Plan Review Details - Permit 23060983
Plan Review Stops For Permit 23060983
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2023-07-07 Time 14:49 Sent To  
Notes
2023-07-07 15:34:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 1) THE REPAIR PLANS NEED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE AND IT HAS BE VERIFIABLE. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC
 61G1 OR FS 471 & FAC 61G15
  
 2) THE SHORING PLANS THAT HAVE BEEN PREPARED BY A
 SPECIALTY SHORING ENGINEER ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD IN WRITING AND
 SUBMITTED TO THIS OFFICE PER THE CITY OF WEST PALM
 BEACH SPECIAL INSPECTOR POLICY AND FBC 107.3.4.1
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2023-06-22 Time 10:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 14:43 Rev Time 0.00
Received By rmcdouga Date 2023-07-07 Time 14:43 Sent To  
Notes
2023-07-07 14:48:52NONE OF THE ENGINEER'S DIGITAL SIGNATURES COULD BE
 VERIFIED. ALL DOCUMENTS FROM A FLORIDA LICENSED
 ENGINEER THAT ARE SUBMITTED FOR PUBLIC RECORD ARE
 REQUIRED TO BE SIGNED AND SEALED. ELECTRONICALLY
 SUBMITTED DRAWINGS AND OTHER DOCUMENTS ARE REQUIRED TO
 HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON
 THEM. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By rmcdouga Date 2023-07-07 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2023-07-07 Time 15:34 Sent To  
Notes
2023-07-07 16:25:33THRESHOLD DOCUMENTS ARE FAILED FOR THE FOLLOWING
 REASONS.
 1) THE CONTRACTOR DID NOT PROVIDE THEIR REGISTRATION
 NUMBER.
 2) THE SPECIAL INSPECTOR DID NOT PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECTS.
  
  