Plan Review Details - Permit 23061300
Plan Review Stops For Permit 23061300
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-31 Cont ID  
Sent By jgomez Date 2023-07-31 Time 19:14 Rev Time 0.00
Received By jgomez Date 2023-07-28 Time 18:23 Sent To  
Notes
2023-07-31 19:17:53SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23061300
 600 S DIXIE HWY # 251
  
  
 PREVIOUS COMMENT;
 1- PERMIT APPLICATION CALLS FOR INSTALLATION OF VINYL
 FLOORING PLANKS. COPIES OF THE UNDERLAYMENT TEST
 SUBMITTED ARE FOR LAMINATED FLOORING. NEED TO PROVIDE
 TEST COPIES FOR VINYL PLANKS. SEE COMMENTS BELOW:
  
 RESPONSE:
 THE LUXURY VINYL PLANK TESTED IN THE TESTS SUBMITTED IS
 NOT THE SAME LUXURY VINYL PLANK SUBMITTED. THE LUXURY
 VINYL PLANK MUST MATCH THE ONE TESTED. NEED TO
 RESUBMIT.
  
 FLOORING SOUND INSULATION MATERIAL:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 AND 720.2 OF FBC
 7TH EDITION (2020).
  
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
 NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH
 OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT
 SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT).
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-24 Cont ID  
Sent By jgomez Date 2023-07-24 Time 17:44 Rev Time 0.00
Received By jgomez Date 2023-07-24 Time 17:30 Sent To  
Notes
2023-07-24 17:45:03BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23061300
 600 S DIXIE HWY # 251
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- PERMIT APPLICATION CALLS FOR INSTALLATION OF VINYL
 FLOORING PLANKS. COPIES OF THE UNDERLAYMENT TEST
 SUBMITTED ARE FOR LAMINATED FLOORING. NEED TO PROVIDE
 TEST COPIES FOR VINYL PLANKS. SEE COMMENTS BELOW:
  
 FLOORING SOUND INSULATION MATERIAL:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 AND 720.2 OF FBC
 7TH EDITION (2020).
  
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
 NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH
 OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT
 SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT).
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-27 Cont ID  
Sent By pleduc Date 2023-07-27 Time   Rev Time 0.00
Received By pleduc Date 2023-07-27 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-31 Cont ID  
Sent By jgomez Date 2023-07-31 Time 19:17 Rev Time 0.00
Received By jgomez Date 2023-07-26 Time 08:46 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-24 Cont ID  
Sent By jgomez Date 2023-07-24 Time 17:45 Rev Time 0.00
Received By jgomez Date 2023-06-28 Time 12:16 Sent To I
Notes
***NONE***