| 2023-07-15 12:07:39 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23060804 |
| | 7/17/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FDHA- FAIR HOUSING DESIGN ACT MANUAL- 1998 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1. GENERAL/ADMINISTRATIVE COMMENTS. |
| | |
| | 1) POTABLE WATER SERVICE BACKFLOW PREVENTER & GREASE |
| | INTERCEPTORS: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | POTABLE WATER BACKFLOW PREVENTER AND THE GREASE |
| | INTERCEPTORS- SEC. 105.1 & 107.2.1 WPB. PLEASE NOTE THE |
| | SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT BE |
| | APPROVED UNTIL PERMIT APPLICATIONS FOR THE ITEMS LISTED |
| | ABOVE HAVE BEEN SUBMITTED. YOU CAN SUBMIT APPLICATIONS |
| | TBD (TO BE DETERMINED) IF YOU DO NOT HAVE CONTRACTORS |
| | SELECTED BY EMAILING COMPLETED PERMIT APPLICATIONS TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE ALL |
| | OF THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SWIMMING POOL: A SEPARATE PERMIT IS REQUIRED FOR THE |
| | POOL HOWEVER THE DETAIL ON SHEET P7-01 SHOWING POOL |
| | WASTEWATER DRAINING INTO THE SANITARY SYSTEM IS NOT IN |
| | COMPLIANCE WITH SEC. 90-126 (B)(5) WPB CODE OF |
| | ORDINANCES. PLEASE NOTE THE FOLLOWING INFORMATION. |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | -THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| | KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| | STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| | - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | 3) IRRIGATION: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | IRRIGATION SYSTEM AND SYSTEM BACKFLOW PREVENTER. A |
| | PRELIMINARY REVIEW OF SHEETS L5 & L5-A SYSTEM WAS |
| | PERFORMED UNDER THIS MASTER PLAN AND THE PLANS APPEAR |
| | INCOMPLETE PER THE FOLLOWING NOTES: |
| | |
| | A) WATER SOURCES, PUMPS, SHUTOFF VALVES, AND BACKFLOW |
| | PREVENTERS NOT SHOWN. |
| | |
| | B) PIPING RUNS, PIPE SIZES AND LOCATIONS OF SLEEVES NOT |
| | PROVIDED |
| | |
| | |
| | 2. ARCHITECTURAL COMMENTS. |
| | |
| | 4) LS1-00: PLEASE REFER TO SEC. 233 FBC ACCESSIBILITY. |
| | BASED ON SECS 233.3.1 & 233.3.1.1 AT LEAST 5% OF THE |
| | TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL BE |
| | PROVIDED WITH MOBILITY FEATURES COMPLYING WITH SECS. |
| | 809.2- 809.4 AND SHALL BE ON AN ACCESSIBLE ROUTE; AND |
| | AT LEAST 2% SHALL BE PROVIDED WITH COMMUNICATION |
| | FEATURES COMPLYING WITH 809.4. THESE REQUIREMENTS ARE |
| | SEPARATE FROM COMPLIANCE WITH THE FAIR HOUSING DESIGN |
| | ACT REQUIREMENTS. REFER TO SEC. 233.3.5 DISPERSION AND |
| | PROVIDE A LIST OR SCHEDULE ON THE PLAN SHOWING THE |
| | LOCATIONS OF THE UNITS, AND REVISE THE ARCHITECTURAL |
| | AND PLUMBING PLANS WHERE REQUIRED. |
| | |
| | 5) LS1-00, A6-35: THE APPLICABLE CODE DATA FOR THE |
| | BUILDING INDICATES THE R2 APARTMENT UNITS ARE DESIGNED |
| | IN ACCORDANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL |
| | (1998). REFER TO PAGES 7.34 & 7.35 OF THE MANUAL AND |
| | INDICATE ON BOTH PLANS WHICH DESIGN SPECIFICATION FOR |
| | THE APARTMENT BATHROOMS AND FIXTURES INSTALLATIONS HAS |
| | BEEN CHOSEN- SPECIFICATION A OR B. |
| | |
| | A) A7-04: PLEASE ADD COMPLIANCE DETAILS FOR THE |
| | SHOWERS- PAGES 7.56- 7.59 FHDA MANUAL. |
| | |
| | 6) LS1-00: AS NOTED IN COMMENT #4 THERE ARE DESIGN |
| | DIFFERENCES BETWEEN AN FBC ACCESSIBLE (ADA COMPLIANT) |
| | DWELLING UNIT AND A FHDA COMPLIANT UNITS HOWEVER SHEETS |
| | A6-35 & A7-04 WHICH ARE INTENDED TO DEMONSTRATE FAIR |
| | HOUSING COMPLIANCE ARE TITLED ENLARGED UNIT |
| | ACCESSIBILITY PLANS & APARTMENT UNIT ACCESSIBILITY |
| | STANDARDS WHICH CAN BE MISLEADING. PLEASE REFER TO SEC. |
| | 809.4 FBC ACCESSIBILITY AND PROVIDE SEPARATE ENLARGED |
| | ACCESSIBLE UNIT DRAWINGS WITH THE FOLLOWING COMPLIANCE |
| | DETAILS PER SEC. 603- 610 FBC ACCESSIBILITY. PLEASE |
| | NOTE SOME OF THE REQUIRED DETAILS ARE CURRENTLY SHOWN |
| | ON A7-05. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| | |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | |
| | F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| | |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3. |
| | |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES |
| | 604.5.1 & 604.5.2. |
| | |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. |
| | |
| | K) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | BATHTUBS- SEC. 607.2. |
| | |
| | L) BATHTUB PERMANENT OR REMOVAL SEAT DETAILS- SEC. |
| | 607.3. |
| | |
| | M) BATHTUB GRAB BAR DETAILS- SEC. 607.4. |
| | |
| | N) BATHTUB CONTROLS DETAILS- SECS. 607.5- 607.6. |
| | |
| | O) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | SHOWER- SECS. 608.2.1 & 608.2.2. |
| | |
| | P) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 AND |
| | 608.3.2. |
| | |
| | Q) LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS IN |
| | THE SHOWERS- SECS. 608.5.1 & 608.5.2. |
| | |
| | R) LOCATIONS OF ACCESSIBLE SHOWER SEATS AND MOUNTING |
| | DETAILS- SECS. 610.3- 610.4. |
| | |
| | 7) A6.05: SHOW THE DIMENSIONS OF THE WATER CLOSET AND |
| | LAVATORY CLEAR FLOOR SPACES- SECS. 604.3 & 606.2 FBC |
| | ACC. |
| | |
| | 8) A6.05: THE RESTROOM DOORS SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACES FOR THE LAVATORIES- SEC. 603.2.3 FBC |
| | ACC. |
| | |
| | 9) A1-01A: ENLARGED ACCESSIBLE PUBLIC RESTROOM FLOOR |
| | PLAN DRAWINGS NOT PROVIDED- SEC. 603- 604 FBC ACC. |
| | |
| | 10) LS1-00: PLUMBING FIXTURE CALCULATIONS FOR THE MIXED |
| | OCCUPANCY BUILDING ARE REQUIRED IN COMPLIANCE WITH |
| | TABLE 403.1 & SEC. 403.1.1 FBC P. PLEASE PROVIDE A |
| | SCHEDULE THAT ITEMIZES THE REQUIRED AND PROVIDED NUMBER |
| | OF FIXTURES. PLEASE NOTE THAT WHERE DRINKING FOUNTAINS |
| | ARE REQUIRED A MINIMUM OF TWO- ONE HI AND ONE LO- SHALL |
| | BE PROVIDED- SEC. 410.3 FBC P. THE ARCHITECTURAL AND |
| | PLUMBING PLANS SHOW ONE DRINKING FOUNTAIN AT THE PUBLIC |
| | RESTROOMS WHICH DOES NOT MEET COMPLIANCE UNLESS THE |
| | FOUNTAIN MEETS EXCEPTION 1 AND HAS TWO SEPARATE SPOUTS- |
| | HI & LO. NO FOUNTAIN WAS SPECIFIED IN THE FIXTURE |
| | SCHEDULES- SHEET P0-02. |
| | |
| | A) A1-01B: THE DRINKING FOUNTAIN AT THE PUBLIC RESTROOM |
| | CORRIDOR IS PROTRUDING INTO THE CIRCULATION PATH AND |
| | SHALL BE EITHER BE RECESSED IN A NICHE OR BARRIERS ON |
| | EACH SIDE SHALL BE PROVIDED- SEC. 307.2 FBC ACC. |
| | |
| | B) A1-01B: PLEASE SHOW THE CLEAR FLOOR DIAGRAM AND |
| | DIMENSIONS FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN |
| | POSITIONED FOR A FORWARD APPROACH- SEC. 606.2 FBC ACC. |
| | |
| | C) A7-05: SHOW THE SPOUT HEIGHT FOR THE HI (STANDING |
| | PERSONS) DRINKING FOUNTAIN- SEC. 602.7 FBC ACC. |
| | |
| | 11) LS-01, A1-05B & A6-06: THE POOL WILL BE UNDER |
| | SEPARATE PERMIT HOWEVER A PRELIMINARY REVIEW OF THE |
| | POOL BATHROOMS AND PLUMBING IS REQUIRED. PLEASE REFER |
| | TO SEC. & TABLE 403.6 AND PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS. THE PLANS SHOW ONE POOL RESTROOM BY THE |
| | POOL AND ONE RESTROOM AT THE CLUB ROOM. PLEASE NOTE |
| | THAT SEC. 451.6.1 STATES THAT POOLS WITH A BATHING LOAD |
| | OF 20 PERSONS OR LESS MAY UTILIZE A UNISEX RESTROOM. |
| | PLEASE PROVIDE BATHING LOAD CALCULATIONS IN ACCORDANCE |
| | WITH SEC. 454.1.1.1 FBC B. |
| | |
| | B) PLEASE REFER TO SEC. 403.6 AND PROVIDE A URINAL AND |
| | DIAPER CHANGING TABLE FOR THE POOL BATHROOM. A FLOOR |
| | DRAINS AND HOSE BIB ARE ALSO REQUIRED FOR THE BATHROOMS |
| | ACCORDING TO SECS. 454.1.6.1.3 & 454.1.6.1.4 FBC |
| | BUILDING. PLEASE NOTE THE HOSE BIB CAN BE PROVIDED IN |
| | OR WITHIN 25 FT. OF THE RESTROOM. PLEASE REVISE THE |
| | PLANS TO SHOW COMPLIANCE. |
| | |
| | C) PLEASE SHOW THE POOL SHOWER LOCATION- SEC. 454.1.6.2 |
| | FBC B. |
| | |
| | 12) LS-01, A1-05B & A6-06: CONCERNING THE CLUBROOM AND |
| | ROOFTOP LOUNGE REFER TO COMMENT #10. |
| | |
| | 13) A1-05B: THE POOL RESTROOM DOOR SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE FOR THE LAVATORY- SEC. 603.2.3 |
| | FBC ACC. |
| | |
| | 14) A1-01B & A7.05: SHOW THE CLEAR FLOOR SPACE FOR THE |
| | WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN AND THE SPOUT |
| | HEIGHT OF THE HI (STANDING PERSONS) FOUNTAIN- SEC. |
| | 602.2 & 602.7 FBC ACC. |
| | |
| | 3. PLUMBING COMMENTS. |
| | |
| | 15) P2-00A: TWO-WAY CLEANOUTS FOR THE 3 & 4-INCH |
| | BUILDING DRAINS ARE REQUIRED AT A POINT 30 INCHES |
| | BEYOND THE EXTERIOR WALL OF EACH UNIT- SEC. 708.1.3, |
| | 708.1.8 EXCEPTION 2 FBC P. |
| | |
| | 16) P2-00A & P2-00B: IT APPEARS CLEANOUTS AT 100 FT. |
| | INTERVAL SPACINGS ARE MISSING FOR THE 6-INCH SANITARY |
| | SEWER LINE ON THE NORTH SIDE OF THE BUILDING- SEC. |
| | 708.1.2 FBC P. |
| | |
| | 17) P2-00A & P-200B: PROVIDE A GROUND FLOOR SANITARY |
| | DRAINAGE AND VENT ISOMETRIC FOR THE GROUND FLOOR WITH |
| | WASTE AND SOIL STACK RISER LOCATIONS NUMBERED TO MATCH |
| | WITH THE NUMBERED RISERS SHOWN ON SHEETS P6-02 & P6-03- |
| | SECS. 107.2.1, 107.3.5.1.3 WPB & SEC. 710.1 FBC P. |
| | |
| | 18) P2-00A: SHOW UNDERGROUND STORM DRAIN PIPING RUNS |
| | INCLUDING PIPE SIZES AND GPM FLOWS AS SHOWN ON P-200B- |
| | SEC. 1106.2 FBC P. |
| | |
| | 19) P2-00A & P-200B: SHOW THE WATER HEATER DRAIN PAN |
| | LINE RUNS AND TERMINATION LOCATIONS- SEC. 504.7.2 FBC |
| | P. |
| | |
| | 20) P2-00A, P2-00B, P2-09A, P2-09B: PROVIDE A STORM |
| | DRAIN RISER DRAWING SHOWING VERTICAL AND HORIZONTAL |
| | PIPE RUNS AND SIZES FROM ROOFTOP TO DISPOSAL LOCATIONS- |
| | SEC. 1106.2 & 1106.3 FBC P. PLEASE INCLUDE GPM FLOWS, |
| | CLEANOUT LOCATIONS AND AC CONDENSATE PIPING POINTS OF |
| | CONNECTIONS TO THE SYSTEM- SECS. 314.2.1, 1101.8 FBC P. |
| | |
| | 21) P2-00A, P2-00B & C2-3: THE PLUMBING UNDERGROUND |
| | PLANS DO NOT MATCH WITH THE WATER AND WASTEWATER CIVIL |
| | PLAN. THE PLUMBING PLANS DO NOT SHOW SANITARY DRAIN |
| | CONNECTIONS INTO TEMPORARY LIFT STATIONS, AND THE CIVIL |
| | PLANS DO NOT SHOW THE GREASE INTERCEPTORS, OR THE |
| | SANITARY SER LINE ON THE NORTH SIDE OF THE BUILDING TO |
| | NAME A FEW OF THE MANY INCONSISTENCIES- SEC. 107.2.1 |
| | WPB. PLEASE CORRECT THE PLANS. AT THIS TIME THE CIVIL |
| | PLANS WILL BE EXCLUDED FROM FURTHER PLUMBING REVIEW. |
| | |
| | 22) P0-02 & P2-00B & GREASE INTERCEPTORS GI-1. |
| | |
| | A) P2-00B & P7-01: THE CLEANOUTS FOR THE GREASE |
| | INTERCEPTORS REQUIRE HEAVY DUTY TRAFFIC LIDS. PLEASE |
| | SPECIFY MAKES AND MODELS- SEC. 305.7 FBC P. |
| | |
| | B) P0-02: THE INTERCEPTOR EQUIPMENT SCHEDULE REFERS TO |
| | SHEET P-702 WHICH WAS NOT INCLUDED WITH THE UPLOADED |
| | PLAN SET- SEC. 107.2.1 WPB. |
| | |
| | C) P2-00B: THE PLAN DOES NOT IDENTIFY WHICH PLUMBING |
| | FIXTURES AND APPLIANCES ARE DISCHARGING INTO THE GREASE |
| | WASTE LINE. PLEASE PROVIDE A KITCHEN PLUMBING FIXTURE |
| | EQUIPMENT PLAN AND SCHEDULE- SEC. 107.2.1 WPB. PLEASE |
| | NOTE THE PLAN APPEARS TO SHOW DRAINAGE FROM A |
| | 3-COMPARTMENT SINK AND A MOP SINK DISCHARGING INTO THE |
| | SANITARY LINE INSTEAD OF THE GREASE WASTE LINE- SEC. |
| | 1003.3.1 FBC P. |
| | D) P2-00B: REFER TO SEC. 1003.9 FBC P AND PROVIDE |
| | VENTING FOR THE INTERCEPTOR. PLEASE NOTE THE AAV (NOTE |
| | 2) CANNOT BE USED AS THE VENT FOR THE INTERCEPTORS- |
| | SEC. 918.8 FBC P. |
| | |
| | 23) P2-00B GREASE INTERCEPTOR GI-2: THE USE OF THE |
| | GREASE INTERCEPTOR FOR TRASH ROOM DRAINAGE DOES NOT |
| | APPEAR TO BE IN COMPLIANCE WITH SEC. 1003.3.1 FBC P. |
| | PLEASE CLARIFY THE USE OF THE INTERCEPTOR. |
| | |
| | A) PROVIDE SIZING CALCULATIONS IN ACCORDANCE WITH SEC. |
| | 1003.3.5 FBC P. |
| | |
| | B) P2-00B & P7-01: THE CLEANOUTS FOR THE GREASE |
| | INTERCEPTORS REQUIRE HEAVY DUTY TRAFFIC LIDS. PLEASE |
| | SPECIFY MAKES AND MODELS- SEC. 305.7 FBC P. |
| | |
| | C) P2-00B: REFER TO SEC. 1003.9 FBC P AND PROVIDE |
| | VENTING FOR THE INTERCEPTOR. PLEASE NOTE THE AAV (NOTE |
| | 2) CANNOT BE USED AS THE VENT FOR THE INTERCEPTORS- |
| | SEC. 918.8 FBC P. |
| | |
| | 24) P2-00B & P5-01: THE DISCHARGES FROM THE ELEVATOR |
| | SUMP PUMPS SHALL BE INDIRECTLY CONNECTED TO A WASTE |
| | RECEPTOR WHICH IS EITHER A FLOOR DRAIN, FLOOR SINK, HUB |
| | DRAIN OR STANDPIPE. DISPOSAL AT THE MOP SINK IS NOT IN |
| | COMPLIANCE - SEC. 3002.4 FBC B, & SECS. 202 & 802.3 FBC |
| | P. |
| | |
| | 25) P2-01A & P2-01B: PROVIDE A FIRST-FLOOR WATER |
| | ISOMETRIC DRAWING WITH WATER RISER LOCATIONS NUMBERED |
| | TO MATCH WITH THE NUMBERED RISERS SHOWN ON SHEET P6-01- |
| | SECS. 107.2.1, 107.3.5.1.3 WPB & SEC. 604.1 FBC P. |
| | |
| | 26) P2-01B: SHOW THE WATER SERVICE ENTRANCE LOCATION |
| | AND MAIN SHUTOFF VALVE FOR THE BUILDING- SEC. 603.1- |
| | 603.2.1 & 606.1 FBC P. |
| | |
| | 27) P2-01B: SHOW THE WATER FEED LINE TO THE RETAIL |
| | RESTROOMS AT DETAIL 4/P5.01- SEC. 107.2.1 WPB. |
| | |
| | 28) P2-01B: PLEASE PROVIDE WATER DISTRIBUTION DESIGN |
| | CRITERIA- SEC. 604.3 FBC P. |
| | |
| | 29) P4-01: ENLARGED SANITARY DRAINAGE/VENT AND WATER |
| | RISER DRAWINGS NOT PROVIDED FOR THE TYPICAL APARTMENT |
| | UNITS- SEC. 107.3.5.1.3 WPB. |
| | |
| | 30) P4-01: TWO-WAY CLEANOUTS FOR THE 3 & 4-INCH |
| | BUILDING DRAINS ARE REQUIRED AT A POINT 30 INCHES |
| | BEYOND THE EXTERIOR WALL OF EACH UNIT- SEC. 708.1.3, |
| | 708.1.8 EXCEPTION 2 FBC P. |
| | |
| | 31) P2-08B, P5-01: ENLARGED SANITARY DRAINAGE/VENT |
| | PLANS FOR THE POOL AND CLUBROOM/ROOFTOP LOUNGE |
| | RESTROOMS NOT PROVIDED- SEC. 107.3.5.1.3 WPB. |
| | |
| | 32) P5-01: ENLARGED SANITARY DRAINAGE/VENT AND WATER |
| | ISOMETRIC DRAWINGS NOT PROVIDED FOR THE 1ST FLOOR |
| | PUBLIC, RETAIL, POOL AND CLUBROOM/LOUNGE BATHROOMS- |
| | SEC. 107.3.5.1.3 WPB. |
| | |
| | 33) P5-01: COLD OR TEMPERED WATER SHALL BE DELIVERED |
| | FROM THE LAVATORIES- SEC. 419.5. |
| | |
| | 34) P5.01: THE 1/2-INCH HOT WATER FIXTURE SUPPLY PIPES |
| | TO THE RETAIL RESTROOM LAVATORIES ARE EXCEEDING THE |
| | MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER |
| | SOURCES- TABLE C404.5.1 FBC ENERGY. |
| | |
| | 35) P4-01 & P5-01: A MEANS OF LIMITING THE TEMPERATURE |
| | OF THE HOT WATER DELIVERY TO THE FIXTURES IS REQUIRED |
| | OTHER THAN THE WATER HEATER THERMOSTAT- SEC. 607.1.1 |
| | FBC P. PLEASE PROVIDE MASTER THERMOSTATIC MIXING |
| | VALVES. |
| | |
| | 36) P6-02 & P6-03: THE VENT STACKS SHALL CONNECT TO THE |
| | BASES OF THE DRAINAGE STACKS AT A POINT BELOW THE |
| | LOWEST HORIZONTAL BRANCH. CONNECTIONS AT THE LAVATORY |
| | DRAINS DO NOT MEET COMPLIANCE- SECS. 904.2 & 904.4 FBC |
| | P. |
| | |
| | 37) P2-09A, P2-09B: AS PREVIOUSLY NOTED IN COMMENT #10 |
| | A STORM RISER ISOMETRIC DRAWING IS REQUIRED- SEC. |
| | 107.3.5.1.3 WPB. |
| | |
| | A) P2-09A, P2-09B: SECONDARY/EMERGENCY ROOF DRAINAGE |
| | WILL BE HANDLED BY OVERFLOW SCUPPERS AS STATED IN NOTE |
| | B. THE LOCATIONS OF THE SCUPPERS SHALL BE SHOWN ON THE |
| | PLANS, AND A CONSTRUCTION DETAIL SHOWING THE SCUPPER |
| | OPENING DIMENSIONS, AND HEIGHT ABOVE ROOF ETC. SHALL BE |
| | PROVIDED- SECS. 1108.1- 1108.3 FBC P. |
| | |
| | 38) P0-01: PLUMBING FIXTURE CALCULATIONS FOR THE MIXED |
| | OCCUPANCY BUILDING ARE REQUIRED IN COMPLIANCE WITH |
| | TABLE 403.1 & SEC. 403.1.1 FBC P. PLEASE PROVIDE A |
| | SCHEDULE THAT ITEMIZES THE REQUIRED AND PROVIDED NUMBER |
| | OF FIXTURES. PLEASE NOTE THAT WHERE DRINKING FOUNTAINS |
| | ARE REQUIRED A MINIMUM OF TWO- ONE HI AND ONE LO- SHALL |
| | BE PROVIDED- SEC. 410.3 FBC P. THE ARCHITECTURAL AND |
| | PLUMBING PLANS SHOW ONE DRINKING FOUNTAIN AT THE PUBLIC |
| | RESTROOMS WHICH DOES NOT MEET COMPLIANCE UNLESS THE |
| | FOUNTAIN MEETS EXCEPTION 1 AND HAS TWO SEPARATE SPOUTS- |
| | HI & LO. NO FOUNTAIN WAS SPECIFIED ON SHEET P0-02. |
| | |
| | 39) P0-01, P2-08B: THE POOL WILL BE UNDER SEPARATE |
| | PERMIT HOWEVER A PRELIMINARY REVIEW OF THE POOL |
| | BATHROOMS AND PLUMBING IS REQUIRED. PLEASE REFER TO |
| | SEC. 403.6 AND PROVIDE A URINAL AND DIAPER CHANGING |
| | TABLE FOR EACH POOL BATHROOM. FLOOR DRAINS AND HOSE |
| | BIBS ARE ALSO REQUIRED FOR THE BATHROOMS ACCORDING TO |
| | SECS. 454.1.6.1.3 & 454.1.6.1.4 FBC BUILDING. PLEASE |
| | NOTE THE HOSE BIB CAN BE PROVIDED IN OR WITHIN 25 FT. |
| | OF EACH RESTROOM. PLEASE REVISE THE PLANS TO SHOW |
| | COMPLIANCE. |
| | |
| | 40) P2-08B, P6-01, P6-02, P-6-03: PROVIDE PLUMBING |
| | PLANS AND RISERS FOR THE POOL AND CLUBHOUSE RESTROOMS |
| | AND THE BAR SINK- SEC. 107.2.1 & SEC. 107.3.5.1.3 WPB. |
| | |
| | 41) P0-01: PLEASE PROVIDE TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLIES FOR PLUMBING PIPES PENETRATING |
| | FIRE-RATED WALLS AND FLOORS- SEC. 315.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |