Plan Review Details - Permit 23061190
Plan Review Stops For Permit 23061190
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-26 Cont ID  
Sent By pleduc Date 2023-07-26 Time   Rev Time 0.00
Received By pleduc Date 2023-07-26 Time 13:15 Sent To  
Notes
2023-07-26 13:26:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 004 EXISTING - THERE IS AN INDICATION OF
 GENERAL QUESTIONS WITH EACH OF THE PICTURES.
  
 A LIFE SAFETY REVIEW FOR COMPLIANCE CAN NOT BE DONE
 WITH OPEN ENDED QUESTIONS WITH NO DETAILS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE SPECIFIC
 DETAILS OF THE PROPOSED WORK IN SUPPORT OF THE CODE
 REQUIREMENTS FOR SUCH WORK.
  
  
 2) SHEET A 141 & 142 - THERE IS AN INDICATION OF DRAFT
 ACROSS EACH OF THE ELEVATION DRAWINGS.
  
 A LIFE SAFETY REVIEW FOR COMPLIANCE CAN NOT BE DONE
 WITH A DRAFT DRAWING.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE SPECIFIC
 DETAILS OF THE PROPOSED WORK IN SUPPORT OF THE CODE
 REQUIREMENTS FOR SUCH WORK.
  
  
  
 3) THERE ARE NO INDICATIONS OF EXISTING FIRE SPRINLKER
 AND/OR FIRE ALARM SYSTEMS WITHIN THE EXISTING
 STRUCTURE.
  
 ANY FS & FA EXISTING SHALL BE EXTENDED TO THE ADDITION
 IF APPROVED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW EXISTING BUILDING AND PROVIDE IF ANY FS &
 FA EQUIDPMENT DEVICES ARE PRESENT.
  
 IF SO, PROVIDE A NOTE OF ACKNOWLEDGMENT TO EXTEND FS &
 FA TO THE PROPOSED ADDITION UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 IF NOT, PROVIDE AN APPLICABLE NOTE INDICATING SUCH.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-24 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***