| Plan Review Stops For Permit 23060788 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-28 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-28 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2023-07-28 08:52:22 | AWNING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING A2.1.1 NEEDS TO BE SIGNED AND SEALED AND | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND | | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | 2) DRAWING A2.1.1 NEEDS TO SHOW THAT FIRE SPRINKLERS | | | ARE REQUIRED (AS NOTED BY THE FIRE REVIEW) FBC | | | 903.2.1.2 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-07-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-05 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-05 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2023-07-05 14:42:36 | AWNING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS NEED TO BE SIGNED AND SEALED AND SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-06-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-06-23 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2023-06-23 11:25:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF A NEW EXPANSIVE CANOPY OVER | | | AN ASSEMBLY OCCUPANCY WITH EXISTING FIRE SPRINKLER | | | PROTECTION, WITHIN THE EXISTING ASSEMBLY OCCUPANCY. | | | | | | THERE IS AN INDICATION A FLAME CERT WHICH IS REQQUIRED, | | | HOWEVER, THERE NO INDICATION OF INSTALLING FIRE | | | SPRINKLER PROTECTION UNDER THIS NEW CANOPY. AN | | | INDICATION OF THE SPEC SHEET FOR THE FLOOR | | | UNDERLAYMENT, | | | | | | PER NFPA 101, CH 12, 42 AND NFPA 13, FIRE SPRINKLER | | | PROTECTION IS REQUIRED. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A NOTE OF | | | ACKNOWLEDGMENT TO PROVIDE FIRE SPRINKLER PROTECTION | | | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-27 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-07-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-05 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-06-20 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-07-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-28 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-28 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2023-07-28 08:53:52 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING A2.1.1 DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-07-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-05 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-05 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2023-07-05 14:44:42 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SIGNED AND SEALED BY DON ARPIN P.E. DO NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-07-03 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
2023-07-03 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
2023-07-03 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2023-07-03 14:45:25 | PLEASE PROVIDE A FLOOR PLAN AND ELEVATIONS OF THE | | | BUILDING WITH THE PROPOSED AWNING TO SHOW HOW THE | | | AWNING IS INTEGRATED WITH THE BUILDING. NOTE, VINYL AND | | | PLASTIC AWNINGS ARE PROHIBITED UNLESS TREATED IN A | | | MANNER SO AS TO APPEAR SIMILAR TO CANVAS OR OTHER | | | NATURAL MATERIALS IN TEXTURE AND COLOR. | | | | | | CLAUDIA D. IBAVEN | | | CITY URBAN DESIGNER / ZONING AND PLANNING | | | [email protected] | | | 561-822-1402 | | | |
|
|