Plan Review Details - Permit 23061080
Plan Review Stops For Permit 23061080
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-26 Cont ID  
Sent By jwitmer Date 2023-07-26 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 15:36 Sent To  
Notes
2023-07-18 16:13:37WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23061080
 ADD: 310 N OLIVE AVE. / ST. ANN???S SCHOOL
 CONT: ALONSO & ASSOCIATES, INC.
 TEL: 561-837-9820
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 18, 2023
 ACTION: DENIED
  
 1) DISCREPANCY IN THE LOCATION WHERE WORK IS TO OCCUR.
 THE PERMIT APPLICATION STATES WORK IS TO OCCUR ON THE
 3RD FLOOR WHEREAS THE FLOOR PLAN STATES EXISTING 2ND
 FLOOR, PROPOSED WORK 2ND FLOOR. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2A) SHEET A-1 THERE ARE NO NOTES ON THIS PLAN FOR WET
 WALL FINISHES. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 2C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 2D) ADA RESTROOM NOTE 15 CLEAR FLOOR SPACE FOR WATER
 CLOSET SHOWS 48X56 INCHES, PLEASE REVIEW 2020
 FBC-ACCESSIBILITY CODE CLEARANCE/ SIZE SECTION 604.3.1.
 CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE WATER
 CLOSET. SECTION 604.3.
  
 2E) THE FLOOR PLAN SUBMITTED DOES NOT STATE THE AGE OF
 THE CHILDREN THAT WILL BE USING THESE RESTROOMS. PLEASE
 REVIEW IN THE 2020 FBC-ACCESSIBILITY CODE 604.9 AND
 ADVISORY FOR CHILDREN???S USE VERSES AGE RANGES.
  
 2F) THE FLOOR PLAN SHOWS ELEVATIONS FOR URINALS THE TOP
 OF URINAL RIM AT 2 FEET ABOVE FINISH FLOOR, PLEASE SEE
 SECTION 605.2 2020 FBC-ACCESS. CODE.
  
 3) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
  
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-19 Cont ID  
Sent By jleahy Date 2023-07-19 Time 11:40 Rev Time 0.00
Received By mpeterso Date 2023-07-19 Time 12:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-06-27 Cont ID  
Sent By pleduc Date 2023-06-27 Time   Rev Time 0.00
Received By pleduc Date 2023-06-27 Time 15:03 Sent To  
Notes
2023-06-27 15:53:41FIRE PROVISO:
  
 DUE TO THE CONSTRUCTION MODIFICATIONS IT REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-28 Cont ID  
Sent By aoliver Date 2023-07-28 Time 07:26 Rev Time 0.00
Received By aoliver Date 2023-06-23 Time 12:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 15:35 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 15:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-19 Cont ID  
Sent By hmoser Date 2023-07-19 Time 09:50 Rev Time 0.00
Received By hmoser Date 2023-07-19 Time 08:51 Sent To  
Notes
2023-07-19 10:42:43PASS PROVISO
 REFER TO SECTION 307 CONDENSATE DISPOSAL
 2020 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By ccole Date 2023-07-19 Time 08:21 Rev Time 0.00
Received By ccole Date 2023-07-18 Time 16:44 Sent To  
Notes
2023-07-19 08:23:071ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23061080
 7/18/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-1 & P-2: PLEASE CLARIFY HOW THE NUMBER OF
 BOY'S AND GIRL'S BATHROOM FIXTURES WERE DETERMINED.
 REFER TO SEC. 468.3.5.1 FBC B AND TABLE 403.1 FBC P AND
 PROVIDE PLUMBING FIXTURE CALCULATIONS. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES. FIXTURE RATIOS FOR EACH FIXTURE
 TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF EACH SEX.
 PLEASE NOTE, BY COMPARISON, THE PLAN SHOWS A GREATER
 NUMBER OF WATER CLOSETS/URINALS FOR BOYS THAN THE
 GIRLS.
  
 A) DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR E
 OCCUPANCIES- TABLE 403.1. WHERE ARE THESE FIXTURES
 LOCATED?
  
 B) REFER TO SEC. 604.1 EXCEPTION AND 604.9 AND INDICATE
 THE AGES OF THE STUDENTS WHO WILL BE USING THE BATHROOM
 FACILITIES.
  
 2) A-1 & P-2: SEC. 213.1 STATES TOILET AND BATHING
 FACILITIES SHALL COMPLY WITH 213 INCLUDING 213.3 &
 213.3.1. SEC. 213.3.1 STATES WHERE TOILET COMPARTMENTS
 ARE PROVIDED A MINIMUM OF ONE TOILET COMPARTMENT SHALL
 COMPLY WITH 604.8.1. PLEASE PROVIDE ONE WHEELCHAIR
 ACCESSIBLE COMPARTMENT IN EACH BATHROOM.
  
 A) IN ADDITION TO THE WHEELCHAIR ACCESSIBLE
 COMPARTMENT, AN AMBULATORY TOILET COMPARTMENT IS
 REQUIRED IN THE BOY'S BATHROOM- SEC. 213.3.1 FBC ACC.
  
 B) SHOW A CLEAR FLOOR SPACE DIAGRAM WITH DIMENSIONS AT
 THE LOCATION OF THE ACCESSIBLE URINAL- SEC.605.3.
  
 3) A-1: DETAIL 4/A-1 SHOWS A 48X56-INCH CLEAR FLOOR
 SPACE FOR THE WATER CLOSET HOWEVER SEC. 604.3.1 FBC ACC
 REQUIRES A 60-INCH WIDE CLEAR FLOOR SPACE MEASURED
 PERPENDICULARLY FROM THE SIDE WALL.
  
 4) A-1 MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS PER
 FBC ACC:
  
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 B) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
  
 C) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3.
  
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
  
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
  
 F) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
  
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 H) HEIGHT OF THE ACCESSIBLE URINAL RIM ABOVE THE FINISH
 FLOOR, AND DEPTH OF THE URINAL FROM THE OUTER FACE TO
 THE BACK OF THE FIXTURE- SEC. 605.2.
  
 5) P-1: ACCESSIBLE LAVATORY SINKS NOT INCLUDED IN THE
 FIXTURE SCHEDULE- SEC. 419.1 FBC P.
  
 6) P-1 & P-2: REFER TO SEC. 468.3.5.6 FBC B AND PROVIDE
 A MINIMUM OF ONE FLOOR DRAIN AND ONE EASILY ACCESSIBLE
 HOSE BIB IN THE BOYS AND GIRLS BATHROOMS.
  
 7) P-1 & P-2: REFER TO SEC. 468.3.5.12 AND PROVIDE
 MIXING VALVES AT THE LAVATORIES TO LIMIT THE HOT WATER
 DELIVERY TEMPERATURE TO 95 DEGREES F MINIMUM AND 110
 DEGREES F MAXIMUM.
  
 8) P1 & P2: PLEASE PROVIDE A PIPING DETAIL FOR THE NEW
 WATER HEATER SHOWING THE REQUIRED DEVICES AND PIPING
 CONNECTIONS-
  
 A) THERMOSTATIC MIXING VALVE- SEC. 607.1.1 FBC P.
  
 B) EXPANSION CONTROL DEVICE- SEC. 607.3.
  
 C) RELIEF VALVE, DRAIN PAN, PAN DRAIN LINE AND
 DISCHARGE LOCATION- SECS. 504.4- 504.7.2.
  
 9) P2: THE LOCATION OF THE KEYED NOTED IN SCHEDULE ARE
 NOT SHOWN ON THE DRAWINGS DON'T APPEAR RELATIVE- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2023-07-25 Cont ID  
Sent By jwitmer Date 2023-07-25 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2023-07-25 Time 06:40 Sent To  
Notes
2023-07-25 07:59:48WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 PRIVATE PROVIDER REVIEW
 W. P. B. PERMIT: 23061080
 ADD: 310 N OLIVE AVE. ST. ANN???S SCHOOL
 CONT: ALONSO & ASSOCIATES
 TEL: 561-8379820
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 25/23
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE CONTRACTOR HAS
 REQUESTED THE USE OF A PRIVATE PROVIDER, BUT THE
 CONTRACTOR HAS NOT INDICATED ON THE PERMIT APPLICATION
 IF THIS IS FOR PLAN, REVIEW, INSPECTIONS OR IF BOTH?
 THE CONTRACTOR HAS NEGLECTED TO ALSO PROVIDE THE SIGNED
 FORMS PER FLORIDA STATUTE 553.791, EACH PRIVATE
 PROVIDER MUST REGISTER WITH THE CITY OF WEST PALM BEACH
 PRIOR TO PREFORMING SERVICES AND BE COMPLIANT WITH F.
 S. 553.791(1)(I) TO PROVIDE SERVICES.
 PROPER NOTIFICATION MUST BE PROVIDED TO THE CITY OF
 WEST PALM BEACH IN ACCORDANCE WITH SECTION 553.791 (2),
 (3) (4) AND (5). FOR INSPECTIONS, AT LEAST (7) DAYS
 PRIOR TO THE OFFERING OF INSPECTION SERVICES, NOTICE ON
 A FORM THAT CONTAINS THE LANGUAGE FOUND IN THE STATUTE
 MUST BE TURNED IN.
  
 FL. S. 553.791 (4) (B) THE NAME, FIRM ADDRESS,
 TELEPHONE NUMBER, AND E-MAIL ADDRESS OF EACH PRIVATE
 PROVIDER WHO IS PERFORMING OR WILL PERFORM SERVICES,
 HIS OR HER PROFESSIONAL LICENSE OR CERTIFICATION
 NUMBER, QUALIFICATION STATEMENTS OR RESUMES, AND IF
 REQUIRED BY THE LOCAL BUILDING OFFICIAL, A CERTIFICATE
 OF INSURANCE DEMONSTRATING THAT PROFESSIONAL LIABILITY
 INSURANCE COVERAGE IS IN PLACE FOR THE PRIVATE
 PROVIDERS FIRM, THE PRIVATE PROVIDER AND ANY DULY
 AUTHORIZED REPRESENTATIVE IN THE AMOUNT REQUIRED BY
 THIS SECTION. SEE FL. S. 553.791(17) FOR INSURANCE
 COVERAGE.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
  
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-07-19 Cont ID  
Sent By jleahy Date 2023-07-19 Time 11:40 Rev Time 0.00
Received By jleahy Date 2023-07-19 Time 11:35 Sent To  
Notes
2023-07-19 08:32:14PLUMBING SIGNATURES PASSED.
2023-07-18 16:20:39ARCHITECTURAL SHEET SIGNATURE GOOD. 7-18-23 J WITMER

Review Stop Z ZONING
Rev No 1 Status P Date 2023-07-13 Cont ID  
Sent By cibaven Date 2023-07-13 Time 15:03 Rev Time 0.00
Received By cibaven Date 2023-07-13 Time 15:03 Sent To  
Notes
***NONE***