| Plan Review Stops For Permit 23061294 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-07-28 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-07-28 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-07-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-07-11 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-07-11 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2023-07-11 14:26:03 | RESIDENTIAL(R3) REVISION BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | REVISION #23061294 | | | 101 GREYMON DR | | | | | | DIGITAL SIGNATURE REVIEW: | | | 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | | REQUIREMENTS OF FBPE: | | | | | | A) NEED A SEPARATE TEXT BOX WITH THE TEXT BOX LANGUAGE | | | IDENTICAL TO THE SAMPLES SHOWN BY FBPE. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | B)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-07-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-07-10 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-07-10 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-07-26 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-07-26 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-30 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-30 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-25 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-17 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-07-17 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-07-17 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-07-17 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-07-26 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-07-26 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-30 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-30 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-07-28 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-07-28 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-07-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-07-11 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-07-11 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2023-07-11 14:26:32 | DIGITAL SIGNATURE REVIEW: | | | 1- ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE | | | REQUIREMENTS OF FBPE: | | | | | | A) NEED A SEPARATE TEXT BOX WITH THE TEXT BOX LANGUAGE | | | IDENTICAL TO THE SAMPLES SHOWN BY FBPE. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | B)THE TEXT BOX LANGUAGE MUST NOT BE A PART OF THE | | | DIGITAL SIGNATURE ITSELF. | | | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU | | | MENTS/ AND REVISE AS REQUIRED | | | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. | | | | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|