| 2023-07-24 16:23:35 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23060889 |
| | 809 S FLAGLER DR |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1-THIS BUILDING IS LOCATED IN A AE FLOOD ZONE WITH A |
| | BASE FLOOD ELEVATION (BFE) OF 6 FEET BASED ON NAVD 88. |
| | THE PROPOSED WORK IS CONSIDERED A SUBSTANTIAL |
| | IMPROVEMENT. THE BUILDING SHALL HAVE THE LOWEST FLOOR |
| | FINISHED ELEVATION ELEVATED TO OR ABOVE THE BASE FLOOD |
| | ELEVATION PLUS TWO FEET. THEREFORE, THE MIN. REQUIRED |
| | FINISHED FLOOR ELEVATION IS 8 FEET. |
| | NOTE: PROVIDE SIGNED AND SEALED FLOOD HAZARD |
| | DOCUMENTATION AS REQUIRED BY SEC. 1612.5 FBC-BUILDING |
| | SHOWING COMPLIANCE. PLANS NEED TO SHOW THE FINISHED |
| | FLOOR ELEVATION. ALSO, NEED TO PROVIDE THE ELEVATION |
| | CERTIFICATE AND SURVEY SHOWING THE ELEVATIONS FOR |
| | VERIFICATION. |
| | CITY ORDINANCE 4729-17. |
| | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING |
| | CODE. |
| | SEC. 107.3.5.3 CITY AMENDMENTS. |
| | |
| | NOTE: |
| | COORDINATE WITH CITY HISTORIC PRESERVATION IF HISTORIC |
| | VARIANCE MAY BE APPLIED FOR AND BUILDING MAY RETAIN THE |
| | HISTORIC VALUE AFTER THE ALTERATION. |
| | |
| | 2- REVISE CODIFICATION INFORMATION ON SHEET CVR: |
| | A)REVISE CODE INFORMATION. PLANS NEED TO BE DESIGNED |
| | BASED ON ASCE 7-16 NOT ASCE 7-10. REVISE AS REQUIRED. |
| | NOTE: THIS APPLIES TO ALL DRAWINGS SUBMITTED WITH THE |
| | REFERENCING ASCE-10. REVISE ALL PLANS. |
| | |
| | B)CLEARLY SPECIFY TYPE OF CONSTRUCTION. SEE SEC. 602 |
| | FBC-BUILDING FOR CORRESPONDING CONSTRUCTION |
| | CLASSIFICATION AND SPECIFY ON PLANS. |
| | |
| | C)BUILDING EXPOSURE IS INCORRECT. THIS BUILDING IS |
| | LOCATED IN EXPOSURE D NOT C. REVISE AS REQUIRED. SEC. |
| | 1609.4 FBC-BUILDING. |
| | |
| | D)SPECIFY THE NOMINAL WIND SPEED AS REQUIRED BY SEC. |
| | 1603.1.4 FBC-BUILDING. |
| | |
| | E)PROVIDE THE COMPONENTS AND CLADDING WIND PRESSURE AS |
| | REQUIRED BY SEC. 1603.1.4 FBC-BUILDING. |
| | |
| | F)SPECIFY THE INTERNAL PRESSURES COEFFICIENT AS |
| | REQUIRED BY SEC. 1603.1.4 FBC-BUILDING. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR WALL |
| | FLASHING AT ALL EXTERIOR OPENINGS. SEC. 1405.4 |
| | FBC-BUILDING. |
| | |
| | 4- ENGINEER OF RECORD TO PROVIDE COMPLETE |
| | DETAILS/SPECIFICATIONS FOR WELDING OF THE DESIGNED |
| | SUPPORT ASSEMBLY TO RECEIVE NEW WINDOWS. SPECIFY |
| | WELDING AT ALL HORIZONTAL AND VERTICAL ALUMINUM FRAMING |
| | MEMBERS, INCLUDING ALUMINUM SILL PLATE SPECIFIED ON |
| | SOME WINDOWS. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | 5- PROVIDE CURRENT PRODUCT APPROVAL FOR WINDOWS TO BE |
| | INSTALLED. FLORIDA PRODUCT APPROVAL FL21334-R2 |
| | SUBMITTED WAS REVISED FOR FL21334-R4. |
| | FAC 61G20-3.001. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) WINDOW PRODUCT APPROVAL AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- PROVIDE COMPLETE SITE SPECIFIC WINDOW INSTALLATION |
| | INFORMATION AS REQUIRED BY THE LIMITATIONS OF USE ON |
| | PAGE 1 OF 11 OF PANEL WALLS PRODUCT APPROVAL FL21334 |
| | SUBMITTED. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS |
| | TO THE SUPPORT ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. |
| | SEC. 1609.1 FBC-BUILDING. |
| | |
| | 8- DIGITAL SIGNATURE COMMENTS: |
| | A)DRAWINGS HAVE AN ENGINEER'S SELF-CERTIFIED DIGITAL |
| | SIGNATURE. ENGINEER CANNOT SELF-CERTIFY THE DIGITAL |
| | SIGNATURE. THIRD PARTY CERTIFICATION IS REQUIRED BY FAC |
| | 61G15-23.004. (NOTE: ENGINEER TO CONTACT THE BOARD OF |
| | ENGINEER'S FOR SELF-CERTIFIED DIGITAL SIGNATURE |
| | QUESTIONS). |
| | |
| | B)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE |
| | TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | SEC. 61G15-23.004 F.A.C. PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |