| 2023-06-29 14:43:22 | 1ST REVIEW FBC-RES. 2020 PLUMBING |
| | PERMIT- 23061311 |
| | 6/29/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA RESIDENTIAL CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) POTABLE WATER SERVICE AND A SEWERAGE DISPOSAL SYSTEM |
| | ARE REQUIRED FOR THE JOB SITE TRAILER- SEC.108.2 WPB |
| | AND SEC. P2602.1 FBC RES. CURRENTLY NO MODULAR PLANS |
| | HAVE BEEN SUBMITTED HOWEVER IF THE TRAILER CONTAINS |
| | PLUMBING FIXTURES INTENDED FOR USE BY THE OCCUPANTS, |
| | PLEASE NOTE SEC. P2601 FBC RES BELOW- |
| | THE WATER-DISTRIBUTION AND DRAINAGE SYSTEM OF ANY |
| | BUILDING OR PREMISES WHERE PLUMBING FIXTURES ARE |
| | INSTALLED SHALL BE CONNECTED TO A PUBLIC WATER SUPPLY |
| | OR SEWER SYSTEM, RESPECTIVELY, IF AVAILABLE. WHERE |
| | EITHER A PUBLIC WATER-SUPPLY OR SEWER SYSTEM, OR BOTH, |
| | ARE NOT AVAILABLE, OR CONNECTION TO THEM IS NOT |
| | FEASIBLE, AN INDIVIDUAL WATER SUPPLY OR INDIVIDUAL |
| | (PRIVATE) SEWAGE-DISPOSAL SYSTEM, OR BOTH, SHALL BE |
| | PROVIDED. INDIVIDUAL WATER SUPPLIES SHALL BE |
| | CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE |
| | APPLICABLE STATE AND LOCAL LAWS. WHERE SUCH LAWS DO NOT |
| | ADDRESS ALL OF THE REQUIREMENTS SET FORTH IN NGWA-01, |
| | INDIVIDUAL WATER SUPPLIES SHALL COMPLY WITH NGWA-01 FOR |
| | THOSE REQUIREMENTS NOT ADDRESSED BY STATE AND LOCAL |
| | LAWS. |
| | |
| | 2) WATER SERVICE SUBMITTAL: SHOW THE TYPE AND SIZE OF |
| | SERVICE LINE, SERVICE LINE RUN, POINT OF CONNECTION TO |
| | THE CITY MAIN, AND THE LOCATIONS OF THE WATER METER AND |
| | BACKFLOW PREVENTER. INDICATE THE TYPE AND SIZE OF |
| | BACKFLOW PREVENTER TO BE INSTALLED- SECS. P2901.1 & |
| | P2902.3 FBC RES AND SEC. E WPB UTILITIES CROSS |
| | CONNECTION MANUAL. |
| | |
| | A) CONCERNING THE BACKFLOW PREVENTER PLEASE NOTE A |
| | PERMIT APPLICATION SHALL BE SUBMITTED FOR THE |
| | INSTALLATION PRIOR TO APPROVAL OF THE PLUMBING PLAN |
| | REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE |
| | THE REVIEW STATUS TO PASS. |
| | |
| | 3) SANITARY SEWER SUBMITTAL: PROVIDE EITHER A DIRECT |
| | PIPE CONNECTION TO THE CITY SEWER LINE OR AN ONSITE |
| | SYSTEM SUCH AS A HOLDING TANK WITH PUMP-OUT CAPABILITY. |
| | |
| | A) SEWER CONNECTION- SHOW THE TYPE AND SIZE OF BUILDING |
| | DRAIN PIPE, THE DRAIN PIPE RUN, POINT OF CONNECTION TO |
| | THE SEWER LINE, AND CLEANOUT LOCATIONS- SEC. P3001.1 |
| | FBC RES. |
| | |
| | B) PUMP TANK- SHOW THE LOCATION OF THE TANK ON THE |
| | PLAN, PROVIDE A PIPING DIAGRAM, AND SUBMIT |
| | MANUFACTURER???S SPECIFICATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |