Plan Review Details - Permit 23061207
Plan Review Stops For Permit 23061207
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-12 Cont ID  
Sent By rmcdouga Date 2023-07-12 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2023-07-12 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2023-07-07 Time 08:01 Sent To  
Notes
2023-07-07 09:13:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ NOT RESOLVED. THE SAME NOTES THAT WERE DENIED ARE
 ON THE SURVEY THAT WAS SUBMITTED.] THE GENERATOR
 EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET FROM ANY
 OPENINGS INTO A BUILDING. THIS CAN BE NOTED ON THE
 SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE
 OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 NOTE: IT APPEARS FROM THE SURVEY THAT THE GENERATOR IS
 4 FEET FROM THE WALL OF THE BUILDING. GENERATORS ARE
 TYPICALLY REQUIRED TO BE FIVE AWAY FROM A BUILDING FOR
 VENTILATION AND FIRE CONCERNS. CHECK THE MANUFACTURER'S
 SPECIFICATIONS FOR THE GENERATOR. FBC FUEL GAS 616.1,
 NFPA 37 SECTION 4.1.4 AND UL2200
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By rmcdouga Date 2023-06-28 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2023-06-28 Time 16:29 Sent To  
Notes
2023-06-28 16:45:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. THIS CAN BE
 NOTED ON THE SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE
 OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-30 Cont ID  
Sent By jleahy Date 2023-06-30 Time 15:50 Rev Time 0.00
Received By jleahy Date 2023-06-30 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-14 Cont ID  
Sent By asangele Date 2023-07-14 Time 09:11 Rev Time 0.00
Received By asangele Date 2023-07-14 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-07 Cont ID  
Sent By asangele Date 2023-07-07 Time 11:38 Rev Time 0.00
Received By asangele Date 2023-07-07 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-30 Cont ID  
Sent By jleahy Date 2023-06-30 Time 15:50 Rev Time 0.00
Received By jleahy Date 2023-06-26 Time 11:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By rmcdouga Date 2023-06-28 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2023-06-28 Time 16:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-14 Cont ID  
Sent By asangele Date 2023-07-14 Time 09:11 Rev Time 0.00
Received By asangele Date 2023-07-14 Time 09:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-07-07 Cont ID  
Sent By asangele Date 2023-07-07 Time 11:38 Rev Time 0.00
Received By asangele Date 2023-07-07 Time 11:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-06-30 Cont ID  
Sent By asangele Date 2023-06-30 Time 13:38 Rev Time 0.00
Received By asangele Date 2023-06-30 Time 13:38 Sent To  
Notes
***NONE***