PROPERTY ON WHICH LOCATED.
 2.ALL SUCH STRUCTURES, INCLUDING TRAILERS, SHALL BE
 REMOVED WITHIN SEVEN DAYS OF THE FINAL CONSTRUCTION
 INSPECTION BY THE CITY AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY.
  
  
 ***** REVIEWED BY *****
  