|
 |
 |
 |
 |
 |
Plan Review Details - Permit 23061207
| Plan Review Stops For Permit 23061207 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-07-12 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-07-12 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-07-07 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-07-07 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2023-07-07 09:13:18 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [ NOT RESOLVED. THE SAME NOTES THAT WERE DENIED ARE | | | ON THE SURVEY THAT WAS SUBMITTED.] THE GENERATOR | | | EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET FROM ANY | | | OPENINGS INTO A BUILDING. THIS CAN BE NOTED ON THE | | | SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE | | | OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | NOTE: IT APPEARS FROM THE SURVEY THAT THE GENERATOR IS | | | 4 FEET FROM THE WALL OF THE BUILDING. GENERATORS ARE | | | TYPICALLY REQUIRED TO BE FIVE AWAY FROM A BUILDING FOR | | | VENTILATION AND FIRE CONCERNS. CHECK THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE GENERATOR. FBC FUEL GAS 616.1, | | | NFPA 37 SECTION 4.1.4 AND UL2200 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-28 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-06-28 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2023-06-28 16:45:04 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. THIS CAN BE | | | NOTED ON THE SURVEY/SITE PLAN. FBC-R303.5.1 INTAKE | | | OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-06-30 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-06-30 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-14 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-14 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-07 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-07 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-06-30 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-06-26 |
Time |
11:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-28 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-06-28 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-07-14 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-14 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-14 |
Time |
09:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-07-07 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-07 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-07 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-06-30 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-06-30 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-06-30 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |