Plan Review Details - Permit 23061257
Plan Review Stops For Permit 23061257
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-07-20 Cont ID  
Sent By jgomez Date 2023-07-20 Time 17:34 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-07-20 Cont ID  
Sent By jgomez Date 2023-07-20 Time 16:04 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 15:52 Sent To  
Notes
2023-07-20 16:06:21RESIDENTIAL REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23061257
 521 17TH ST
  
 1- REVISE DIGITAL SIGNATURE ON NEW ENGINEER
 CALCULATIONS:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 RESPONSE:
 REPEAT COMMENT THREE TIMES. NEW ENGINEER DOESN'T COMPLY
 WITH THE REQUESTED INFORMATION EITHER.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-07-14 Cont ID  
Sent By jgomez Date 2023-07-14 Time 15:17 Rev Time 0.00
Received By jgomez Date 2023-07-14 Time 14:42 Sent To  
Notes
2023-07-14 15:35:04RESIDENTIAL REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23061257
 521 17TH ST
  
 1- REVISE DIGITAL SIGNATURE ON NEW ENGINEER
 CALCULATIONS:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-10 Cont ID  
Sent By jgomez Date 2023-07-10 Time 18:01 Rev Time 0.00
Received By jgomez Date 2023-07-10 Time 17:10 Sent To  
Notes
2023-07-10 18:01:19RESIDENTIAL REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23061257
 521 17TH ST
  
 1- REVISE DIGITAL SIGNATURE ON ENGINEER CALCULATIONS:
 A)CALCULATIONS HAVE AN ENGINEER'S SELF CERTIFIED
 DIGITAL SIGNATURE. ENGINEER CAN NOT SELF CERTIFY THE
 DIGITAL SIGNATURE. THIRD PARTY CERTIFICATION IS
 REQUIRED BY FAC 61G15-23.004. (NOTE: ENGINEER TO
 CONTACT THE BOARD OF ENGINEER'S FOR SELF CERTIFIED
 DIGITAL SIGNATURE QUESTIONS).
  
 B)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-06 Cont ID  
Sent By jbrooks Date 2023-07-06 Time 11:31 Rev Time 0.00
Received By jbrooks Date 2023-07-06 Time 08:13 Sent To  
Notes
2023-07-06 11:32:00JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. PROVIDE THE FOLLOWING INFORMATION FOR
 MIAMI-DADE NOA NO.: 18-0919.12 FOR THE PROPOSED FLAT
 ROOF SYSTEM TO BE USED CORRESPONDING TO ENGINEERS
 CALCULATIONS. INSTALLATION INSTRUCTIONS FOR SYSTEM E
 (1) PAGE(S) #51-52. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. SECOND REQUEST.
 2. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF
 DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD
 OF PROVIDING POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By jbrooks Date 2023-06-29 Time 09:02 Rev Time 0.00
Received By jbrooks Date 2023-06-29 Time 07:38 Sent To  
Notes
2023-06-29 09:03:05JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. PROVIDE THE FOLLOWING INFORMATION FOR
 MIAMI-DADE NOA NO.: 18-0919.12 FOR THE PROPOSED FLAT
 ROOF SYSTEM TO BE USED CORRESPONDING TO ENGINEERS
 CALCULATIONS. INSTALLATION INSTRUCTIONS FOR SYSTEM E
 (1) PAGE(S) #51-52. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-07-20 Cont ID  
Sent By jgomez Date 2023-07-20 Time 17:34 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 17:26 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-07-20 Cont ID  
Sent By jgomez Date 2023-07-20 Time 16:07 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 15:52 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-14 Cont ID  
Sent By jgomez Date 2023-07-14 Time 15:19 Rev Time 0.00
Received By jgomez Date 2023-07-14 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-10 Cont ID  
Sent By jgomez Date 2023-07-10 Time 18:02 Rev Time 0.00
Received By jgomez Date 2023-07-10 Time 17:09 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-06 Cont ID  
Sent By jbrooks Date 2023-07-06 Time 11:32 Rev Time 0.00
Received By jbrooks Date 2023-07-03 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-29 Cont ID  
Sent By jbrooks Date 2023-06-29 Time 09:03 Rev Time 0.00
Received By jbrooks Date 2023-06-27 Time 12:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-07-20 Cont ID  
Sent By jgomez Date 2023-07-20 Time 17:34 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 17:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-07-20 Cont ID  
Sent By jgomez Date 2023-07-20 Time 16:06 Rev Time 0.00
Received By jgomez Date 2023-07-20 Time 16:06 Sent To  
Notes
2023-07-20 16:06:521- REVISE DIGITAL SIGNATURE ON NEW ENGINEER
 CALCULATIONS:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 RESPONSE:
 REPEAT COMMENT THREE TIMES. NEW ENGINEER DOESN'T COMPLY
 WITH THE REQUESTED INFORMATION EITHER.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-07-14 Cont ID  
Sent By jgomez Date 2023-07-14 Time 15:18 Rev Time 0.00
Received By jgomez Date 2023-07-14 Time 15:18 Sent To  
Notes
2023-07-14 15:18:371- REVISE DIGITAL SIGNATURE ON NEW ENGINEER
 CALCULATIONS:
 ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-07-10 Cont ID  
Sent By jgomez Date 2023-07-10 Time 18:01 Rev Time 0.00
Received By jgomez Date 2023-07-10 Time 18:01 Sent To  
Notes
2023-07-10 17:45:36DIGITAL SIGNATURE REVIEW:
  
 1- REVISE DIGITAL SIGNATURE ON ENGINEER CALCULATIONS:
 A)CALCULATIONS HAVE AN ENGINEER'S SELF CERTIFIED
 DIGITAL SIGNATURE. ENGINEER CAN NOT SELF CERTIFY THE
 DIGITAL SIGNATURE. THIRD PARTY CERTIFICATION IS
 REQUIRED BY FAC 61G15-23.004. (NOTE: ENGINEER TO
 CONTACT THE BOARD OF ENGINEER'S FOR SELF CERTIFIED
 DIGITAL SIGNATURE QUESTIONS).
  
 B)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-07-06 Cont ID  
Sent By jbrooks Date 2023-07-06 Time 11:33 Rev Time 0.00
Received By jbrooks Date 2023-07-06 Time 11:33 Sent To  
Notes
2023-07-06 11:34:10JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS IS A COPY OF A WET SIGNATURE. PLEASE
 UPLOAD VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO
 PROJECTDOX. SECOND REQUEST.
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By jbrooks Date 2023-06-29 Time 09:03 Rev Time 0.00
Received By jbrooks Date 2023-06-29 Time 08:48 Sent To  
Notes
2023-06-29 09:03:51JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS IS A COPY OF A WET SIGNATURE. PLEASE
 UPLOAD A VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO
 PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  