Plan Review Details - Permit 23060632
Plan Review Stops For Permit 23060632
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By rperdomo Date 2023-07-19 Time 15:35 Rev Time 0.00
Received By rperdomo Date 2023-07-19 Time 14:48 Sent To  
Notes
2023-07-19 15:57:07FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE EQUIPMENT SPECIFICATIONS. FBC 107.3.5
 A. GENERAC GENERATOR
 B. IEM SWITCHGEAR EQUIPMENT
  
 END OF COMMENT
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By clfranci Date 2023-07-14 Time   Rev Time 0.00
Received By clfranci Date 2023-07-14 Time   Sent To  
Notes
2023-07-14 10:06:35THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) GENERATOR SPECS MUST BE SUBMITTED WITH THE PLANS.
  
 2)THERE IS A FUEL TANK INDICATED ON THE PLANS, IF THE
 FUEL TANK IS SEPARATE FROM THE GENERATOR THE SPECS FOR
 THE FUEL TANK MUST BE SUBMITTED.
  
 3)THIS BUILDING HAS A FIRE ALARM SYSTEM BUT THERE IS NO
 INDICATION OF THE GENERATOR BEING ATTACHED TO THE FIRE
 ALARM SYSTEM. PLEASE REFER TO NFPA 110 AND NFPA 72 TO
 INDICATE IF THESE WILL BE REQUIRED TO BE CONNECTED OR
 IF THE GENERATOR IS REQUIRED TO BE MONITORED PER THE
 CODES.
  
 4)IF THE GENERATOR IS REQUIRED TO BE CONNECTED AND
 MONITORED BY THE FIRE ALARM SYSTEM, SEPARATE FIRE ALARM
 DRAWINGS MUST BE SUBMITTED TO THE CITY.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-07 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-07-22 Cont ID  
Sent By cmontell Date 2023-07-22 Time 09:40 Rev Time 0.00
Received By cmontell Date 2023-07-22 Time 09:40 Sent To  
Notes
2023-07-22 09:41:13MECHANICAL PLAN REVIEW FAIL
  
 1- NEED GENERATOR SPECS FBC SEC 107
  
 CHRIS MONTELLO
 561-805-6733

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By ecolon Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***